PW2 Series Installation Guide

2.2"

(57 mm)

4"

(102 mm)

5.8"

(147 mm)

LOW

HIGH

WET DIFFERENTIAL PRESSURE 

Dimensions

Installation

Observe precautions for handling static sensitive

devices to avoid damage to the circuitry that

is not covered under the factory warranty.

1.  Mount sensor on a duct or pipe, across the pump, filter, or other pressure differential.

2.  Wire as shown below.

DIGITAL CONTROL

Digital Output

4-20mA IN

POWER SOURCE

12 to 24 VDC

 

Port Swap/

Norm 

Bi-Dr/

Normal 

Slow Avg/

Fast Norm

 

Analog Rev/

Norm

 

Bar/

PSI 

ZERO 

A-High 

B-Mid High 

C-Mid Low 

D-Low 

REMOTE 

ZERO 

 

4-20mA 

Pressure 

Range 

Settings 

Polarity

Insensitive

Default Settings in bold.  

Insert jumper to activate 

other features. 

Model

PW2-03
PW2-04
PW2-05

A

         50 

100
250

B

25
50

125

C

10
20
50

D

5

10
25

Model

PW2-03
PW2-04
PW2-05

A

        3.45 

   6.89

17.24

B

1.72
3.45
8.62

C

0.69
1.38
3.45

D

0.34
0.69
1.72

Range (PSI)

Range (bar)

HI PORT

100 psi
100 psi
  50 psi
  50 psi
    0 psi

LO PORT

     0 psi
   50 psi
   50 psi
100 psi
100 psi

4-20mA

  +100 psi
     +50 psi
           0 psi
       -50 psi
    -100 psi

Bidirectional Operation

Input Conditions

Result

Outputs Read

DP

20mA
16mA
12mA
  8mA
  4mA

Output is mA only.
Example:  PW2-04

Optional:  Connect Zero terminals to digital output (contact 
closure) of control system.

Caution:  Zero input is for dry-contact only. Do not apply voltage to 
the Zero terminals.

Range:  Use the Range switch to select 
F.S. differential pressure.

Note:  Use of 

a housing 

grounding screw 
is required for CE 

applications