E51C2, E51C3 Installation Guide

This section describes the Modbus registers reserved for SunSpec compliance-related information. See www.sunspec.org for 
the original specifications.

SunSpec Register Blocks

E51C2 FDS

E51C3 L

og

Regist

er

R/W NV Format Units

Scale

Range

SunSpec Name

Description

SunSpec 1.0 Common Model

• • 40001

R

NV ULong

0x5375
6e53

C_SunSpec_ID

ASCII “SunS”. Identifies this as the beginning of a SunSpec Modbus 

point

• • 40002
• • 40003

R

NV UInt

1

C_SunSpec_DID

SunSpec common model Device ID

• • 40004

R

NV UInt

65

C_SunSpec_Length Length of the common model block

• • 40005 to 40020 R

NV String (32) ASCII

C_Manufacturer

null terminated ASCII text string = “VERIS”

• • 40021 to 40036 R

NV String (32) ASCII

C_Model

null terminated ASCII text string = “E51C_”

• • 40037 to 40044 R

NV String (16) ASCII

C_Options

null terminated ASCII text string

• • 40045 to 40052 R

NV String (16) ASCII

C_Version

null terminated ASCII text string

• • 40053 to 40068 R

NV String (32) ASCII

C_SerialNumber

null terminated ASCII text string

• • 40068

R

NV UInt

ASCII

C_SunSpec_Length Modbus address

SunSpec 1.1 Integer Meter Model

Identification

• • 40070

R

NV UInt

201 to 204

C_SunSpec_DID

SunSpec Integer meter model device IDs. Meter configuration by 

device ID:

201 = single phase (A-N or A-B) meter
202 = split single phase (A-B-N) meter
203 = Wye-connect 3-phase (ABCN) meter
204 = delta-connect 3-phase (ABC) meter

• • 40071

R

NV UInt

105

C_SunSpec_Length Length of the meter model block

Current

• • 40072

R

SInt

Amps M_AC_Current_SF

-32767 to +32767 M_AC_Current

AC Current (sum of active phases)

• • 40073

R

SInt

Amps M_AC_Current_SF

-32767 to +32767 M_AC_Current_A

Phase A AC current

• • 40074

R

SInt

Amps M_AC_Current_SF

-32767 to +32767 M_AC_Current_B

Phase B AC current

• • 40075

R

SInt

Amps M_AC_Current_SF

-32767 to +32767 M_AC_Current_C

Phase C AC current

• • 40076

R

NV SInt

1

M_AC_Current_CN AC Current Scale Factor

Voltage:  Line to Neutral

• • 40077

R

SInt

Volts

M_AC_Voltage_SF

-32767 to +32767 M_AC_Voltage_LN Line to Neutral AC voltage (average of active phases)

• • 40078

R

SInt

Volts

M_AC_Voltage_SF

-32767 to +32767 M_AC_Voltage_AN Phase A to Neutral AC Voltage

• • 40079

R

SInt

Volts

M_AC_Voltage_SF

-32767 to +32767 M_AC_Voltage_BN Phase B to Neutral AC Voltage

• • 40080

R

SInt

Volts

M_AC_Voltage_SF

-32767 to +32767 M_AC_Voltage_CN Phase C to Neutral AC Voltage

Voltage:  Line to Line

• • 40081

R

SInt

Volts

M_AC_Voltage_SF

-32767 to +32767 M_AC_Voltage_LL Line to Line AC voltage (average of active phases)

• • 40082

R

SInt

Volts

M_AC_Voltage_SF

-32767 to +32767 M_AC_Voltage_AB Phase A to Phase B AC Voltage

• • 40083

R

SInt

Volts

M_AC_Voltage_SF

-32767 to +32767 M_AC_Voltage_BC Phase B to Phase C AC Voltage

• • 40084

R

SInt

Volts

M_AC_Voltage_SF

-32767 to +32767 M_AC_Voltage_CA Phase C to Phase A AC Voltage

• • 40085

R

NV SInt

1

M_AC_Voltage_SF AC Voltage Scale Factor

Frequency

• • 40086

R

SInt

Hertz M_AC_Freq_SF

-32767 to +32767 M_AC_Freq

AC Frequency

• • 40087

R

NV SInt

SF

1

M_AC_Freq_SF

AC Frequency Scale Factor

Содержание E51C2

Страница 1: ...ce complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received...

Страница 2: ...35mm DIN Rail per EN 50022 OPERATING CONDITIONS Operating Temperature Range 30 to 70 C 22 to 158 F Storage Temperature Range 40 to 85 C 40 to 185 F Humidity Range 95 RH non condensing Altitude of Oper...

Страница 3: ...sions 4 Application Example 4 Data Outputs 5 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power Diagrams 9 Quick Setup Instructio...

Страница 4: ...L L C intheUSAand orothercountries Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners TM E51C2 E51C3 Installation Guide Dimensions 4 2 107mm 3 6 91mm 1 5 39mm 2 3 59mm 1 9 4...

Страница 5: ...ealTime Clock user configurable 10 user configurable log buffers each buffer holds 5760 16 bit entries User configures which 10 data points are stored in these buffers User configurable logging interv...

Страница 6: ...ways on standard 35 mm DIN rail or screw mounted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots...

Страница 7: ...a particular System Type will display as on the User Interface or as QNAN in the Modbus registers CTs Voltage Connections SystemType Phase Loss Measurements Wiring Diagram Number of wires Qty ID Qty...

Страница 8: ...WARNING Wiring Observe correct CT orientation N L1 X2 X1 White Black A B C N X1 X2 X1 X2 X1 X2 A B C Diagram1 1 PhaseLine to Neutral2 Wire System1CT Diagram2 1 PhaseLine to Line2 Wire System1CT L1 L2...

Страница 9: ...oundeddelta seetheLinetoNeutral installationlimits InCEcompliantinstallations thelinesmust beneutral earth referencedatlessthan300VACL N TheControlPowerTransformermaybewiredL NorL L Outputto meetmeter...

Страница 10: ...ack to the S COM screen 6 to the S CT Set Current Transducer screen If this unit does not have an RS 485 port this will be the first screen a to the CT V screen Use the or buttons to select the voltag...

Страница 11: ...be rated for the short circuit current at the connection point All pulse outputs and communication circuits are only intended to be connected to non hazardous circuits SELV or Class 2 Do not connect t...

Страница 12: ...pparent Power S Export Demand Maximum Reactive Power Q Export Demand Maximum Real Power P Export Demand DKVAR Present Reactive Power Demand Q D KVA Present Apparent Power Demand S DEMND Demand Scroll...

Страница 13: ...Reactive Power Q Export Demand Maximum Real Power Export Demand D KQ Present Reactive Power Demand D KS Present Apparent Power Demand DEMND Demand Scroll When Idle Total Import Real Energy A KPh 3 KPh...

Страница 14: ...C A B C INFO MODEL OS SN RS Serial Number Reset System Operating System ALERT INFO PLOSS A b C LOWPF A b C F ERR A I OVR A b C V OVR A b C PASWD 00000 PASWD 00000 Model Number Energy Pulse Output Err...

Страница 15: ...tem Type Current Transformer S SYS Next S CT CT V 1 0 33 CT SZ 100 SYSTM 3L 1n 3L 2L 1n 2L 1L 1n Back To SETUP Back Back Back S COM To Setup p 2 SPLOS Next S PT Set Potential Transfomer Ratio RATIO Po...

Страница 16: ...the ALARM PULSE screen and enable Energy pulse output configuration error bit in the Modbus Diagnostic Alert Bitmap if equipped Wh P Set Pulse Energy In Watt Hours VAR Hours if present per Pulse When...

Страница 17: ...setting the buffers hold 60 days of data An external timer can be used over Modbus by setting this register to 0 Use register 159 to turn on data logging and select either Single Shot or Continuous m...

Страница 18: ...ble CTs and PTs allowing a much wider range of operation from 90V x 5A up to 32000V x 32000A To promote this the meter permits variable scaling of the 16 bit integer registers via the scale registers...

Страница 19: ...ly a fraction to be read correctly This is done to allow integer numbers to represent fractional numbers Range Defines the limit of the values that a register can contain Standard Modbus Default Setti...

Страница 20: ...and Export correspond with Real Energy 016 LSR 017 R NV ULong kVAh E 0 to 0xFFFFFFFF Apparent Quadrants 1 4 Import MSR 018 LSR 019 R NV ULong kVAh E 0 to 0xFFFFFFFF Apparent Quadrants 2 3 Export MSR 0...

Страница 21: ...al Energy Phase C MSR 054 LSR 055 R NV ULong kVARh E 0 to 0xFFFFFFFF Accumulated Q1 Reactive Energy Phase A MSR Import Accumulated Reactive Energy Qh Per Phase 056 LSR 057 R NV ULong kVARh E 0 to 0xFF...

Страница 22: ...67 Real Power P Phase A Real Power P 092 R SInt kW W 32767 to 32767 Real Power P Phase B 093 R SInt kW W 32767 to 32767 Real Power P Phase C 094 R SInt kVAR W 32767 to 32767 Reactive Power Q Phase A R...

Страница 23: ...this value by 100 i e entering 200 yields a potential transformer ratio of 2 1 The default is 100 1 00 1 which is with no PT attached Set this value before setting the system voltage below 134 R W NV...

Страница 24: ...gy per Pulse Output Contact Closure If the meter cannot find a pulse duration that will keep up with the max system power register 135 it will reject the new value Check the meter configuration and or...

Страница 25: ...Logging Configuration and Status 155 R W NV UInt Day Month See Bytes Most Significant Byte MSB Least Significant Byte LSB Date Time Clock Following a power cycle resets to Day 01 Month 01 Hour 00 Yea...

Страница 26: ...t during the previous demand sub interval Bit 4 Logging Interrupted Logging has been interrupted power cycled log configuration change etc during the previous demand sub interval Bit 5 RTC Changed The...

Страница 27: ...177 R W NV UInt Log Register 9 Default is 156 Year Hour 178 R W NV UInt Log Register 10 Default is 157 Minutes Seconds Floating Point Data Summary of Active Phases 257 258 R NV Float kWh Accumulated...

Страница 28: ...user defined 315 316 R Float 1 0 4294967040 Pulse Counter 2 Export Reactive Energy Floating Point Data Per Phase 317 318 R Float kWh Accumulated Real Energy Phase A Import Accumulated Real Energy Ph...

Страница 29: ...Power Phase A 381 382 R Float kVA Apparent Power Phase A 383 384 R Float Ratio 0 0 1 0 Power Factor Phase A Power Factor PF 385 386 R Float Ratio 0 0 1 0 Power Factor Phase A 387 388 R Float Ratio 0...

Страница 30: ...device IDs Meter configuration by device ID 201 single phase A N or A B meter 202 split single phase A B N meter 203 Wye connect 3 phase ABCN meter 204 delta connect 3 phase ABC meter 40071 R NV UInt...

Страница 31: ...M_AC_VAR_SF 32767 to 32767 M_AC_VAR_A Phase A AC Reactive Power 40100 R SInt VAR M_AC_VAR_SF 32767 to 32767 M_AC_VAR_B Phase B AC Reactive Power 40101 R SInt VAR M_AC_VAR_SF 32767 to 32767 M_AC_VAR_C...

Страница 32: ...0 to 0xFFFFFFFF M_Import_VARh_Q1 Quadrant 1 Total Imported Reactive Energy 40143 40144 R NV ULong VAR hours M_Energy_VAR_SF 0x0 to 0xFFFFFFFF M_Import_VARh_ Q1A Phase A Quadrant 1 Total Imported React...

Страница 33: ...Total Exported Reactive Energy 40173 40174 R NV UInt SF 1 M_Energy_VA_SF Reactive Energy Scale Factor Events 40175 R NV ULong Flags M_Events Bit Map See M_EVENT_flags 0 no event 40176 Event Bit Descri...