Installation Guide

Power Monitoring

H81xx

TM

Product Diagram

H81xx Series Cover

1.  Display.  Large digit backlit LCD for data and diagnostics.

2.  Security hasp.

3.  Current transformer input terminals. These ensure that voltage lead and current transformer are properly matched (e.g. red to 

red).

4.  Voltage input terminals. These ensure that voltage lead and current transformer are properly matched (e.g. red to red).

5.  Pulse output terminals. These provide easy integration to existing control/data acquisition systems. (H8163 and H8167)

6.  Phase loss output alarm. Alarm trips to protect equipment if phase voltage drops 25%. (H8163 and H8167)

7.  Pulse rate selection switch. Set the pulse output at 0.1, 0.25, 0.50, or 1 pulse/kWh to match resolution requirements. (H8163 

and H8167)

8.  kWh reset. To reset the kWh counter, push both buttons at the same time and hold for 10 seconds. To reset kW max, push both 

buttons and hold for 5 seconds.

9.  Backlight enabling jumper. Remove this jumper to disable lighting.

10. Plain/full display data jumper. 20 or 90 second display cycle.

UL

®

C

US

2

1

H8163/H8167 Inside and Board Layout

N

A

+ A D + B D

+ C D

B

C

N

A B

C

+ - + - + -

Comm Board Slot *

* Comm board is optional and sold as a separate product.

Display

Plain

Full

Black

Black

Yellow

Yellow

Red

Red

Power Supply Board Slot

3

4

5 6

7

8

9

10

H8150 Inside and Board Layout

N

A

+ A D + B D

+ C D

B

C

N

A B

C

+ - + - + -

Display

Plain

Full

Black

Black

Yellow

Yellow

Red

Red

Power 

Supply

Comm Board Slot *

* Comm board is optional and sold as a separate product.

3

4

8

9

10

www.

.com

[email protected]

1.800.561.8187

Содержание H8150-0100-0-1

Страница 1: ...sconnect the H81xx from the supply source Place this device in close proximity to the equipment and within easy reach of the operator and mark it as the disconnecting device The disconnecting device s...

Страница 2: ...Opto FET 100mA 24VAC DC 0 10 0 25 0 50 1 00 kWh per pulse jumper selectable 200msec closed H8163 N O opens on alarm remains open while alarm persists H8167 N C closes on alarm remains closed while ala...

Страница 3: ...193 mm 8 3 211mm 14 8 375 mm Dimensions A B E F C D B E F C D A A B E C F D A 2 6 66mm B 1 1 28mm C 0 8 19mm D 1 27mm E 2 9 74mm F 3 5 90mm MINI 200Amp A 4 9 124mm B 2 9 73mm C 2 5 62mm D 1 1 29mm E...

Страница 4: ...and H8167 6 Phase loss output alarm Alarm trips to protect equipment if phase voltage drops 25 H8163 and H8167 7 Pulse rate selection switch Set the pulse output at 0 1 0 25 0 50 or 1 pulse kWh to ma...

Страница 5: ...and the CT serial number is on the CT label If using 100 A CTs serial number matching does not apply Matchserialnumbers betweenmetersandCTs Serialnumbermatchingdoes notapplyifusing100ACTs 2 Mount the...

Страница 6: ...uisition system The Pulse Output is normally open For the H8163 the Phase Loss Output is normally open and for the H8167 it is normally closed Both are rated for 24 VAC VDC 100 mA maximum Ensure that...

Страница 7: ...ed 1 0 0 5 0 25 0 1 11 Secure the meter cover shut using a padlock wire tie or other locking device 12 Apply power to the meter 13 Check the display At initial power up the meter checks each phase If...

Страница 8: ...ed black yellow wire to Wiring Typical120VAC 2 Wire 1 Installation N A A B C B C N A B C Red Black Yellow Red Black White Yellow RED CT WHITE A N External fuse provided by installer optional per NEC a...

Страница 9: ...re rated to 300 VAC L N and the H8150 is rated to 132 VAC L N Operation above these levels damages the device Alarms The H81xx continually reports kWh or MWh depending on the total accumulated energy...

Страница 10: ...sing 100 A CTs Accuracy not as specified Verify CTs and terminals are color matched Verify that no stray conductive materials wire clippings etc have shorted between the terminals No Pulse output H816...

Отзывы: