E. Low Battery LED:

 LED illuminates when the battery 

needs to be replaced.

F. 6 Foot Coiled Cord: 

Insulation black colour PVC.

G. Banana Plug:

 Industrial Standard .175" (4.4 mm) Banana 

Plug, fits banana jack ≥ .157".

Operation

USING THE TESTER

1.  Use the slide switch to select a test range.
2.  Connect the coiled cord’s banana plug end to known 

 

ground. Use adapters where needed.  NOTE: The 

 

Vermason Low Resistance Tester may be used with 

 

an outlet polarity checker such as the Vermason 

222606

 

 or 

222607

 to determine a known ground.

3.  Connect or touch the tester end to a banana jack, 

 

common ground point, earth bonding point or other 

 

equipment that is being tested for resistance to ground.

4.  Press and hold the test button.
5.  An audio and visual indication will activate for a PASS 

 condition.
6.  A FAIL condition is indicated when the buzzer does not 

 

sound and the PASS LED does not illuminate.

Example of Test Range Uses

<1 OHM Range

 

- ESD Technical element Grounding Conductors:

 

Banana Jacks, Common Ground Points, Earth Bonding

 

Points, Grounding Blocks, Mat Ground Cords

 

  

ANSI/ESD S6.1 Grounding, sections 6.4 Technical  

 

 

  Elements,

 6.4.1, 6.4.2 and 6.4.3

 

- New AC Powered Hand Tools

 

  

ESD Handbook ESD TR20.20 section 5.5.2.2 Electrical  

 

  Hand Tools 

<2 OHM

 

- Soldering Irons

 

  

ESD Handbook ESD TR20.20 section 5.5.2.2 Electrical 

 

  Hand Tools

 

- Other AC Powered Hand Tools

 

  

ESD Handbook ESD TR20.20 section 5.5.2.2 Electrical 

 

  Hand Tools

<20 OHM

 

- Soldering iron compliance verification

  

 ESD Handbook ESD TR20.20 section 5.5.2.2 Electrical  

 

  Hand Tools

 

- Functional auxiliary grounds (ground rods)

  

 ANSI/ESD S20.20*

* ANSI/ESD S20.20 requires <25 ohms from the Auxiliary 

Ground to the Equipment Grounding Conductor.  Vermason’s 

Low Resistance Tester only tests to <20 ohms.  In cases of a 

no pass result with the Low Resistance Tester when testing 

an Auxiliary Functional Ground, an Ohmmeter should used to 

determine the actual resistance from the Auxiliary Functional 

Ground to Protective Earth Ground

Figure 3.  Testing a soldering iron with the 222644 tester

Figure 4.  Testing functional auxiliary ground with the 

222644 tester