Z204998-0M 

PAGE 10 

©2012 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected]  

07121

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

TM

e30

INSTALLATIoN GUIDe

commIssIonIng

1.  Reconnect power to the panel.

2.  Configure installation mode using Modbus Register 6.

3.  Configure CT scaling.

4.  Configure alarms.

5.  Configure demand.

Download the free E3x configuration tool from www.veris.com to commission the 
device for operation.

recommended accessorIes

Part ID

Description

CBL008

Flat ribbon cable, 50 x 28 AWG, 1.5 ft. (0.45 m)

CBL016

Flat ribbon cable, 50 x 28 AWG, 4 ft. (1.2 m)

CBL017

Flat ribbon cable, 50 x 28 AWG, 5 ft. (1.5 m)

CBL018

Flat ribbon cable, 50 x 28 AWG, 6 ft. (1.8 m)

CBL019

Flat ribbon cable, 50 x 28 AWG, 8 ft. (2.4 m)

CBL020

Flat ribbon cable, 50 x 28 AWG, 10 ft. (3.0 m)

CBL021

Flat ribbon cable, 50 x 28 AWG, 20 ft. (6.1 m)

CBL022

Round ribbon cable, 50 x 28 AWG, 4 ft. (1.2 m) 

CBL023

Round ribbon cable, 50 x 28 AWG, 10 ft. (3 m) 

CBL024

Round ribbon cable, 50 x 28 AWG, 20 ft. (6 m) 

CBL025

Flat ribbon cable, 50 x 28 AWG, 2 m

CBL026

Flat ribbon cable, 50 x 28 AWG, 4 m

CBL027

Flat ribbon cable, 50 x 28 AWG, 6 m

CBL031

Round ribbon cable, 50 x 28 AWG, 1.5 ft. (0.45 m)

CBL032

Round ribbon cable, 50 x 28 AWG, 2.5 ft. (0.76 m)

AE001

E3x MCB cover

AE006

E30 CT repair kit

safety

If Veris E30 products are used in installations with circuits higher than the product 
ratings, the circuits must be kept segregated per UL508A Sec. 17.5.

Note: 277/480 VAC Wye connected (center grounded) power systems operate 
within the 300 VAC line to neutral safety rating of the E3x series, and the 
operational voltage limit (single-phase connection) as the line to neutral 
voltage is 277 VAC in such power systems. Corner-grounded delta 480 VAC 
systems would not qualify, as the actual line to earth voltage is 480 VAC on 
each leg, exceeding the E3x ratings.

Note:  E3x internal circuitry (cables and CTs) are not circuits as defined by 
UL508A, as they do not extend beyond the E3x itself without further safety/
fire isolation.

UL listed under standard 508 as an “open type device.”

Maximum ambient air temperature for use is 60°C.

Installation category:  CAT III

The E30 Series must be installed in an appropriate electrical and fire enclosure per 
local regulations.

For use in a Pollution Degree 2 or better environment only.

A Pollution Degree 2 environment must control conductive pollution and the 
possibility of condensation or high humidity. Consideration must be given to the 
enclosure, the correct use of ventilation, thermal properties of the equipment and the 
relationship with the environment.

If the equipment is used in a manner not specified by the manufacturer, the 
protection provided by the device may be impaired.

IEC/EN 61010-1     

This symbol indicates an electrical shock hazard exists.

Documentation must be consulted where this symbol is used on the 
product.

Содержание E30 series

Страница 1: ...se a properly rated voltage sensing device to con rm power is o DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION Only install this product on insulated conductors Failure to follow these instructi...

Страница 2: ...h circuits The E30B measures both current and power for the mains and current only in each circuit The E30C measures current only for the mains and branch circuits dimensions CircuitBoardandMountingBr...

Страница 3: ...ors on the left are for panelboard 1 the two on the right are for panelboard 2 Note Connect CT strips to the correct ribbon cable connectors for each panel The top connector is for Strip A and the bot...

Страница 4: ...20 20 20 20 20 20 20 20 A B A B A B A B Panel 1 Panel 2 1 5 9 13 17 21 25 29 33 37 41 3 7 11 15 19 23 27 31 35 39 2 6 10 14 18 22 26 30 34 38 42 4 8 12 16 20 24 28 32 36 40 A B A B 1 5 9 13 17 21 25 2...

Страница 5: ...on 5 Install the E30 acquisition board mounting bracket in the panel using screws and bolts provided Figure 3 A grounding connection is located on the mounting bracket near the lower right corner Use...

Страница 6: ...p I1 I2 I3 IN I1 I2 I3 IN Panel2 Panel1 CTInput 0 0 333VAC CTInput 0 0 333VAC E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP Panel1 Panel2 Recommen...

Страница 7: ...Wire 4 Wire 2 WireExample Figure11 Belden1120Aor equivalent 120 terminator onlastdeviceof daisychain NotUsed WARNING After wiring the RS 485 cable remove all scraps of wire or foil shield from the ele...

Страница 8: ...RS 485 2 Address Configuration Each Modbus device on a single network must have a unique address Set the switch block to assign a unique address before the device is connected to the Modbus RS 485 ne...

Страница 9: ...andtheVeris V logoaretrademarksorregisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries TM E30 INSTALLATION GUIDE Address Setup DO NOT USE ZERO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15...

Страница 10: ...If Veris E30 products are used in installations with circuits higher than the product ratings the circuits must be kept segregated per UL508A Sec 17 5 Note 277 480 VAC Wye connected center grounded p...

Страница 11: ...ng This can be caused by a signal greater than 100 A or 277V L N or by a signal with highTHD near the gain stage switching points 1 5 A and 10 A The main board has a flashing green light Everything is...

Отзывы: