DVBH7 Series Direct Vent Gas Fireplace
8
54D8001
cleARANceS
cleARANceS to comBuStIBleS
W
ARNING
Follow these instructions carefully to
ensure safe installation. Failure to follow
instructions exactly can create a fire
hazard.
the appliance cannot be installed on a
carpet, tile or other combustible material
other than wood flooring. If installed on
carpet or vinyl flooring, the appliance
shall be installed on a metal, wood or
noncombustible material panel extending
full width and depth of the appliance.
71”
Minimum
12”
Minimum
12”
Max.
Min. 4”
From Either
Side Wall
FP2580
mantel clearances
Figure 4 -
Clearances
Ceiling
Combustible Mantel
12”
12”
FP2581
mantel clearances
Wall
Stud
Standoff
FP581
Top of Exhaust
Louvers
Side View
1"
2
56O
”
3"
4"
1
56O
”
2
56O
”
45°
FP2582
mantel side clearance
Wall
Combustible
Material Area
Side of Fire-
place Opening
FP58
top View
Figure 5 -
Mantel Clearances
mANtel cleARANceS
Note:
The combustible area above the facing must
not protrude more than 3/4" from the facing. If it does,
it is considered a mantel and must meet the mantel
requirements listed in this manual.
W
ARNING
Never obstruct or modify the air inlet or
outlet grilles (louvers). this may create a
fire hazard.
FP580
Note:
All mantel shelves, regardless of depth, should be a min-
imum of 1” from top of fireplace. Mantel shelf shall not exceed
1” maximum depth at 1” minimum height from opening.
Insulation Board