4
Chateau™ Direct Vent Gas Fireplace
20011957
Y
D
A
B
C
E
Y
X
LU584
Locating unit
DVT38S2
3/17/04 djt
Locating Your Fireplace
LU584-1
Fig. 2
Locate gas fireplace.
A) Flat on wall
B) **Island
C) *Room divider
D) *Flat on wall corner E) Chase installation
Y) 6” minimum
Note (Fig. 2):
** Island (B) and Room Divider (C) installation is possible as long
as the horizontal portion of the vent system (X) does not exceed 20’
(610cm). See details in Venting Section.
* When you install your fireplace in (C) Room divider or (D) Flat on
wall corner positions (Y), a minimum of 6” (152mm) clearance must
be maintained from the perpendicular wall and the front side edge of
the fireplace.
24
���
"
(622 mm)
C
L
10
���
"
(267 mm)
3/4"
(19 mm)
C
L
51
���
" (1299 mm)
*
3/4" (19 mm)
34
���
" (876mm)
29
���
"
(746 mm)
32
���
"
(829 mm)
33
���
"
(854 mm)
*
49
���
"
(1245 mm)
1
���
"
(35 mm)
1/2"
(13 mm)
5/8" (16 mm)
44
���
" (1121 mm)
37
���
" (962 mm)
5
���
" (143 mm)
6" (152 mm)
1"
(25 mm)
*
When framing unit on outside wall, flush with the wall,
a 1/4" (6mm) clearance must be allowed on both sides and top of surround.
11957
DVT38s2 specs
5/07
Sides and Top
of Surround
C
L
25
����
”
(649 mm)
Glass
25
����
”
(649 mm)
Gas Line
Connection
15
���
”
(403 mm)
10
����
”
(262 mm)
Noncombustible Material in This Area
Fireplace Dimensions
Fig. 1
Fireplace specifications and framing dimensions for DVT38S2.
Finished Wall 24
¹⁄₂
” (622 mm)
for Flush Install 16” (406 mm)
I.D. Minimum Clearance to
Combustibles
Standard Framing
NOTE:
Noncombustible insula-
tion may be placed behind the
facing material.
Only
Noncombustible
Material in
This Area
Exterior Side
(If installed on
outside wall)
Interior
Side
Содержание Chateau DVT38S2IN
Страница 46: ...46 Chateau Direct Vent Gas Fireplace 20011957...