background image

9

Vermont Castings Concord

30005102

To meet these requirements, a floor protector must be 
at least 54” (1372 mm) wide (“A”,Fig. 12) and 52” (1320 
mm) deep (“B”, Fig. 12).

fireplace hearth protection 

Do not assume that your fireplace hearth is completely 
noncombustible. Many fireplace hearths do not satisfy 
the “completely noncombustible” requirement because 
the brick or concrete in front of the fireplace opening is 
supported by heavy wood framing. (Fig. 13)  Because 
heat is readily conducted by brick or concrete, it can 
easily pass through to the wood.  As a result, such fire-
place hearths can be a fire hazard and are considered 
a combustible floor.  
For all fireplace installations, follow the floor protection 
guidelines described above.
Keep in mind that many raised hearths will extend 
less than the required clearance from the front of the 
heater when it is installed.  In such cases, sufficient 
floor protection as described above must be added in 
front of the hearth to satisfy the minimum floor protector 
requirement from the front of the stove:  18” (460 mm) 
from the front in the United States and 18” (460 mm) 
from the front in Canada. 
Hearth rugs do not satisfy the requirements for floor 
protection as they are only fire-retardant, not fire proof.  

ST247a
Rear exit floor dgrm
12/14/99   djt

fig. 13 

  Supporting timbers under fireplace hearths are 

considered to be combustible.

Wood framing 
requires protection 
from radiant heat

ST247a

clearance to Surrounding 

combustible materials

When the stove is operating, both the stoveplate and 
the chimney connector radiate heat in all directions.  A 
safe installation requires that adequate clearance  be 
maintained between the stove and nearby combustible 
materials to ensure that those materials do not over-
heat.
Clearance is the distance between either your stove 
or chimney connector, and nearby walls, floors, the 
ceiling, and any other fixed combustible surface.  

keep  

furnishings and other combustible materials away 
from the stove as well.

  In general, a distance of 48” 

(1219 mm) must be maintained between the stove and 
moveable combustible items such as drying clothes, 
furniture, newspapers, firewood, etc. Keep this area 
empty of any combustible material.  

Safe ways to reduce clearances 

The Concord clearance requirements,  and diagramed 
on Pages 12-13, have been established through testing 
to UL and ULC standards to meet most installation con-
figurations. These involve four basic variables:
  • When neither the chimney connector nor the wall 

has a heat shield  installed.

  • When only the chimney connector has a heat 

shield installed.

  • When only the wall has a heat shield  mounted on 

it.

  • When a heat shield is installed on both the chim-

ney connector and wall.

In general, the greatest clearance is required when the 
stove will be positioned with no heat shield near a wall 
with no heat shield.  The least clearance is required 
when both the stove and the wall have heat shields.  
Reducing a stove clearance may require installation of 
a  heat shield on the chimney connector as well. 
Clearances may be reduced only by means approved 
by the regulatory authority, or in accordance with the 
clearances  in this manual.

D

A

B

A

D

C

C

E

C

E

C

Top Vent

Rear Vent

F

St500a
Madison 
floor protection
7/26/01   djt

fig. 12 

  These dimensions are minimum requirements only. 

Use greater dimensions whenever possible.

floor protection requirements

 

 

A:  48” 

54”   (1372 mm)

B:  48” 

52”   (1321 mm)

C:   4”  

8”   (203 mm)

D:  18”  

18”   (457 mm)

E:  16” 

18”   (457 mm)

F:  10” 

10”   (254 mm)

    

u. S. 

canada

ST500a

Содержание Concord 1660

Страница 1: ...sk of fire follow the installation instructions Failure to follow instructions may result in property damage bodily injury or even death Contact local building officials about restrictions and install...

Страница 2: ...se you on the installation should you attempt to install it yourself Consult the au thority having local jurisdiction such as a municipal building department fire department fire prevention bureau etc...

Страница 3: ...rated the type and moisture content of the fuel used as well as the design construction and climatic location of your home Figures shown are based on maximum fuel consumption obtained under laboratory...

Страница 4: ...arge enough and is construct ed properly to meet all requirements You have all necessary permits from local authori ties Your local building official is the final authority for ap proving your install...

Страница 5: ...ection from the stove to the chimney They are for interior use only Double wall connectors must be tested and for use with solid fuel burning appliances Single wall con nectors should be made of 24 ga...

Страница 6: ...ring the Single wall Connector to a Prefabricated Chimney Follow the installation instructions of the chimney manufacturer exactly Special adapters are available from your local dealer to make the con...

Страница 7: ...National Fire Protection Association NFPA has established guidelines for use in the United States for passing chimney connectors through combustible walls Many building code inspectors follow these g...

Страница 8: ...Fig 9 Wall Pass through using single wall chimney connector with a ventilated steel thimble Min 6 152mm Chimney clearance to sheet steel supports and combustibles 2 51mm Min Glass Fiber Insulation Ch...

Страница 9: ...e maintained between the stove and nearby combustible materials to ensure that those materials do not over heat Clearance is the distance between either your stove or chimney connector and nearby wall...

Страница 10: ...t corner if desired Shielding for connector is centered behind con nector Wall pass through must comply with codes Corner installation vertical chimney connector two wall shields Fig 17 Reduced side c...

Страница 11: ...ve lining ST503 Alcove side view 11 10 00 djt Metal Stud Combustible facing may overlap metal studs by only 1 1 air gap top and bottom on both sides and back wall 7 16 Durock or equivalent Joist Shiel...

Страница 12: ...lds Top exit heat shields on stove no shields on single wall con nector Top exit heat shield on stove heat shield on single wall con nector Top exit heat shield on stove double wall chimney connector...

Страница 13: ...Surfaces Top Exit Installations no heat shields Top Exit Installations heat shield on stove no shields on single wall connector Top Exit Installations heat shield on stove heat shields on single wall...

Страница 14: ...Corner Protected Surfaces Concord 1660 Series Clearance Diagram Unprotected surfaces Rear Exit Installations Bottom Heat Shield floor protec tion minimum 18 457mm in front Y Z AA BB EE FF CC DD ST563...

Страница 15: ...eat Shield must be used in the U S and Canada in any installation on a floor that is not comprised of unpainted cement on earth 1 Remove the 1 4 20x 1 2 phillips screw from the cen tral mounting boss...

Страница 16: ...rews provided in the kit to attach the Adapter to the Rear Heat Shield at the aligned holes Without Rear Heat Shield 1 Facing the rear of the stove loosen the pan head screw located a the upper left h...

Страница 17: ...is delivered to the upper area of the firebox to support combustion of gases released from the main fuel bed This Second ary Air enters the stove through two unrestricted inlets and is heated while pa...

Страница 18: ...fect your stove s performance You and the stove are parts of a system other parts of the system have a strong effect on performance You may need to vary your firing technique to get the results you de...

Страница 19: ...ositon for several minutes after refueling Reset the primary air control for the desired heat output after the fire is re established Ash Disposal Remove ash before it reaches the top of the ash pan C...

Страница 20: ...n the inner gasket with the coated side down marked This Side Out toward the outside of the door Tighten the screws snugly but loose enough to allow for a little move ment of the glass when the stove...

Страница 21: ...imney connector should be cleaned by discon necting the sections taking them outside and removing any deposits with a stiff wire brush Reinstall the con nector sections after cleaning being sure to se...

Страница 22: ...tures Because the insulation is less dense than masonry the inner steel liner warms up more quickly than a masonry chimney Although steel chimneys are not as attractive as their masonry counterparts t...

Страница 23: ...290 F Creosote is volatile and can generate chimney fire All of the installation characteristics that adversely affect chimney draft also promote creosote condensation Consequently you can minimize cr...

Страница 24: ...m Description Part Number 1 Bottom Outer 30000795 2 End Left See Chart Pg 26 3 Back 30000798 4 Secondary Manifold Left 30000802 5 Front See Chart Pg 26 6 Load Door See Chart Pg 26 7 Ashlip See Chart P...

Страница 25: ...0001390 44 Thermostat Cover 30001414 45 Fl Hd PH 1 4 20 x 2 50 Blk 30001444 46 Brick Side Back 30000969 47 Brick Support Bracket 30000986 48 Griddle 30004700 49 Right Airwash Manifold 30001457 50 Left...

Страница 26: ...69 2320969 Front 30000808 30001182 Ashlip 30000815 30001184 Left Door Subassembly 30001173 30001229 Left Door Only 30000810 30001186 Right Door Subassembly 30001172 30001228 Right Door Only 30000809 3...

Страница 27: ...urfaces Inspect your woodburning stove prior to accepting it for any damage to the enamel 3 This warranty does not cover misuse of the stove as de scribed in the Owner s Guide nor does it cover any st...

Страница 28: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Отзывы: