e30

INSTALLATIoN GUIDe

confIguratIon

1.  Communications Configuration:  Communications parameters for the E30 series 

are field selectable for your convenience. Please see the Product Diagram section 
(page 2) for selector location. The following parameters are configurable:

•  Baud Rate:  9600, 19200, 38400
•  Parity On or Off
•  Parity:  odd or even
•  Wiring:  two or four

B

ø

 Reserved

B1 Off/

On

Parity

2/4

Wire

Odd/
Even

Parity

Example:  2-wire 19200 Baud No Parity (Default Only)

1

2

3

4

5

6

7

8

off

off

X

X

X

9600

on

off

X

X

X

19200

off

on

X

X

X

38400

on

on

X

X

X

Reserved

off

off

X

X

X

No Parity

on

off

X

X

X

Odd Parity

off

on

X

X

X

No Parity

on

on

X

X

X

Even Parity

on

X

X

X

4-wire RS-
485

off

X

X

X

2-wire RS-
485

2.  Address Configuration:  Each Modbus device on a single network must have a 

unique address. Set the switch block to assign a unique address before the device 
is connected to the Modbus RS-485 network. If an address is selected which 
conflicts with another device, neither device will be able to communicate. 

3.  The E30 uses two logical addresses. Panel 1 uses the base address as set on the DIP 

switches, and Panel 2 uses this base a 1. Address the E30 as any whole 
number between and including 1-246. Each unit is equipped with a set of 8 DIP 
switches for addressing. See below.

1

LSB

MSB

1               2             4             8           16           32           64         128

DIP Switch Values

=

4.  To determine an address, simply add the values of any switch that is on. 

For example:

40

=

LSB

MSB

Switch number 4 has an ON Value of 8 and switch number 6 has an ON Value of 32.  

(8 + 32 = 40). Therefore, the address for Panel 1 is 40, and the address for Panel 2 is 
41.

See the Address Setup section (page 8) for a pictorial listing of the first 63 switch 
positions.

default dIP sWItch settIngs

The E30 includes two DIP switches, as shown below. Switches are shown in their 
default positions.

Comms Address

Comms Settings

Содержание E30 series

Страница 1: ...se a properly rated voltage sensing device to con rm power is o DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION Only install this product on insulated conductors Failure to follow these instructi...

Страница 2: ...h circuits The E30B measures both current and power for the mains and current only in each circuit The E30C measures current only for the mains and branch circuits dimensions CircuitBoardandMountingBr...

Страница 3: ...ors on the left are for panelboard 1 the two on the right are for panelboard 2 Note Connect CT strips to the correct ribbon cable connectors for each panel The top connector is for Strip A and the bot...

Страница 4: ...20 20 20 20 20 20 20 20 A B A B A B A B Panel 1 Panel 2 1 5 9 13 17 21 25 29 33 37 41 3 7 11 15 19 23 27 31 35 39 2 6 10 14 18 22 26 30 34 38 42 4 8 12 16 20 24 28 32 36 40 A B A B 1 5 9 13 17 21 25 2...

Страница 5: ...on 5 Install the E30 acquisition board mounting bracket in the panel using screws and bolts provided Figure 3 A grounding connection is located on the mounting bracket near the lower right corner Use...

Страница 6: ...p I1 I2 I3 IN I1 I2 I3 IN Panel2 Panel1 CTInput 0 0 333VAC CTInput 0 0 333VAC E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP Panel1 Panel2 Recommen...

Страница 7: ...Wire 4 Wire 2 WireExample Figure11 Belden1120Aor equivalent 120 terminator onlastdeviceof daisychain NotUsed WARNING After wiring the RS 485 cable remove all scraps of wire or foil shield from the ele...

Страница 8: ...RS 485 2 Address Configuration Each Modbus device on a single network must have a unique address Set the switch block to assign a unique address before the device is connected to the Modbus RS 485 ne...

Страница 9: ...andtheVeris V logoaretrademarksorregisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries TM E30 INSTALLATION GUIDE Address Setup DO NOT USE ZERO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15...

Страница 10: ...If Veris E30 products are used in installations with circuits higher than the product ratings the circuits must be kept segregated per UL508A Sec 17 5 Note 277 480 VAC Wye connected center grounded p...

Страница 11: ...ng This can be caused by a signal greater than 100 A or 277V L N or by a signal with highTHD near the gain stage switching points 1 5 A and 10 A The main board has a flashing green light Everything is...

Отзывы: