10. DETERMINE KW VALUE FOR PROGRAMING YOUR
AUTOMATION PANEL.

KW MAXIMUM

 = 

E  x   

I

 x  1.73

       1000

KW DEMAND = E   x  

I

  X  1.73   x   (mA out -

 

4)

1000 x 16

Where:
E    =

Line-to-line voltage

I

   =

Maximum rated full scale of one  CT in amps

mA out   =

 4-20 mA reading (note: you must provide DC volts)

11.  OPTIONAL QUICK CHECK OF OUTPUTS

1.  Calculate average of the three line currents (I ave.) with
a portable clamp on ammeter.

2.  Calculate the approximate KW:

=  E x 

I

 (ave.)  x 1.73 x power factor (use 0.9 if unkown)

1000

3.  Compare the calculated value with the actual 4-20 mA
reading (Use KW MAXIMUM formula above)

4.  Calculate the approximate seconds per pulse
(see TABLE 2 on page 7 for CTs up to 1000A):

=

KW DEMAND    x  Pulses per second maximum
KW MAXIMUM

Pulses per second maximum is read from selection switch.

5. Compare approx. seconds  per pulse with the number of
seconds between KW pulses as indicated by PULSE LED on unit.

NOTE: The 6001 is very accurate.  Since these calculations
are approximate, there may be some variation.  Also,
calculations will vary if there are load changes  during
readings.

INSTALLATION CONTINUED

TEST MODE

The TEST setting on the MAX PULSE/SEC. switch is used to
verify operation of the power multiplication portion of
the circuit, and also facilitates trouble shooting.  When in
the test mode, the pulse LED should blink steadily to
indicate proper circuitry operation.  Since it accelerates the
pulse output to 9.2 pulses/sec. at max load, you will be able
to determine the unit is operating even when no load is
present (voltage must be present--the unit is monitoring
its own current draw).

TROUBLESHOOTING

Problem:

  Phase loss LED out.

Solution:

A.

On initial installation, check L-1, L-2, L-3 to ensure
phases are not reversed, and that all are connected.

B.

Check that  voltages on phases are above undervoltage
set-point.

Problem:

  Pulse LED does not blink

Solution:

A.

Ensure monitored load is ON.  Ensure fuse or breakers
to unit are not blown.

B.

Verify that CTs are all oriented towards load as
indicated on label.

C.

Verify all CT wiring is correct (polarity of black/white
must be observed.)

Problem:

  Unit output is only a fraction of actual power

     consumption

Solution:

A.

Verify that CTs are all oriented towards load as indicated
on label.

B.

Verify all CT wiring is correct (polarity of black/white
must be observed.)

C.

Check that the current and voltage inputs have proper
relationship (if voltage legs are reversed, Phase Loss
LED will be out).

Problem:

  Unit output is only a fraction of actual power

     consumption

Solution:

A.

Verify that CTs are all oriented towards load as indicated
on label.

B.

Verify all CT wiring is correct (polarity of black/white
must be observed.)

C.

Check that the current and voltage inputs have proper
relationship (if voltage legs are reversed, Phase Loss
LED will be out).

Problem:

  The phases are not clearly marked, or difficult to

     identify:

Solution:

A.

Make sure that there is power supplied to the load.

B.

Put the pulse selector switch in the test mode.

C.

Put jumpers on the phase B and C CT inputs of the
transducer, and connect one of the CTs to the phase A
input. The kWH pulse light will either be flashing or it
will be off.

D.

If the light is flashing, reverse the wires and see if the
light goes out. If the light goes out the CT is on the
proper phase.

E.

If the light is off when the connection is made, reverse
the wires and see if the light starts flashing. If it does ,the
CT is on the correct phase.

F.

Repeat steps 3-5 for each phase (e.g. put jumpers on
phase A & C and connect a CT to phase B), and mark each
CT for the correct phase.

Содержание H-6001

Страница 1: ...each phase to calculate true RMS power KW ExIx1 73xpowerfactor Theinstantaneous power KW of all three phases is summed and converted to an industry standard 4 20 mA output signal for use in demand ma...

Страница 2: ...G DIAGRAM This unit accepts 1 0V full scale output Current Transformers CTs only Do not use 0 5A OUTPUT Current Transformers e g 200 5 type CTs without H 6902B Adapter Consult Factory Enclose unit by...

Страница 3: ...WITH A NEUTRAL e g 120 V the following installation instructions apply see drawing below SINGLE PHASE INSTALLATION ON THREE PHASE BALANCED LOADS kW DEMAND E x I x 1 73 x mA out 4 x 3 1000 x 16 FORMUL...

Страница 4: ...sensors to be used in parallel so that multiple locations can be monitored by a single meter This allows for a totalized output from two or more locations RULES FOR ACCURATE PARALLEL INSTALLATION 1 Cu...

Страница 5: ...y voltage divided by secondary voltage Locate transducer within 30 of current transformers in an area accessible to qualified service personnel only Transducer and or enclosure should be mounted using...

Страница 6: ...L 3 to ensure phases are not reversed and that all are connected B Check that voltages on phases are above undervoltage set point Problem Pulse LED does not blink Solution A Ensure monitored load is...

Страница 7: ...9 0 0040 0 0100 0 0140 0 0200 0 0300 0 0400 0 0600 0 0800 0 1200 0 1600 0 2000 0 6 1 7 0 0080 0 0200 0 0280 0 0400 0 0600 0 0800 0 1200 0 1600 0 2400 0 3200 0 4000 0 3 3 5 0 0160 0 0400 0 0560 0 0800...

Страница 8: ...kside of the LCD display The front red push button may be enabled or disabled with the jumper When disabled the display may only be reset using the black reset switch near the jumper This feature is u...

Отзывы: