background image

7

Vermont Castings Concord

30005102

connection above the fireplace

In this installation, the chimney connector enters the 
fireplace flue through a thimble located above the 
fireplace. (Fig. 6) The liner of the fireplace chimney 
should extend at least to the point at which the chimney 
connector enters the chimney.  Follow all the guidelines 
for installing a chimney connector into a freestanding 
masonry chimney, and pay special attention to these 
additional points:

• 

The stove and chimney connector clearances to 
combustible mantel and trim materials are the same 
as clearances to combustible walls.  If necessary, 
use a combination of mantel, trim, and connector 
heat shields to provide the required clearances. 
Refer to Page 12.

• 

Double-check connector clearance to the ceiling.

• 

The fireplace damper must be closed and sealed to 
prevent room air from being drawn up the flue which 
could reduce performance.  However, it must be 
possible to reopen the damper to inspect or clean 
the chimney.

• 

Floor protection requirements also apply to fireplace 
installations. 

wall pass-throughs

Whenever possible, design the installation so that the 
connector does not pass through a combustible wall.  
If you must include a wall pass-through in your instal-
lation, check with your building inspector before you 
begin.  Also check with the chimney connector manu-
facturer for any specific requirements.
Consult with your dealer regarding special connection 
components available for use as wall pass-throughs.  
Use only parts that have been tested and  for use as a 
wall pass-through.

u.S. requirements:

The National Fire Protection Association (NFPA) has 
established guidelines for use in the United States for 
passing chimney connectors through combustible walls.  
Many building code inspectors follow these guidelines.  
Figure 7 shows one NFPA-approved method.  All com-
bustible material in the wall is cut away to provide 12” 
(305 mm) clearance to the connector.  Brick and mortar 
are used to enclose the clearance area.

alternate methods approved by the Nfpa: 

• 

Using a section of double-wall chimney with a 9” 
(229 mm) clearance to combustibles. (Fig. 8)

• 

Placing a chimney connector pipe inside a steel 
double-wall ventilated thimble, which is then sepa-
rated from combustibles by 6” (152 mm) of fiberglass 
insulating material. (Fig. 9)

ST272
masonry wall pass through
w/ single wall
connector
12/99

Min. 2” (51mm) Chimney clear-
ance to brick and combustibles

a

 = Minimum 12” (305 mm) brick con-

struction between liner and combustible 
framing materials

Min. 12” 

(305 mm) 

Fire clay 
liner

a

a

Chimney Flue

Fire clay 
liner 

Masonry 
Chimney 
constructed 
to NFPA 211

fig. 7

  Masonry Wall Pass-through with single wall 

chimney connector.

Chimney 
connector

ST272

ST273
nfpa 
factory built insulated
chimney section
12/99

fig. 8

  Wall Pass-through using factory-built insulated 

chimney section.

Min. 9” 

(230mm) 

Air Space

Min. 9”

230mm 

Chimney Flue

Sheet Steel 
Supports

Min. 2” 

(51mm) 

Non-soluble refrac-
tory cement

Solid insulated,  
factory-built 
chimney length 
set flush with 
flue

Chimney 
Connector

Masonry 
Chimney 
constructed to 
NFPA 211

24 ga.Sheet 
Steel Sup-
ports 

ST273

ST244a
Madison
fplc over mantel
12/00

fig. 6 

  If the clearance between the chimney connector and 

either the ceiling or the mantel is inadequate, a  protective 
heat shield is required.

Note clearance 
requirement on 
pages 12-13

Mantel

Chimney Connector 
Heat Shield

ST244a

*

*

*

Содержание Concord 1660

Страница 1: ...sk of fire follow the installation instructions Failure to follow instructions may result in property damage bodily injury or even death Contact local building officials about restrictions and install...

Страница 2: ...se you on the installation should you attempt to install it yourself Consult the au thority having local jurisdiction such as a municipal building department fire department fire prevention bureau etc...

Страница 3: ...rated the type and moisture content of the fuel used as well as the design construction and climatic location of your home Figures shown are based on maximum fuel consumption obtained under laboratory...

Страница 4: ...arge enough and is construct ed properly to meet all requirements You have all necessary permits from local authori ties Your local building official is the final authority for ap proving your install...

Страница 5: ...ection from the stove to the chimney They are for interior use only Double wall connectors must be tested and for use with solid fuel burning appliances Single wall con nectors should be made of 24 ga...

Страница 6: ...ring the Single wall Connector to a Prefabricated Chimney Follow the installation instructions of the chimney manufacturer exactly Special adapters are available from your local dealer to make the con...

Страница 7: ...National Fire Protection Association NFPA has established guidelines for use in the United States for passing chimney connectors through combustible walls Many building code inspectors follow these g...

Страница 8: ...Fig 9 Wall Pass through using single wall chimney connector with a ventilated steel thimble Min 6 152mm Chimney clearance to sheet steel supports and combustibles 2 51mm Min Glass Fiber Insulation Ch...

Страница 9: ...e maintained between the stove and nearby combustible materials to ensure that those materials do not over heat Clearance is the distance between either your stove or chimney connector and nearby wall...

Страница 10: ...t corner if desired Shielding for connector is centered behind con nector Wall pass through must comply with codes Corner installation vertical chimney connector two wall shields Fig 17 Reduced side c...

Страница 11: ...ve lining ST503 Alcove side view 11 10 00 djt Metal Stud Combustible facing may overlap metal studs by only 1 1 air gap top and bottom on both sides and back wall 7 16 Durock or equivalent Joist Shiel...

Страница 12: ...lds Top exit heat shields on stove no shields on single wall con nector Top exit heat shield on stove heat shield on single wall con nector Top exit heat shield on stove double wall chimney connector...

Страница 13: ...Surfaces Top Exit Installations no heat shields Top Exit Installations heat shield on stove no shields on single wall connector Top Exit Installations heat shield on stove heat shields on single wall...

Страница 14: ...Corner Protected Surfaces Concord 1660 Series Clearance Diagram Unprotected surfaces Rear Exit Installations Bottom Heat Shield floor protec tion minimum 18 457mm in front Y Z AA BB EE FF CC DD ST563...

Страница 15: ...eat Shield must be used in the U S and Canada in any installation on a floor that is not comprised of unpainted cement on earth 1 Remove the 1 4 20x 1 2 phillips screw from the cen tral mounting boss...

Страница 16: ...rews provided in the kit to attach the Adapter to the Rear Heat Shield at the aligned holes Without Rear Heat Shield 1 Facing the rear of the stove loosen the pan head screw located a the upper left h...

Страница 17: ...is delivered to the upper area of the firebox to support combustion of gases released from the main fuel bed This Second ary Air enters the stove through two unrestricted inlets and is heated while pa...

Страница 18: ...fect your stove s performance You and the stove are parts of a system other parts of the system have a strong effect on performance You may need to vary your firing technique to get the results you de...

Страница 19: ...ositon for several minutes after refueling Reset the primary air control for the desired heat output after the fire is re established Ash Disposal Remove ash before it reaches the top of the ash pan C...

Страница 20: ...n the inner gasket with the coated side down marked This Side Out toward the outside of the door Tighten the screws snugly but loose enough to allow for a little move ment of the glass when the stove...

Страница 21: ...imney connector should be cleaned by discon necting the sections taking them outside and removing any deposits with a stiff wire brush Reinstall the con nector sections after cleaning being sure to se...

Страница 22: ...tures Because the insulation is less dense than masonry the inner steel liner warms up more quickly than a masonry chimney Although steel chimneys are not as attractive as their masonry counterparts t...

Страница 23: ...290 F Creosote is volatile and can generate chimney fire All of the installation characteristics that adversely affect chimney draft also promote creosote condensation Consequently you can minimize cr...

Страница 24: ...m Description Part Number 1 Bottom Outer 30000795 2 End Left See Chart Pg 26 3 Back 30000798 4 Secondary Manifold Left 30000802 5 Front See Chart Pg 26 6 Load Door See Chart Pg 26 7 Ashlip See Chart P...

Страница 25: ...0001390 44 Thermostat Cover 30001414 45 Fl Hd PH 1 4 20 x 2 50 Blk 30001444 46 Brick Side Back 30000969 47 Brick Support Bracket 30000986 48 Griddle 30004700 49 Right Airwash Manifold 30001457 50 Left...

Страница 26: ...69 2320969 Front 30000808 30001182 Ashlip 30000815 30001184 Left Door Subassembly 30001173 30001229 Left Door Only 30000810 30001186 Right Door Subassembly 30001172 30001228 Right Door Only 30000809 3...

Страница 27: ...urfaces Inspect your woodburning stove prior to accepting it for any damage to the enamel 3 This warranty does not cover misuse of the stove as de scribed in the Owner s Guide nor does it cover any st...

Страница 28: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Отзывы: