background image

4

83D4009

VLI31 Fireplace Insert

NOte ReGARDING VeNteD PRODuctS

This product must be installed by a licensed plumber or gas fitter 

when installed within the Commonwealth of Massachusetts.
Any  residence  with  a  direct  vent  product  must  have  a  CO 

detector installed in the residence.
Installation  of  the  fireplace  or  vented  gas  log  in  the  State  of 

Massachusetts requires the damper to be permanently removed 

or welded in the fully open position.
In addition, a naturally vented gas log may not be installed in a 

bedroom or bathroom in the State of Massachusetts.
Flex line installation must not exceed 36 inches and must have 

a T shutoff valve. 

NOte ReGARDING VeNt FRee PRODuctS

This product must be installed by a licensed plumber or gas fitter 

when installed within the Commonwealth of Massachusetts.
In  addition,  vent  free  products  may  not  be  installed  in  a 

bedroom or bathroom regardless of size or type in the State of 

Massachusetts.
Flex line installation must not exceed 36 inches and must have 

a T shutoff valve.

cARBON MONOxIDe DetectOR RequIReMeNtS

() Revise  10.8.3  by  adding  the  following  additional 

requirements:
(a)  

For  all  side  wall  horizontally  vented  gas  fueled 

equipment installed in every dwelling, building or structure used 

in  whole  or  in  part  for  residential  purposes,  including  those 

owned or operated by the Commonwealth and where the side 

wall exhaust vent termination is less than seven (7) feet above 

finished  grade  in  the  area  of  the  venting,  including  but  not 

limited to decks and porches, the following requirements shall 

be satisfied:
1. 

Installation  of  carbon  monoxide  detectors. 

At  the  time 

of  installation  of  the  side  wall  horizontal  vented  gas  fueled 

equipment,  the  installing  plumber  or  gas  fitter  shall  observe 

that a hard wired carbon monoxide detector with an alarm and 

battery  back-up  is  installed  on  the  floor  level  where  the  gas 

equipment is to be installed. In addition, the installing plumber 

or gas fitter shall observe that a battery operated or hard wired 

carbon  monoxide  detector  with  an  alarm  is  installed  on  each 

additional level of the dwelling, building or structure served by 

the side wall horizontal vented gas fueled equipment. It shall be 

the responsibility of the property owner to secure the services of 

qualified licensed professionals for the installation of hard wired 

carbon monoxide detectors
 

a.  In the event that the side wall horizontally vented gas 

fueled equipment is installed in a crawl space or an attic, the 

hard  wired  carbon  monoxide  detector  with  alarm  and  battery 

back-up may be installed on the next adjacent floor level.
 

b.  In the event that the requirements of this subdivision 

can  not  be  met  at  the  time  of  completion  of  installation,  the 

owner shall have a period of thirty (30) days to comply with the 

above requirements; provided, however, that during said thirty 

(30) day period, a battery operated carbon monoxide detector 

with an alarm shall be installed.

Massachusetts Residents Only — Please read and follow these special requirements

Approved  carbon  Monoxide  Detectors.

 

Each  carbon 

monoxide detector as required in accordance with the above 

provisions shall comply with NFPA 70 and be ANSI/UL 034 

listed and IAS certified.
3. 

Signage.

  A  metal  or  plastic  identification  plate  shall  be 

permanently  mounted  to  the  exterior  of  the  building  at  a 

minimum height of eight (8) feet above grade directly in line with 

the exhaust vent terminal for the horizontally vented gas fueled 

heating appliance or equipment. The sign shall read, in print size 

no less than one-half (1/) inch in size, “GAS VENT DIRECTLY 

BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
4. 

Inspection.

 The state or local gas inspector of the side wall 

horizontally vented gas fueled equipment shall not approve the 

installation  unless,  upon  inspection,  the  inspector  observes 

carbon monoxide detectors and signage installed in accordance 

with the provisions of 48 CMR 5.08()(a)1 through 4.
(b) 

exemptions:

 The following equipment is exempt from 48 

CMR 5.08()(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not 

Required To Be Vented" in the most current edition of NFPA 54 

as adopted by the Board; and
.  Product Approved  side  wall  horizontally  vented  gas  fueled 

equipment  installed  in  a  room  or  structure  separate  from  the 

dwelling,  building  or  structure  used  in  whole  or  in  part  for 

residential purposes.
(c)  

Manufacturer requirements — Gas equipment Venting 

System  Provided.

 

When  the  manufacturer  of  Product 

Approved side wall horizontally vented gas equipment provides 

a  venting  system  design  or  venting  system  components  with 

the equipment, the instructions provided by the manufacturer 

for installation of the equipment and the venting system shall 

include:
1. Detailed instructions for the installation of the venting system 

design or the venting system components; and
. A complete parts list for the venting system design or venting 

system.
(d) 

Manufacturer requirements — Gas equipment Venting 

System Not Provided. 

When the manufacturer of a Product 

Approved  side  wall  horizontally  vented  gas  fueled  equipment 

does  not  provide  the  parts  for  venting  the  flue  gases,  but 

identifies “special venting systems,” the following requirements 

shall be satisfied by the manufacturer:
1.  The  referenced  "special  venting  system"  instructions  shall 

be  included  with  the  appliance  or  equipment  installation 

instructions; and
. The “special venting systems” shall be Product Approved by 

the Board, and the instructions for that system shall include a 

parts list and detailed installation instructions.
(e)  

A  copy  of  all  installation  instructions  for  all  Product 

Approved side wall horizontally vented gas fueled equipment, 

all  venting  instructions,  all  parts  lists  for  venting  instructions, 

and/or all venting design

Содержание VLI31DVNTSC

Страница 1: ...r assistance or additional information consult a qualified installer service agency or the gas supplier This appliance may be installed in an aftermarket permanently located manufactured home USA only...

Страница 2: ...l Installation 16 Electrical Wiring 16 Command Center Wall Installation 17 Wall Switch Installation 17 Light Bulb Installation 17 Log Placement 19 Surround Installation 22 Operating Instructions 23 To...

Страница 3: ...by a qualified service person with glass door properly seated and sealed combustion leakage can occur CARBON MONOXIDE POISONING Early signs of carbon monoxide poisoning are similar to the flu with he...

Страница 4: ...fireplace with glass door removed cracked or broken Code Approval Direct Vent type appliances draw all combustion air from outside of the dwelling through the vent pipe These appliances have been test...

Страница 5: ...s product SPECIFICATIONS Figure 1 VLIDV Series Fireplace Insert Controls Command Center HIGH ELEVATIONS Input ratings are shown in BTU per hour and are certified without deration for elevations up to...

Страница 6: ...sert insert dimensions 834009 VLI31 dims 20 6QE 513 mm 9 6 251 mm 4 102 mm 2 6QE 56 mm 7 6 194 mm 15 6QE 389 mm 3 76 mm 16 6QE 411 mm 6 6M 172 mm 2556M 641 mm 2856 714 mm 20 6M 527 mm Figure 2 VLIDV F...

Страница 7: ...specific installation requirements IMPORTANT Your direct vent insert was designed to be installed in an existing wood burning fireplace The location and clearances are subject to local building codes...

Страница 8: ...de Wall Combustible Mantel Top Facing Side Facing 3 4 19 mm Maximum Depth Combustible Facing 42 1067 mm Minimum 10 254 mm Minimum 12 305 mm Minimum FP1947 insert clearances 9 08 12 305 mm 9 228 mm FP2...

Страница 9: ...rs on HIGH the first time you use it Place the fan in the OFF position during this time P ZERO CLEARANCE REQUIREMENTS Insulation Damper Smoke Shelf Masonry Lining or Refractory Screen Metal or Glass D...

Страница 10: ...ing installation Failure to do so could result in serious injury property damage or loss of life Operation of improperly installed and maintained venting system could result in serious injury property...

Страница 11: ...e orifice for use at high altitude contact your dealer High Temp Silicone FP1923 exhaust pipe 9 08 3 and 3 UL 1777 Gas Liner Apply high temperature silicone to lines on both ends and secure with two 2...

Страница 12: ...mmended block off plate noncombustible metal Prevents odors from chimney entering room UL 127 Solid Fuel Z C Firebox Figure 8 Inlet and Exhaust Reline NOTE You may use either reline configuration with...

Страница 13: ...r of Step 2 6 Re attach glass door in reverse order NOTE The VLIDV has an adjustable baffle and may be adjusted as needed by loosening four 4 screws Figure 10 INTAKE MANIFOLD VENT INSTALLATION Before...

Страница 14: ...ou must reduce incoming gas pressure to between 11 and 13 inches of water If you do not reduce incoming gas pressure burner system regula tor damage could occur Install external regulator with the ven...

Страница 15: ...ied with Appliance Tee Joint Pipe Nipple Cap Figure 12 Gas Connection A manual shut off valve is factory installed upstream of the appliance Union tee and plugged 1 8 NPT pressure tapping point should...

Страница 16: ...heck for gas leaks Electrical Wiring General 1 This fireplace is equipped with the Signature Control valve which operates on 6 volts The A C module plugs into an A C power supply Four 4 AA batteries a...

Страница 17: ...l cover provided and screw to junction box WALL SWITCH INSTALLATION The wall switch wire connection is located off the 2 ft wire harness from the control box to the command center Fig ure 15 The conne...

Страница 18: ...Ground Plug in Connector Control Board to Solenoid Gas In Gas Out Pilot Gas Tubing Valve A C Module FP2679 SCS wiring diagram To Outlet Optional Aux 300 Watts Max 300 Watts Max 300 Watts CAUTION Elect...

Страница 19: ...only parts specifically approved for this heater may result in property damage or personal in jury PLACE ROCK WOOL EMBER MATE RIAL IN FIREBOX Break up rock wool ember material into dime sized pieces P...

Страница 20: ...og 4 with the pointed end of the log to the left Place the log on the key provided on the top of the frint of log 2 and position it so the pointed end protrudes through and rests on the bottom of the...

Страница 21: ...I31 log 7 Log 7 LG834 Figure 22 7 Hold Log 7 with the pointy end of the log down and the knot in the log facing forward Place the right end on the key provided on the top of log 5 The pointy end of th...

Страница 22: ...stallation INSTALL SURROUND 1 Remove glass door assembly Page 39 Figure 54 2 Align cast or beveled surround holes with insert and attach with screws provided 3 Re attach glass door assembly 4 Attach f...

Страница 23: ...hone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will not fu...

Страница 24: ...s go to next step 4 Press the master switch to the ON position Within eight 8 seconds it will beep once This indicates the system is ready 5 Press ON button Sparker will spark and pilot flame will lig...

Страница 25: ...Low battery Indication for Transmitter X Child Proof Lock out X LCD Backlight X Security Codes 16 X Countdown 6 hr Timer X Standard Thermostatic Control Mode X Smart Mode Thermostat Auto Flame Blower...

Страница 26: ...ate if unattended You may disable this feature if you wish NOTE By disabling this feature your fireplace may con tinue to operate unattended 2 When the master switch is in the ON position press ing th...

Страница 27: ...c until manual reset Self Diagnostics Chart The Command Center has a self diagnostic LED enabling you to troubleshoot problems and potentially avoid a service call Please refer to the charts below for...

Страница 28: ...t arrows The blue LED backlight lights up for 8 seconds when any of the touch buttons is pressed The menus include TIMER THERMO LIGHT FAN and AUX The adjustment arrows include ON up and OFF down Their...

Страница 29: ...en LED on the Command Cen ter will flash for 10 seconds FP2649 set privace code FP2650 command ctr ctrl brd RF Receiver ON OFF Control Board FP2650 command ctr ctrl brd Battery Door Master Switch ON L...

Страница 30: ...Timer Mode a Push and hold the TIMER button for 3 seconds Or b Use the OFF down buttons to decrease the Set Time to zero Or FP2651 Manual mode FP2652 Timer mode c Slide down on the arrow buttons to e...

Страница 31: ...this setting and the blower is still off see blower On Delay and Off Delay in the next section TOUCH SCREEN REMOTE CONTROL OPERATION FP2655 blower speed control 4 After the signal is sent the ON up an...

Страница 32: ...will flash once to indicate that the setting has changed to B 2 When the current setting is B pressing TIMER button and THERMO button at the same time for 3 seconds will switch to A Mode The touch ar...

Страница 33: ...lank 2 Check battery installation or re place batteries 3 LCD display shows funny display 3 Reset the transmitter see Reset ting the Transmitter section 4 Appliance does not come on 2 The transmitter...

Страница 34: ...at sea level The burner on Natural Gas models may be adjusted for high altitude as follows To increase air mixture open the shutter more This will reduce soot formation Figure 40 To decrease air mixtu...

Страница 35: ...s frame from insert by releasing two latches on top of insert and lifting the door up and off the unit Figure 42 3 Set glass frame aside 4 Re install in reverse order FP2680 Figure 42 Glass Frame Remo...

Страница 36: ...ted on the right and left 6 Unfasten the brick support plate fastened to the burner Brick Panels Glass Door Assembly Brick Support Blower Assembly FP1963 Figure 43 Blower Removal and Assembly Light Bo...

Страница 37: ...l paint curing of the appliance can also leave a slight film on the glass This is a temporary problem CLEANING and MAINTENANCE FP2453 hooded pilot flames Sensor Thermopile FP2453 Figure 45 Typical Pil...

Страница 38: ...s shut off to shut off gas to heater See step To Turn Off Gas Page 25 Let heater cool for 15 minutes Remove faceplate see instructions included with face plate and glass Pages 37 38 3 Carefully remove...

Страница 39: ...83D4009 VLI31 Fireplace Insert 39 REPLACEMENT PARTS 8 11 12 15 24 25 27 834009 VLI31 parts 26 10 9 23 28 30 34 33 32 19 18 37 12 14 20 42 21 16 38 38 22 11 17 13 35 44 43 1 2 3 4 6 5 7 29...

Страница 40: ...K 83D3007K 24 Left Brick Liner 1 83D4018 83D4018 25 Rear Brick Liner 1 83D4020 83D4020 26 Right Brick Liner 1 83D4019 83D4019 27 Glass Door Assembly 1 83D1252 83D1252 28 Control Box 1 80D0018 80D0018...

Страница 41: ...ert 41 REPLACEMENT PARTS Optional Accessories Description VLI31 Cast Iron Surround HAR31CB Cast Iron Eyebrow HE31CB Cast Iron Face Door Kit PLY31CB SCS Wall Mount Extension Kit not shown SCSWEK 15ft w...

Страница 42: ...ith the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed Massachusetts Residents Only Please read...

Страница 43: ...mited Lifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner as...

Страница 44: ...ficiency Ratings Model EnerGuide Ratings Steady State D O E Fireplace Efficiency Fan OFF Fan ON AFUE VLI31DVNTSC 67 5 73 5 74 5 66 4 VLI31DVPTSC 73 9 79 8 80 8 74 6 Vermont Castings Group 149 Clevelan...

Отзывы: