OPERATION

Installation Instructions

H-6001

KW/KWH Transducer

Easy installation

Small size (9.50" X 8.25" x 4.0") fits directly in
most panel enclosures.

Conduit ready enclosure for external mounting.
Hinged panel door

Direct voltage connection up to 600 VAC--no
expensive  potential transformers (PTs)

Powered by voltage inputs

Easy field voltage selection (120 to 600 VAC)

4-20 mA output loop continuity LED

Pulse output rate LED

Accurate analog and pulse outputs

Accurate to +/- 0.5% of reading..true
RMS power!

4-20 mA output for demand KW

Pulse output for KWH...adjustable rate
compatible with all automation systems and
data loggers

Phase loss/reversal/low voltage alarm output to
protect valuable equipment

KW and/or KWH display options. Maintains
readings in event of power loss

SAFE CTs...eliminates need for costly CT
shorting bars

Current transformers (CTs) utilize accurate
1.0 V output...non hazardous, even if left
unshorted!

Eliminates need for current shorting bars

Choose from split-core or solid-core CTs

CT accuracy 

±

 1% from 1% to 100% of the

rating

The H-6001 series 3-phase Power (KW) transducer is de-
signed for use in industrial, commercial,  and building
automation KW and KWH applications.

The H-6001 accepts three Veris  1.0 V current transformer
inputs and three direct connect voltage inputs.  The trans-
ducer multiplies the input current signal, voltage input,
and power factor for each phase to calculate true RMS
power (KW = E x I x 1.73 x power factor).  The instantaneous
power (KW) of all three phases is summed and converted
to an industry-standard 4-20 mA output signal for use in
demand management (load shedding) applications.  The
sensor also accumulates this instantaneous  value over
time and produces  a pulsed output proportional to the
energy usage (KWH).  The frequency of the output pulses
is proportional to the total power consumed and can be
used to measure energy usage for an entire building,
selected area, or individual loads (chillers, compressors,
etc..).

WARNING--REFER SERVICING TO
QUALIFIED PERSONNEL ONLY!

!

• This product is not intended for life or safety
applications

• Potential electrocution hazard exists.  Installing
sensors in an energized motor control center or
on any energized conductor can be hazardous.

•  Read instructions thoroughly prior to install

Severe injury or death can result from electrical shock
during contact with high voltage conductors or related
equipment.  Disconnect and lock-out all power sources
during installation and service. Applications  shown
are suggested means of installing sensors, but it is the
responsibility of the installer to ensure that the instal-
lation is in compliance with all national and local
codes.  Installation should be attempted only by indi-
viduals familiar with codes, standards, and proper
safety procedures for high-voltage installations.

Literature #L10159-1196

                  10831 S.W. CASCADE BLVD. 

PORTLAND, OREGON 97223

(503) 598-4564   FAX (503) 598-4664

1-800-354-8556

VERIS INDUSTRIES, INC.

http://www.veris.com    email:[email protected]     

®

Содержание H-6001

Страница 1: ...each phase to calculate true RMS power KW ExIx1 73xpowerfactor Theinstantaneous power KW of all three phases is summed and converted to an industry standard 4 20 mA output signal for use in demand ma...

Страница 2: ...G DIAGRAM This unit accepts 1 0V full scale output Current Transformers CTs only Do not use 0 5A OUTPUT Current Transformers e g 200 5 type CTs without H 6902B Adapter Consult Factory Enclose unit by...

Страница 3: ...WITH A NEUTRAL e g 120 V the following installation instructions apply see drawing below SINGLE PHASE INSTALLATION ON THREE PHASE BALANCED LOADS kW DEMAND E x I x 1 73 x mA out 4 x 3 1000 x 16 FORMUL...

Страница 4: ...sensors to be used in parallel so that multiple locations can be monitored by a single meter This allows for a totalized output from two or more locations RULES FOR ACCURATE PARALLEL INSTALLATION 1 Cu...

Страница 5: ...y voltage divided by secondary voltage Locate transducer within 30 of current transformers in an area accessible to qualified service personnel only Transducer and or enclosure should be mounted using...

Страница 6: ...L 3 to ensure phases are not reversed and that all are connected B Check that voltages on phases are above undervoltage set point Problem Pulse LED does not blink Solution A Ensure monitored load is...

Страница 7: ...9 0 0040 0 0100 0 0140 0 0200 0 0300 0 0400 0 0600 0 0800 0 1200 0 1600 0 2000 0 6 1 7 0 0080 0 0200 0 0280 0 0400 0 0600 0 0800 0 1200 0 1600 0 2400 0 3200 0 4000 0 3 3 5 0 0160 0 0400 0 0560 0 0800...

Страница 8: ...kside of the LCD display The front red push button may be enabled or disabled with the jumper When disabled the display may only be reset using the black reset switch near the jumper This feature is u...

Отзывы: