2

Accepts 1.0 V output CTs only!
Size CT appropriately for you applications
CT rating must be greater than maximum current monitored.
Orient CT arrow towards load
Observe polarity (color coding) of wiring for CTs
To interface with 5A output CTs, consult factory.

Mandatory Fuse or breaker per NEC.
Max. current draw is 50 mA.  Installer must ensure
compliance with local and national codes (fuse rating
100 KAIC max.)

Line Voltage Selector.
Set to match line voltage

Undervoltage/phase Set-point.
Phase loss output opens on alarm when below set
percentage.

KWH Consumption Pulse Rate Selection
Sets maximum pulses per second at full scale operation.
Set for desired rate compatible with your automation
system.

Optional KW/KWH displays.
See OPTIONAL DISPLAYS section.

KW Demand Analog 4-20 mA Output
Provides instaneous KW demand analog output for input
to automtion system.
Requires external 12- 24 VDC supply.

Install Resistor for KW Voltage Output
For automation systems requiring a voltage, rather than
current, KW analog output, install appropriately sized
resistor as shown.

GENERAL WIRING DIAGRAM

• This unit accepts 1.0V full-scale output Current
Transformers (CTs) only.

 • Do not use 0-5A OUTPUT Current Transformers
(e.g., 200:5 type CTs) without H-6902B Adapter.
Consult Factory

• Enclose unit by bolt and nut or use a padlock to
secure.

1

2

3

5

6

7

8

4

!

IMPORTANT INSTALLATION NOTE

NOTE: The use of potential transformers
has not been evaluated by UL

LINE VOLTAGE

600

480

240/208

120

85

90

95%

80

75

UNDERVOLTAGE SET
   % of full voltage

(For 208V, add 10% 
to scale, i.e. 85 = 95%)

PHASE
Loss/Reversal
On-Normal

MAX. PULSE/SEC.

kWH
PULSE (N.O.)

kW
4-20 mA

PHASE LOSS
N.C.

WHT
BLK

0

A

WHT
BLK

ØB

WHT
BLK

ØC

H-6000 SERIES

kW/kWH TRANSDUCER

0.3

0.6

4.6

TEST

1.2 2.3

Orient CT arrow
towards load

Observe polarity
(color coding) of
wiring for CTs

LINE

0

B

0

C

5892

16

kW (mA)

kWH   

+

-

-

+

kWH Pulse
Output

DC Supply

Voltage

ØA

Under Voltage/Phase Loss
(Opens on alarm)

LOAD

                  

1-800-354-8556

VERIS INDUSTRIES, INC.

For use with single or three phase AC circuits only, 120 to 
600 VAC, 50–60 Hz.  For single phase operation, connect L-1 
and L-2 only. Maximum current consumption 50 mA.

®

ØB

L-2

ØC

L-3

ØA

L-1

C

®

®

NRTL/C

Optional Potential 

Transformers for 

voltages above 600 V

Optional Surge

Suppressor

FUSE

FUSE

FUSE

FUSES: 600 V 1/4 AMP, 100 KAIC

L-1

L-2

L-3

NOTE:

 Consult factory for

single phase installation

2

3

4

5

6

7

1

Содержание H-6001

Страница 1: ...each phase to calculate true RMS power KW ExIx1 73xpowerfactor Theinstantaneous power KW of all three phases is summed and converted to an industry standard 4 20 mA output signal for use in demand ma...

Страница 2: ...G DIAGRAM This unit accepts 1 0V full scale output Current Transformers CTs only Do not use 0 5A OUTPUT Current Transformers e g 200 5 type CTs without H 6902B Adapter Consult Factory Enclose unit by...

Страница 3: ...WITH A NEUTRAL e g 120 V the following installation instructions apply see drawing below SINGLE PHASE INSTALLATION ON THREE PHASE BALANCED LOADS kW DEMAND E x I x 1 73 x mA out 4 x 3 1000 x 16 FORMUL...

Страница 4: ...sensors to be used in parallel so that multiple locations can be monitored by a single meter This allows for a totalized output from two or more locations RULES FOR ACCURATE PARALLEL INSTALLATION 1 Cu...

Страница 5: ...y voltage divided by secondary voltage Locate transducer within 30 of current transformers in an area accessible to qualified service personnel only Transducer and or enclosure should be mounted using...

Страница 6: ...L 3 to ensure phases are not reversed and that all are connected B Check that voltages on phases are above undervoltage set point Problem Pulse LED does not blink Solution A Ensure monitored load is...

Страница 7: ...9 0 0040 0 0100 0 0140 0 0200 0 0300 0 0400 0 0600 0 0800 0 1200 0 1600 0 2000 0 6 1 7 0 0080 0 0200 0 0280 0 0400 0 0600 0 0800 0 1200 0 1600 0 2400 0 3200 0 4000 0 3 3 5 0 0160 0 0400 0 0560 0 0800...

Страница 8: ...kside of the LCD display The front red push button may be enabled or disabled with the jumper When disabled the display may only be reset using the black reset switch near the jumper This feature is u...

Отзывы: