GeNeRAL INStALLAtION INFORMAtION  

BeFORe yOu StARt

Read this homeowner manual thoroughly and follow all 

instructions  carefully.  Inspect  all  contents  for  shipping 

damage and immediately inform your dealer if any damage 

is found. Do not install any unit with damaged, incomplete, 

or substitute parts. Check your packing list to verify that all 

listed parts have been received.

The following factors should be taken into consideration:

  This insert should have sufficient access for its safe 

operation and maintenance.

  The flow of combustion and ventilation air must not be 

obstructed.

  Minimum clearances to combustibles, such as mantels, 

must be maintained. 

Refer to Pages 8 and 9, Figures 3 

and 4.

  Never obstruct the front opening of the insert.

  Do  not  install  in  the  vicinity  where  gasoline  or  other 

flammable liquids may be stored.

  These  units  can  be  installed  in  a  bedroom.  Refer  to 

National Fuel Gas Code ANSI Z33.1/NFPA 54 (current 

edition),  the  Uniform  Mechanical  Code  (current  edi-

tion), and Local Building Codes for specific installation 

requirements.

IMPORtANt: your direct vent insert was designed to 

be installed in an existing wood burning fireplace. the 

location and clearances are subject to local building 

codes

.

INSeRt APPLIcAtIONS

Before  installing  the  gas  fireplace  insert,  consider  the 

functioning needs of the fireplace. Confirm the size of the 

fireplace cavity, the design of the chimney, and the avail-

ability of the gas supply and electricity.

IMPORtANt: your  direct  vent  insert  is  designed  to 

be  only  vented  vertically  with  a  minimum  height  of 

10 feet.

When the unit is installed into a wood burning fireplace, 

the minimum distance the mantel can be placed above the 

fireplace is governed by local building codes applicable to 

wood burning fireplaces. Consult local authorities having 

jurisdiction  for  these  clearances. The  underside  of  the 

mantel will become warm. Use only finishes which are heat 

resistant and do not discolor.

cLeARANceS
MINIMuM FIRePLAce SIZe/cLeARANceS 

tO cOMBuStIBLeS

W

ARNING

The  dimensions  shown  on 

Pages  8  and  9, 

Figures 3 and 4

, are minimum clearances to 

maintain  when  installing  this  heater.  Follow 

these  instructions  carefully  to  ensure  safe 

installation. Failure to follow instructions exactly 

can create a fire hazard.

Содержание VLI31DVNTSC

Страница 1: ...r assistance or additional information consult a qualified installer service agency or the gas supplier This appliance may be installed in an aftermarket permanently located manufactured home USA only...

Страница 2: ...l Installation 16 Electrical Wiring 16 Command Center Wall Installation 17 Wall Switch Installation 17 Light Bulb Installation 17 Log Placement 19 Surround Installation 22 Operating Instructions 23 To...

Страница 3: ...by a qualified service person with glass door properly seated and sealed combustion leakage can occur CARBON MONOXIDE POISONING Early signs of carbon monoxide poisoning are similar to the flu with he...

Страница 4: ...fireplace with glass door removed cracked or broken Code Approval Direct Vent type appliances draw all combustion air from outside of the dwelling through the vent pipe These appliances have been test...

Страница 5: ...s product SPECIFICATIONS Figure 1 VLIDV Series Fireplace Insert Controls Command Center HIGH ELEVATIONS Input ratings are shown in BTU per hour and are certified without deration for elevations up to...

Страница 6: ...sert insert dimensions 834009 VLI31 dims 20 6QE 513 mm 9 6 251 mm 4 102 mm 2 6QE 56 mm 7 6 194 mm 15 6QE 389 mm 3 76 mm 16 6QE 411 mm 6 6M 172 mm 2556M 641 mm 2856 714 mm 20 6M 527 mm Figure 2 VLIDV F...

Страница 7: ...specific installation requirements IMPORTANT Your direct vent insert was designed to be installed in an existing wood burning fireplace The location and clearances are subject to local building codes...

Страница 8: ...de Wall Combustible Mantel Top Facing Side Facing 3 4 19 mm Maximum Depth Combustible Facing 42 1067 mm Minimum 10 254 mm Minimum 12 305 mm Minimum FP1947 insert clearances 9 08 12 305 mm 9 228 mm FP2...

Страница 9: ...rs on HIGH the first time you use it Place the fan in the OFF position during this time P ZERO CLEARANCE REQUIREMENTS Insulation Damper Smoke Shelf Masonry Lining or Refractory Screen Metal or Glass D...

Страница 10: ...ing installation Failure to do so could result in serious injury property damage or loss of life Operation of improperly installed and maintained venting system could result in serious injury property...

Страница 11: ...e orifice for use at high altitude contact your dealer High Temp Silicone FP1923 exhaust pipe 9 08 3 and 3 UL 1777 Gas Liner Apply high temperature silicone to lines on both ends and secure with two 2...

Страница 12: ...mmended block off plate noncombustible metal Prevents odors from chimney entering room UL 127 Solid Fuel Z C Firebox Figure 8 Inlet and Exhaust Reline NOTE You may use either reline configuration with...

Страница 13: ...r of Step 2 6 Re attach glass door in reverse order NOTE The VLIDV has an adjustable baffle and may be adjusted as needed by loosening four 4 screws Figure 10 INTAKE MANIFOLD VENT INSTALLATION Before...

Страница 14: ...ou must reduce incoming gas pressure to between 11 and 13 inches of water If you do not reduce incoming gas pressure burner system regula tor damage could occur Install external regulator with the ven...

Страница 15: ...ied with Appliance Tee Joint Pipe Nipple Cap Figure 12 Gas Connection A manual shut off valve is factory installed upstream of the appliance Union tee and plugged 1 8 NPT pressure tapping point should...

Страница 16: ...heck for gas leaks Electrical Wiring General 1 This fireplace is equipped with the Signature Control valve which operates on 6 volts The A C module plugs into an A C power supply Four 4 AA batteries a...

Страница 17: ...l cover provided and screw to junction box WALL SWITCH INSTALLATION The wall switch wire connection is located off the 2 ft wire harness from the control box to the command center Fig ure 15 The conne...

Страница 18: ...Ground Plug in Connector Control Board to Solenoid Gas In Gas Out Pilot Gas Tubing Valve A C Module FP2679 SCS wiring diagram To Outlet Optional Aux 300 Watts Max 300 Watts Max 300 Watts CAUTION Elect...

Страница 19: ...only parts specifically approved for this heater may result in property damage or personal in jury PLACE ROCK WOOL EMBER MATE RIAL IN FIREBOX Break up rock wool ember material into dime sized pieces P...

Страница 20: ...og 4 with the pointed end of the log to the left Place the log on the key provided on the top of the frint of log 2 and position it so the pointed end protrudes through and rests on the bottom of the...

Страница 21: ...I31 log 7 Log 7 LG834 Figure 22 7 Hold Log 7 with the pointy end of the log down and the knot in the log facing forward Place the right end on the key provided on the top of log 5 The pointy end of th...

Страница 22: ...stallation INSTALL SURROUND 1 Remove glass door assembly Page 39 Figure 54 2 Align cast or beveled surround holes with insert and attach with screws provided 3 Re attach glass door assembly 4 Attach f...

Страница 23: ...hone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will not fu...

Страница 24: ...s go to next step 4 Press the master switch to the ON position Within eight 8 seconds it will beep once This indicates the system is ready 5 Press ON button Sparker will spark and pilot flame will lig...

Страница 25: ...Low battery Indication for Transmitter X Child Proof Lock out X LCD Backlight X Security Codes 16 X Countdown 6 hr Timer X Standard Thermostatic Control Mode X Smart Mode Thermostat Auto Flame Blower...

Страница 26: ...ate if unattended You may disable this feature if you wish NOTE By disabling this feature your fireplace may con tinue to operate unattended 2 When the master switch is in the ON position press ing th...

Страница 27: ...c until manual reset Self Diagnostics Chart The Command Center has a self diagnostic LED enabling you to troubleshoot problems and potentially avoid a service call Please refer to the charts below for...

Страница 28: ...t arrows The blue LED backlight lights up for 8 seconds when any of the touch buttons is pressed The menus include TIMER THERMO LIGHT FAN and AUX The adjustment arrows include ON up and OFF down Their...

Страница 29: ...en LED on the Command Cen ter will flash for 10 seconds FP2649 set privace code FP2650 command ctr ctrl brd RF Receiver ON OFF Control Board FP2650 command ctr ctrl brd Battery Door Master Switch ON L...

Страница 30: ...Timer Mode a Push and hold the TIMER button for 3 seconds Or b Use the OFF down buttons to decrease the Set Time to zero Or FP2651 Manual mode FP2652 Timer mode c Slide down on the arrow buttons to e...

Страница 31: ...this setting and the blower is still off see blower On Delay and Off Delay in the next section TOUCH SCREEN REMOTE CONTROL OPERATION FP2655 blower speed control 4 After the signal is sent the ON up an...

Страница 32: ...will flash once to indicate that the setting has changed to B 2 When the current setting is B pressing TIMER button and THERMO button at the same time for 3 seconds will switch to A Mode The touch ar...

Страница 33: ...lank 2 Check battery installation or re place batteries 3 LCD display shows funny display 3 Reset the transmitter see Reset ting the Transmitter section 4 Appliance does not come on 2 The transmitter...

Страница 34: ...at sea level The burner on Natural Gas models may be adjusted for high altitude as follows To increase air mixture open the shutter more This will reduce soot formation Figure 40 To decrease air mixtu...

Страница 35: ...s frame from insert by releasing two latches on top of insert and lifting the door up and off the unit Figure 42 3 Set glass frame aside 4 Re install in reverse order FP2680 Figure 42 Glass Frame Remo...

Страница 36: ...ted on the right and left 6 Unfasten the brick support plate fastened to the burner Brick Panels Glass Door Assembly Brick Support Blower Assembly FP1963 Figure 43 Blower Removal and Assembly Light Bo...

Страница 37: ...l paint curing of the appliance can also leave a slight film on the glass This is a temporary problem CLEANING and MAINTENANCE FP2453 hooded pilot flames Sensor Thermopile FP2453 Figure 45 Typical Pil...

Страница 38: ...s shut off to shut off gas to heater See step To Turn Off Gas Page 25 Let heater cool for 15 minutes Remove faceplate see instructions included with face plate and glass Pages 37 38 3 Carefully remove...

Страница 39: ...83D4009 VLI31 Fireplace Insert 39 REPLACEMENT PARTS 8 11 12 15 24 25 27 834009 VLI31 parts 26 10 9 23 28 30 34 33 32 19 18 37 12 14 20 42 21 16 38 38 22 11 17 13 35 44 43 1 2 3 4 6 5 7 29...

Страница 40: ...K 83D3007K 24 Left Brick Liner 1 83D4018 83D4018 25 Rear Brick Liner 1 83D4020 83D4020 26 Right Brick Liner 1 83D4019 83D4019 27 Glass Door Assembly 1 83D1252 83D1252 28 Control Box 1 80D0018 80D0018...

Страница 41: ...ert 41 REPLACEMENT PARTS Optional Accessories Description VLI31 Cast Iron Surround HAR31CB Cast Iron Eyebrow HE31CB Cast Iron Face Door Kit PLY31CB SCS Wall Mount Extension Kit not shown SCSWEK 15ft w...

Страница 42: ...ith the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed Massachusetts Residents Only Please read...

Страница 43: ...mited Lifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner as...

Страница 44: ...ficiency Ratings Model EnerGuide Ratings Steady State D O E Fireplace Efficiency Fan OFF Fan ON AFUE VLI31DVNTSC 67 5 73 5 74 5 66 4 VLI31DVPTSC 73 9 79 8 80 8 74 6 Vermont Castings Group 149 Clevelan...

Отзывы: