CONTROL POWER
AC
5 VA max.; 90V min.;
UL Maximums: 600 V
L-L
(347 V
L-N
); CE Maximum: 300 V
L-N
DC*
3 W max.; UL and CE: 125 to 300 VDC
Ride Through Time
100 msec at 120 Vac
OUTPUT
Alarm Contacts
N.C., static output (30Vac/dc, 100mA max. @ 25 °C,
derate 0.56 mA per °C above 25 °C)
Real Energy Pulse Contacts
N.O., static output (30 Vac/dc, 100 mA max. @ 25°C,
derate 0.56 mA per °C above 25 °C)
RS-485 Port
2-wire, 1200 to 38400 baud, Modbus RTU
MECHANICAL CHARACTERISTICS
Weight
0.62 lb (0.28 kg)
IP Degree of Protection
(IEC 60529)
IP40 front display; IP20 meter
Display Characteristics
Back-lit blue LCD
Terminal Block Screw Torque
0.37 to 0.44 ft-lb (0.5 to 0.6 N·m)
Terminal Block Wire Size
24 to 14 AWG (0.2 to 2.1 mm
2
)
Rail
T35 (35mm) DIN Rail per EN 50022
OPERATING CONDITIONS
Operating Temperature Range
-30° to 70 °C (-22° to 158 °F)
Storage Temperature Range
-40° to 85 °C (-40° to 185 °F)
Humidity Range
<95% RH non-condensing
Altitude of Operation
3000 m
Mounting Location
Not suitable for wet locations. For indoor use only.
COMPLIANCE INFORMATION
US and Canada
CAT III, Pollution Degree 2;
for distribution systems up to 347V
L-N
/600Vac
L-L
CE
CAT III, Pollution Degree 2;
for distribution systems up to 300V
L-N
Dielectric Withstand
Per UL 508, IEC/EN 61010-1
Conducted and Radiated
Emissions
FCC part 15 Class B, EN 55011/EN 61000 Class B (residential and light industrial)
Conducted and Radiated
Immunity
EN 61000 Class A (heavy industrial)
US and Canada (cULus)
UL 508 (open type device)/CSA 22.2 No. 14-05
Europe (CE)
IEC/EN 61010-1
* External DC current limiting is required, see fuse recommendations.
Specifications (cont.)
This meter implements the draft SunSpec 1.0 common elements starting at base 1 address 40001, and the proposed SunSpec 1.1
meter model at 40070 (these addresses are not in Modicon notation). See www.veris.com or www.sunspec.org for copies of these
specifications.
The SunSpec Alliance logo is a trademark or registered trademark of the SunSpec Alliance.
SunSpec Alliance
Interoperability
Specification
Compliance