Brookhaven Direct Vent Gas Fireplace

FP297A

INSTA VENT FREE

UVHB26 GAS SUPPLY 

7/1/98

FP297A

1/2” Gas Supply

1/2” NPT x 1/2” Flare Shut-

off Valve

3/8” Flex Line

(From Valve)

Fig. 5

  Typical gas supply installation.

The fireplace valve must not be subjected 
to any test pressures exceeding 1/2 psi. 
Isolate or disconnect this  or any other gas 
appliance control form the gas line when 
pressure testing.

The gas control is equipped with a captured screw type 
pressure test point, therefore it is not necessary to pro-
vide a 1/8” test point up stream of the control.
When using copper or flex connector use only approved 
fittings. Always provide a union when using black iron 
pipe so the gas line can be easily disconnected for 
burner or fan servicing. See gas specification for pres-
sure details and ratings.
The fireplace valve must not be subjected to any test 
pressures exceeding 1/2 psi. Isolate or disconnect this 
and any other gas appliance control from the gas line 
when pressure testing. 

Remote ON/OFF Switch

Do not wire the remote ON/OFF wall switch for this gas 
appliance into a 120v power supply.
1.  Thread wire through the electrical knockout located 

on either side of the unit. Take care not to cut the 
wire or insulation on metal edges. Ensure the wire is 
secured and protected form possible damage. Run 
one end of the gas control valve and the other end to 
the conveniently located wall switch.

2.  Attach the wire to the  ON/OFF switch and install 

switch into receptacle box. Attach cover plate to 
switch.

3.  Connect wiring to gas valve. (Fig. 6)

TPTH

TH

TP

FP1218
Remote switch
wiring
8/02

Remote ON/OFF Switch

FP1218

Fig. 6

  Remote switch wiring diagram for R models.

Your fireplace is approved to be vented either through 
the side wall, or vertically through the roof.

• 

Only CFM Corporation venting components specifi-
cally approved and labelled for this fireplace may be 
used.

  If vent termination is installed in an accessible loca-

tion, Vent Termination Guard #53525 shall be in-
stalled.

• 

Vent terminations shall not be recessed into a wall or 
siding.

• 

Horizontal venting which incorporates the twist lock 
pipe must be installed on a level plane without an 
inclining or declining slope.

• 

Horizontal venting which incorporates the use of flex 
venting shall have an inclining slope from the unit of 
1/2” (13 mm) per 12” (305 mm).

General Venting

There must not be any obstruction

 such as bushes, 

garden sheds, fences, decks or utility buildings within 
24” (610 mm) from the front of the termination hood.
Do not locate termination hood where excessive snow 
or ice build up may occur. Be sure to check vent termi-
nation area after snow falls, and clear to prevent ac-
cidental blockage of venting system. When using snow 
blowers, make sure snow is not directed towards vent 
termination area.

Location of Vent Termination 

It is imperative the vent termination be located observ-
ing the minimum clearances as shown on the next  
page.
*Check with local codes or in absence of same with 
CSA B149.1 Installation Codes (1991) for Canada 
or follow the current National Fuel Gas Code, ANSI 
Z223.1/NFPA 54 for installations in the USA.

Содержание Brookhaven 20DVT

Страница 1: ...the re department WARNING IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY A FIRE OR EXPLO SION MAY RESULT CAUSING PROPERTY DAMAGE PER SONAL INJURY OR LOSS OF LIFE PLEASE READ THIS MANUAL BEF...

Страница 2: ...Gas Line Installation 6 General Venting Information General Venting 7 General Venting Information Termination Location 8 General Information Assembling Vent Pipes 9 Flex Vent Pipes 9 Twist Lock Pipes...

Страница 3: ...on and ventilation air must not be ob structed in any way 11 When replace is installed directly on carpeting vinyl tile or any combustible material other than wood the replace must be installed on a m...

Страница 4: ...ions L 31 806 mm M 44 1140 mm N 23 587 mm O 21 540 mm P 34 864 mm Q 15 394 mm 20DVT Fireplace Dimensions Fig 2 Fireplace speci cations and framing dimensions O Rough Opening Width K F Q Rough Opening...

Страница 5: ...From Side Ref Leg Depth Ref of Comb Opening F 12 305 mm K 12 305 mm G 9 229 mm L 9 229 mm H 6 152 mm M 6 152 mm I 4 102 mm N 4 102 mm J 3 76 mm O 3 76 mm Fig 3b Combustible mantel leg minimum installa...

Страница 6: ...r elevations above 4 500 feet 1 370m in USA installations must be in accordance with the cur rent ANSI Z223 1 NFPA 54 and or local codes hav ing jurisdiction In Canada please consult provincial and or...

Страница 7: ...tall switch into receptacle box Attach cover plate to switch 3 Connect wiring to gas valve Fig 6 TPTH TH TP FP1218 Remote switch wiring 8 02 Remote ON OFF Switch FP1218 Fig 6 Remote switch wiring diag...

Страница 8: ...91cm 3 91cm J Clearance to nonmechanical air supply inlet 6 15cm for appliances 10 000 6 15cm for appliances to building or the combustion air inlet to any Btuh 3kW 12 30cm for 10 000 Btuh 3kW 9 othe...

Страница 9: ...e Apply High Tem perature Sealant Hose Clamp FP1471a Fig 8 Apply high temperature sealant to 4 and 7 pipes Outside Corner Inside Corner Termination Clearances Termination clearances for buildings with...

Страница 10: ...k Pipes When using CFM Corporation twist lock pipe it is not necessary to use sealant on the joints The only areas of the venting system that need to be sealed with high temperature silicone sealant a...

Страница 11: ...duced to 17 5 2 m In Figure 13 Dimension A plus B must not be greater than 17 5 2 m The maximum number of 45 elbows permitted per side wall installation is two 2 These elbows can be installed in eithe...

Страница 12: ...p i e from the elbow to the outside wall nish plus 2 or the distance required if installing a second 90 elbow Fig 18 Always install horizontal venting on a level plane X X FP1181 Fig 17 Vertical heigh...

Страница 13: ...pacer springs 6 165mm FP1475 flex 90 bend 4 04 djt FP1475 Fig 20 Bend ex vent at 90 so horizontal portion is 6 165 mm off top of unit STEP 4 Install the 4 102 mm ex vent pipe to the appliance collar a...

Страница 14: ...the horizon tal plane the maximum horizontal length must be reduced by 18 450 mm Example Maximum horizontal length No elbows 10 3 m 1 x 45 elbow 8 5 2 6 m 2 x 45 elbows 7 2 1 m A minimum of an 8 2 5m...

Страница 15: ...In all cases the opening must provide a mini mum of 1 25 mm clearance to the vent pipe i e the hole must be at least 9 x 9 240 x 240 mm 5 Place replace into position 6 Place restop s 7DVFS or Attic In...

Страница 16: ...r Vent to Vertical Vent 90 Elbow 7TDV90 Vertical Horizontal Offset Telescopic vent sections 7TDVP1117 11 to 17 adjustable length 7TDVP3567 35 to 67 adjustable length Pipe sections for vertical or hori...

Страница 17: ...onia household cleaner and warm water gas replace glass cleaner is recommended After the initial cleaning process the glass should be cleaned two or three times during each operating season depending...

Страница 18: ...n of Logs The logs are fragile and should be handled with care Keep the packaging material out of the reach of children and dispose of the mterial in a safe manner The individual logs can be easily id...

Страница 19: ...tating the Hi Lo adjustment knob located near the centre of the gas control Fig 33 or 34 Flame Characteristics It is important to periodically perform a visual check of the pilot and the burner ames C...

Страница 20: ...tly B BEFORE LIGHTING smell all around the heater area for gas Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor WHAT TO DO IF YOU SMELL GAS Do not try t...

Страница 21: ...rning no gas to A Wall switch or wires defective Check wall switch and wires for proper connections main burner Jumper wires across terminals at wall switch if burner comes on repalce defective wall s...

Страница 22: ...m assembly FC107 D E F FC108 SIT regulator conversion 10 03 OF F P I L O T O FC108 Fig 38 Replace regulator Burner Ori ce Conversion 1 Remove two 2 burner housing assembly mounting screws Fig 39 2 Lif...

Страница 23: ...stall conversion pilot ori ce 4 Reinstall pilot hood and be sure to align with index tab 5 Turn the gas supply valve and gas valve on and test for leaks Use a 50 50 solution of liquid soap and water t...

Страница 24: ...May Be HOT 1 Turn off pilot light at gas valve side 2 Let replace cool if it has been running 3 Remove window frame assembly Refer to Window Frame Assembly Removal section 4 Remove logs 5 Vacuum burn...

Страница 25: ...a 1b 2 3 4 5 7a b 8a b 12 13 9 14 10 16 17 18 20 21 22 24 9459 20DVT parts 5 06 19 15 Ref Description 20DVT 1 Log Set Complete 10009451 1a Log Rear J11 1b Log Front J12 2 Lava Rock Pkg 10001454 3 Embe...

Страница 26: ...ctrode Ignitor w Cable RN RP 10001297 15 Ignitor Piezo w Nut 50932 16 Valve SIT 820 662 RN 20010563 17 Flexible Gas Line w ON OFF Shut Off Valve 10009064 18 Frame Window w Glass Assy 10009485 19 Conso...

Страница 27: ...nd supported Installation Instructions 1 Remove window frame assembly and logs 2 Place rear ceramic panel in back of unit Fig 44 3 Place side panels 4 Re install logs and window frame assembly Optiona...

Страница 28: ...Brookhaven Direct Vent Gas Fireplace 28 10009459...

Страница 29: ...10009459 29 Brookhaven Direct Vent Gas Fireplace...

Страница 30: ...Brookhaven Direct Vent Gas Fireplace 30 10009459...

Страница 31: ...p Ifuponinspection thedamageisfoundtobethefaultofthemanufacturer repairs will be authorized at no charge to the customer parts and or labor Any part and or component replaced under the provisions of t...

Страница 32: ...Ratings EnerGuide Ratings D O E Model Fireplace Ef ciency Steady State AFUE 20DVTRN 60 1 80 64 20DVTRP 60 1 81 64 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 800 668 5323 www cfmcorp com CFM C...

Отзывы: