8
20304685
VC41LDVI/VC41CDVI Gas Fireplace Insert
12” (305 mm)
Maximum Depth
14”
(356 mm)
Side Wall
Combustible Mantel
Side Facing
10” (254 mm)
Minimum
10” (254 mm)
Minimum
FP2988
insert clearances
11”
(279 mm)
CLeARANCeS
INSeRT CLeARANCeS
No combustibles (ie: drapes, doors) may be within, or
swing within 36" of the front of the insert.
MANTeL CLeARANCeS
NOTe: The combustible area above the facing must
not protrude more than 3/4" (19 mm) from the facing.
If it does, it is considered a mantel and must meet the
mantel requirements listed in this manual.
FP2988
Figure 3 -
Mantel Clearances
NOTe:
Side clearance
to combustibles is 10"
(254 mm) from opening
whether it is side wall or
mantel legs.
14"
(356 mm)
12" (305 mm)
FP2989
mantel clearance
Finish Wall
FP2989
Figure 4 -
Mantel Clearances
Fireplace Insert
Opening
Noncombustible
Material Required
up to 14" (356
mm) Above Fire-
place Opening
heARTh ReQuIReMeNTS
The insert must be installed on a noncombustible hearth
extending a minimum of 10" (254 mm) from the fireplace
opening (local codes may require a larger hearth). The
hearth must also extend to both sides of the face.