Brookhaven Direct Vent Gas Fireplace

Top of Unit to Ceiling ................................32” (813 mm)
Front of Unit to Combustibles ...................36” (914 mm)

Appliance

 

Top of Standoff .........................................0” (0 mm)

 

Bottom ......................................................0” (0 mm)

 

Side .....................................................3/4” (19 mm)

 

Back .........................................................0” (0 mm)

Venting

Concentric sections of DV Vent ....................1” (25 mm)
Nonconcentric sections of DV Vent
 

Sides and Bottom ...................................1” (25 mm)

 

Top .........................................................2” (51 mm)

Clearance to Combustibles

Mantels

The height that a combustible mantel is fitted above the 
fireplace is dependent on the depth of the mantel. This 
also applies to the distance between the mantel leg (if 
fitted) and the fireplace.
For the correct mounting height and widths refer to 
Figs. 3a and  3b, and the following Mantel Charts.
The fitting of a bay window trim kit does not effect 
the distances and reference points referred to in the 
diagram and chart.
Noncombustible mantels and legs may be installed 
at any height and width around the appliance. When 
using paint or lacquer to finish the mantel, such paint or 
lacquer must be heat resistant to prevent discoloration.

CFM170

J

F

G

H

I

CFM164b

Mantel Leg Char

DVT44

4/9/03   djt

CFM170

DV Builder Front 

View

O

N

M

L

K

Side of Fireplace

CFM164b

 

 

Mantel 

 

Mantel Leg From Side

  Ref. 

Leg Depth 

Ref. 

of Comb. Opening

 

12  (305 mm)  K 

12” 

(305 mm)

 

9”  (229 mm) 

9” 

(229 mm)

 

6”  (152 mm)  M 

6” 

(152 mm)

 

4”  (102 mm)  N 

4” 

(102 mm)

 

3”  (76 mm) 

3” 

(76 mm)

Fig. 3b

  Combustible mantel leg minimum installation.

A hearth is not mandatory but is recommended for  
aesthetic purposes.  We recommend a noncombustible 
hearth which projects out 12” (305 mm) or more from 
the front of the fireplace.

Cold climate installation recommendation:  

When installing this unit against a 
non-insulated exterior wall or chase, 
it is mandatory that the outer walls 
be insulated to conform to applicable 
insulation codes.  

Hearth

Proposition 65 Warning:

 Fuels used in gas, wood-

burning or oil fired appliances, and the products of 
combustion of such fuels, contain chemicals known to 
the State of California to cause cancer, birth defects 
and other reproductive harm.
California Health & Safety Code Sec. 25249.6

CFM146

A

B

C

D

E

V

W

X

Y

Z

Fireplace

CFM146
DV Mantel Chart
7/5/01   sta

Top of Combustion 

Chamber

Mantel Chart

Fig. 3a

  Combustible mantel minimum installation.

Maintain minimum 2

¹⁄₂

” 

(64 mm) clearance to 

combustible

 

 

Mantel Shelf 

 

Mantel from Top of

  Ref. 

or Breast Plate 

Ref.  Combustion Chamber

 

 

Depth 

 

20DVT

 

10”   (254 mm) 

18

¹⁄₂

”  (470 mm)

 

8”   (203 mm) 

16

¹⁄₂

”  (419 mm)

 

6”   (152 mm) 

14

¹⁄₂

”  (368 mm)

 

4”   (101 mm) 

12

¹⁄₂

”  (318 mm)

 

2”   (51 mm) 

10

¹⁄₂

”  (267 mm)

Fireplace 

Front

Combustion 

Opening

Содержание Brookhaven 20DVT

Страница 1: ...the re department WARNING IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY A FIRE OR EXPLO SION MAY RESULT CAUSING PROPERTY DAMAGE PER SONAL INJURY OR LOSS OF LIFE PLEASE READ THIS MANUAL BEF...

Страница 2: ...Gas Line Installation 6 General Venting Information General Venting 7 General Venting Information Termination Location 8 General Information Assembling Vent Pipes 9 Flex Vent Pipes 9 Twist Lock Pipes...

Страница 3: ...on and ventilation air must not be ob structed in any way 11 When replace is installed directly on carpeting vinyl tile or any combustible material other than wood the replace must be installed on a m...

Страница 4: ...ions L 31 806 mm M 44 1140 mm N 23 587 mm O 21 540 mm P 34 864 mm Q 15 394 mm 20DVT Fireplace Dimensions Fig 2 Fireplace speci cations and framing dimensions O Rough Opening Width K F Q Rough Opening...

Страница 5: ...From Side Ref Leg Depth Ref of Comb Opening F 12 305 mm K 12 305 mm G 9 229 mm L 9 229 mm H 6 152 mm M 6 152 mm I 4 102 mm N 4 102 mm J 3 76 mm O 3 76 mm Fig 3b Combustible mantel leg minimum installa...

Страница 6: ...r elevations above 4 500 feet 1 370m in USA installations must be in accordance with the cur rent ANSI Z223 1 NFPA 54 and or local codes hav ing jurisdiction In Canada please consult provincial and or...

Страница 7: ...tall switch into receptacle box Attach cover plate to switch 3 Connect wiring to gas valve Fig 6 TPTH TH TP FP1218 Remote switch wiring 8 02 Remote ON OFF Switch FP1218 Fig 6 Remote switch wiring diag...

Страница 8: ...91cm 3 91cm J Clearance to nonmechanical air supply inlet 6 15cm for appliances 10 000 6 15cm for appliances to building or the combustion air inlet to any Btuh 3kW 12 30cm for 10 000 Btuh 3kW 9 othe...

Страница 9: ...e Apply High Tem perature Sealant Hose Clamp FP1471a Fig 8 Apply high temperature sealant to 4 and 7 pipes Outside Corner Inside Corner Termination Clearances Termination clearances for buildings with...

Страница 10: ...k Pipes When using CFM Corporation twist lock pipe it is not necessary to use sealant on the joints The only areas of the venting system that need to be sealed with high temperature silicone sealant a...

Страница 11: ...duced to 17 5 2 m In Figure 13 Dimension A plus B must not be greater than 17 5 2 m The maximum number of 45 elbows permitted per side wall installation is two 2 These elbows can be installed in eithe...

Страница 12: ...p i e from the elbow to the outside wall nish plus 2 or the distance required if installing a second 90 elbow Fig 18 Always install horizontal venting on a level plane X X FP1181 Fig 17 Vertical heigh...

Страница 13: ...pacer springs 6 165mm FP1475 flex 90 bend 4 04 djt FP1475 Fig 20 Bend ex vent at 90 so horizontal portion is 6 165 mm off top of unit STEP 4 Install the 4 102 mm ex vent pipe to the appliance collar a...

Страница 14: ...the horizon tal plane the maximum horizontal length must be reduced by 18 450 mm Example Maximum horizontal length No elbows 10 3 m 1 x 45 elbow 8 5 2 6 m 2 x 45 elbows 7 2 1 m A minimum of an 8 2 5m...

Страница 15: ...In all cases the opening must provide a mini mum of 1 25 mm clearance to the vent pipe i e the hole must be at least 9 x 9 240 x 240 mm 5 Place replace into position 6 Place restop s 7DVFS or Attic In...

Страница 16: ...r Vent to Vertical Vent 90 Elbow 7TDV90 Vertical Horizontal Offset Telescopic vent sections 7TDVP1117 11 to 17 adjustable length 7TDVP3567 35 to 67 adjustable length Pipe sections for vertical or hori...

Страница 17: ...onia household cleaner and warm water gas replace glass cleaner is recommended After the initial cleaning process the glass should be cleaned two or three times during each operating season depending...

Страница 18: ...n of Logs The logs are fragile and should be handled with care Keep the packaging material out of the reach of children and dispose of the mterial in a safe manner The individual logs can be easily id...

Страница 19: ...tating the Hi Lo adjustment knob located near the centre of the gas control Fig 33 or 34 Flame Characteristics It is important to periodically perform a visual check of the pilot and the burner ames C...

Страница 20: ...tly B BEFORE LIGHTING smell all around the heater area for gas Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor WHAT TO DO IF YOU SMELL GAS Do not try t...

Страница 21: ...rning no gas to A Wall switch or wires defective Check wall switch and wires for proper connections main burner Jumper wires across terminals at wall switch if burner comes on repalce defective wall s...

Страница 22: ...m assembly FC107 D E F FC108 SIT regulator conversion 10 03 OF F P I L O T O FC108 Fig 38 Replace regulator Burner Ori ce Conversion 1 Remove two 2 burner housing assembly mounting screws Fig 39 2 Lif...

Страница 23: ...stall conversion pilot ori ce 4 Reinstall pilot hood and be sure to align with index tab 5 Turn the gas supply valve and gas valve on and test for leaks Use a 50 50 solution of liquid soap and water t...

Страница 24: ...May Be HOT 1 Turn off pilot light at gas valve side 2 Let replace cool if it has been running 3 Remove window frame assembly Refer to Window Frame Assembly Removal section 4 Remove logs 5 Vacuum burn...

Страница 25: ...a 1b 2 3 4 5 7a b 8a b 12 13 9 14 10 16 17 18 20 21 22 24 9459 20DVT parts 5 06 19 15 Ref Description 20DVT 1 Log Set Complete 10009451 1a Log Rear J11 1b Log Front J12 2 Lava Rock Pkg 10001454 3 Embe...

Страница 26: ...ctrode Ignitor w Cable RN RP 10001297 15 Ignitor Piezo w Nut 50932 16 Valve SIT 820 662 RN 20010563 17 Flexible Gas Line w ON OFF Shut Off Valve 10009064 18 Frame Window w Glass Assy 10009485 19 Conso...

Страница 27: ...nd supported Installation Instructions 1 Remove window frame assembly and logs 2 Place rear ceramic panel in back of unit Fig 44 3 Place side panels 4 Re install logs and window frame assembly Optiona...

Страница 28: ...Brookhaven Direct Vent Gas Fireplace 28 10009459...

Страница 29: ...10009459 29 Brookhaven Direct Vent Gas Fireplace...

Страница 30: ...Brookhaven Direct Vent Gas Fireplace 30 10009459...

Страница 31: ...p Ifuponinspection thedamageisfoundtobethefaultofthemanufacturer repairs will be authorized at no charge to the customer parts and or labor Any part and or component replaced under the provisions of t...

Страница 32: ...Ratings EnerGuide Ratings D O E Model Fireplace Ef ciency Steady State AFUE 20DVTRN 60 1 80 64 20DVTRP 60 1 81 64 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 800 668 5323 www cfmcorp com CFM C...

Отзывы: