Chateau™ Direct Vent Gas Fireplace

20011957

Gas Inlet and Manifold Pressures

   

Natural  LP (Propane)

  Minimum Inlet Pressure 

5.5” w.c. 

11.0” w.c.

  Maximum Inlet Pressure  14.0” w.c. 

14.0” w.c.

  Manifold Pressure 

3.5” w.c. 

10.0” w.c.

High Elevations

Input ratings are shown in BTU per hour and are 
certified without deration for elevations up to 
4,500 feet (1,370m) above sea level.
For elevations above 4,500 feet (1,370m) in USA, 
installations must be in accordance with the 
current ANSI Z223.1/NFPA 54 and/or local codes 
having jurisdiction.
In Canada, please consult provincial and/or local 
authorities having jurisdiction for installations at 
elevations above 4,500 feet (1,370m).

WARNING:  Improper installation, adjust-
ment, alteration, service or maintenance 
can cause injury or property damage. Refer 
to this manual for correct installation and 
operational procedures. For assistance or 
additional information consult a qualified 
installer, service agency, or the gas supplier.

Gas Line Installation

When purging gas line the front glass must 
be removed.

A gas shut off valve must be installed on 
the gas pipe line going into the appliance 

within easy access.

The gas pipeline can be brought in through the top of 
the valve box assembly.    
The gas line connection can be made with properly 
tinned 1/2” copper tubing or 1/2” gas tight.  Some 
municipalities have additional local codes, it is always 
best to consult your local authority and the 

CSA-B149.1

 

installation codes.
For USA installations consult the current National Fuel 
Gas Code, 

ANSI Z223.1/NFPA 54.

������

���������������

������������������

������

FP297A

1/2” Gas Supply

1/2” NPT X 1/2” Flare 
Shut-off Valve

1/2” Gas Tight or 
Tinned Copper 
(from valve)
(Not provided)

Fig. 6

  Typical gas supply installation.

Always check for gas leaks with a mild 
soap and water solution applied with a 
brush no larger than 1” (25mm). Never ap-
ply soap and water solution with a spray 
bottle. Do not use an open flame for leak 
testing.
The fireplace valve must not be subjected 
to any test pressures exceeding 1/2 psi. 
Isolate or disconnect this or any other gas 
appliance control from the gas line when 
pressure testing.

The gas control is equipped with an inlet and manifold 
pressure test point, therefore it is not necessary to pro-
vide an 1/8” test point up stream of the control.
When using copper, use only approved fittings. 

Always 

provide a union

 when using black iron pipe so the gas 

line can be easily disconnected for burner servicing. A 
union may not be behind a wall. (Fig. 8) See the gas 
specifications for pressure details and ratings.

The fireplace, when installed, must be elec-
trically connected and grounded in accord-
ance with local codes or, in the absence 
of local codes, with the current CSA C22.1 
Canadian Electrical Code or the national 
electrical code  ANSI/NFPA No. 70 in the 
USA.
It is strongly suggested that the wiring of 
the Electrical Junction Box be carried out 
by a licensed electrician. The box should 
be near the valve box assembly to plug the 
cord into.

Ensure the power to the supply line has 
been disconnected before commencing 
this procedure.

Electrical Junction Box

Содержание Chateau DVT38S2IN

Страница 1: ...tallation and service must be performed by a quali ed installer service agency or the gas supplier WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch Do not...

Страница 2: ...Instructions 10 General Venting Information General Venting 14 General Venting Information Termination Location 15 General Information Assembling Vent Pipes 16 SK8 Venting Pipes 16 Restrictor Plate G...

Страница 3: ...t is burned This is due to the curing of the paint and any undetected oil from the manufac turing process Please ensure that your room is well ventilated open all windows It is recommended that you bu...

Страница 4: ...4 622 mm C L 10 267 mm 3 4 19 mm C L 51 1299 mm 3 4 19 mm 34 876mm 29 746 mm 32 829 mm 33 854 mm 49 1245 mm 1 35 mm 1 2 13 mm 5 8 16 mm 44 1121 mm 37 962 mm 5 143 mm 6 152 mm 1 25 mm When framing unit...

Страница 5: ...the following Mantel Charts Noncombustible mantels and legs may be installed at any height and width around the appliance When using paint or lacquer to nish the mantel such paint or lacquer must be h...

Страница 6: ...located on the top of the unit as well as the nailing anges on the sides that were men tioned in Step 1 are designed to accommodate non combustible board recommended Dura Rock They are positioned 1 25...

Страница 7: ...149 1 installation codes For USA installations consult the current National Fuel Gas Code ANSI Z223 1 NFPA 54 FP297A 1 2 Gas Supply 1 2 NPT X 1 2 Flare Shut off Valve 1 2 Gas Tight or Tinned Copper fr...

Страница 8: ...ocate the learn button on the main module Fig 9 Press and release the learn button using a pencil point There will be a beep sound from the module Then press any key on the remote control transmit ter...

Страница 9: ...ont edge between the rebox side and outer casing The upper test port is inlet pressure The lower test port is manifold pressure Refer to Figure 8 CAUTION Turn off the gas supply before removing test p...

Страница 10: ...ormance Before using the transmitter install the 2 AAA transmitter bat teries into the battery compartment Use caution that batteries are installed in the proper direction ON H L 1 2 OFF Continuous Pi...

Страница 11: ...N and display will show HI ON LO Flame Operation Press the ON H L key The appliance ame will modulate down to low ame and display will show LO Changing Flame Height Press and hold the ON H L key to ra...

Страница 12: ...ress and hold the OFF CONTINUOUS PILOT key for approximately 5 seconds until the word PILOT appears on the LCD screen NOTE The word PILOT will appear on the LCD screen in ON mode CP CHILDPROOF FEATURE...

Страница 13: ...ace of the transmitter When a button on the transmitter is pressed the word ON or OF will appear on the LCD screen to show while the signal is being sent Upon initial use there may be a delay of three...

Страница 14: ...ning or declining slope There must not be any obstruction such as bushes gar den sheds fences decks or utility buildings within 24 610mm from the front of the termination hood Do not locate terminatio...

Страница 15: ...to nonmechanical air supply inlet 6 15 cm for appliances 10 000 6 15 cm for appliances to building or the combustion air inlet to any Btuh 3kW 12 30 cm for 10 000 Btuh 3kW 9 other appliances appliance...

Страница 16: ...The venting system must conform with local codes and or the current National Fuel Gas code ANSI Z223 1 NFPA 54 Only venting components manufactured by CFM Cor poration can be used in Direct Vent syst...

Страница 17: ...may be used Vertical Run in feet Measured from the appliance flue collar to the top of the vent pipe Horizontal Run in feet May use up to three 3 90 elbows but must not have two 2 consecutive 90 elbo...

Страница 18: ...umber of 45 elbows permitted per side wall installation is two 2 These elbows can be installed in either the vertical or horizontal run Fig 15 3 914mm FP1454 DVT38s2 horizontal plane 3 17 04 djt 2 610...

Страница 19: ...ce using UL approved metal adhesive tape to ensure the joints are sealed Attach an appropriate length of vent pipe to the replace Follow with the installation of the inner and outer elbow tape elbow j...

Страница 20: ...mm hole through the exterior wall and frame as shown Noncombustible Walls Hole opening must be 11 286mm in diameter STEP 2 Measure wall thickness and cut zero clearance sleeve parts to proper length M...

Страница 21: ...e vent pipes overlap the collars by 2 51 mm Secure the termina tion to the wall with screws provided and caulk around the wall plate to weatherproof Fig 24 As an alterna tive to screwing the terminati...

Страница 22: ...e machine screws attach the Vista door to the four 4 brackets Do not overtighten WARNING The glass frame assembly pro vided with the replace must be left in place for proper operation Failure to do so...

Страница 23: ...the burner Turn the shutter plate around so the bottom opening is 1 25 mm Replace the screws removed earlier Fig 31 1 25 mm FP1616 shutter plate 4 06 Remove Screws Shutter Plate Shutter Plate FP1616a...

Страница 24: ...e must be at least 14 x 14 368 x 368 mm 5 Place replace into position 6 Place restop s SKFS2A or Attic Insulation Shield AIS SK into position and secure Figs 35 36 7 Install roof support Fig 35 and ro...

Страница 25: ...36 Attic shield installation If an attic is above ceiling level an AIS SK Attic Insulation Shield must be installed The enlarged ends of the vent section always face downward Min 2 610mm CFM190 TTR Te...

Страница 26: ...act with AIS SK the chimney system Chimney Support Used to support chimney for each of 30 vertical SKCS8 height and 6 of angled chimney run Round Top Termination Top used to terminate chimney at roof...

Страница 27: ...glass will void all product warranties Care must be taken to avoid breakage of the glass Do not operate appliance with glass front removed cracked or broken A replacement glass frame assembly complete...

Страница 28: ...ing and remove each log from its wrapping material The logs are fragile and should be handled with care Keep the packaging materials out of the reach of children and dispose of the material in a safe...

Страница 29: ...Fig 43 Do not obstruct fresh air inlet with volcanic rock 4 Place the ember material lightly between each burner tube as sembly and the burner housing between the joined burner tubes and in front ove...

Страница 30: ...cing down Set the log on the inside of the fettle toward the left over the overlay and hook the branch and the pointed end of the log through the rst and second opening on the fettle by using the seco...

Страница 31: ...e Log Front Right F48 Figure 49 LG505 Log Front Upper Right F47 Figure 50 LG506 11 Position the log front right Fig 49 Hold the log with the two 2 branches toward you Set the left branch on the inside...

Страница 32: ...7 It is important to periodically perform a visual check of the pilot and burner ames Compare them to Figures 51 If the ame patterns appear abnormal contact a quali ed service provider for service and...

Страница 33: ...sure the bottom is over lapping the bottom trim piece The right side of the trim should butt up against the right side nailing ange of the replace 3 Place the left trim on the left side of the window...

Страница 34: ...OFF all electrical power to the replace if service is required 3 Turn the shut off valve on the gas supply line to the OFF position FP297A Warning If you do not follow these instructions exactly a re...

Страница 35: ...on the module for approximately 10 seconds to clear the memory you should hear a series of beeps from the receiver Then press and release the learn button you should hear a single beep from the receiv...

Страница 36: ...here is an issue with the main control system or an individual transmitter If the issue is with an individual transmitter make sure the batteries in both the transmitter and receiver are in stalled in...

Страница 37: ...uence is initiated This fault will also occur if pilot ame sensor is shorted to ground How to Clear Press OFF then ON buttons to re attempt normal ignition What to Check Check if pilot ame is actually...

Страница 38: ...ermin e tant que le fonctionnement de l appareil converti n a pas t v ri selon la notice du fabricant qui accompagne la trousse ATTENTION Avant d effectuer la conversin coupez d abord l limentation en...

Страница 39: ...The shaft will remain pushed in 9 Remove the slotted brass minimum rate screw lo cated in the valve next to the motor drive Fig 58 10 Replace the minimum rate screw with the one provided in the LP con...

Страница 40: ...lete Table 1 DVT38S2 Injector Ori ce Size Matrix Conversion to LP KiT Burner 20012368 Burner Housing Burner Burner Input BTU hr Model Housing Part Pilot Part Tube Part Tube Part Min Max DVT38S2IP 55 3...

Страница 41: ...hnician 1 Turn off main gas shut off valve 2 Allow replace to cool if it has been operating 3 Remove window frame assembly Refer to Window Frame Assembly Removal section 4 Remove logs 5 Vacuum burner...

Страница 42: ...ions prices and discontinue colors and products at any time without notice DVT38S2 Units GFYW5Q0 1 2 3 6 7a 8 9a b 10a b 11a b 16 21 11957 DVT38s2 parts 5 07 djt 1i 2 1j 2 1k 5 11a b 9a b 10a b 22 11a...

Страница 43: ...576 5 Spring Latch Assembly 20005788 6 Burner Housing Assembly 20009392 7a Burner 20009311 7b Burner Tube Assembly Pilot Side 20009308 8 Manifold Tube Assembly 20009282 9a Burner Housing Ori ce 55 LP...

Страница 44: ...6 Trim Kit Complete 2 per replace 20010894 26a Top Trim 2 per replace 20010901 26b Right Side Trim 2 per replace 20010902 26c Left Side Trim 2 per replace 20010903 26d Bottom Trim 2 per replace 200109...

Страница 45: ...45 Chateau Direct Vent Gas Fireplace 20011957 Accessories Back up Battery Kit All Models DVTBBK Follow instructions provided with the kit and on Page 8 for installation...

Страница 46: ...46 Chateau Direct Vent Gas Fireplace 20011957...

Страница 47: ...elated repair charges relating to the cost and expenses of replacing or repairing defective components under the Limited Lifetime Warranty are not covered except as provided for under the Basic One Ye...

Страница 48: ...Ef ciency Ratings Model EnerGuide Ratings Fireplace Ef ciency DVT38S2IN 47 1 DVT38S2IP 47 1 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 800 668 5323 www cfmcorp com CFM Corporation...

Отзывы: