PW2 Series Installation Guide
Installation (cont.)
Operation
Jumper
Notes
Port Swap/Norm
Reverses polarity of the pressure ports (i.e. makes the LO port operate as the HI port and vice versa); used when the
sensor is incorrectly plumbed.
Bi-Dr/Normal
Normal: 0 to F.S. pressure
Bidirectional: -F.S. pressure to +F.S. pressure; output reads 1/2 when pressure is zero.
Slow Avg/Fast Norm
Slow mode provides 5-second averaging for surge damping.
Analog Rev/Norm
Normal: Output increases as pressure increases;
Reverse: Output is maximum when pressure differential is zero and decreases as pressure increases.
Bar/PSI
Select output units.
Auto-Zero: Press and hold the Zero button for two seconds or provide contact closure on the auxiliary ‘Remote Zero’ terminal to
reset the output to zero pressure. To protect the device from accidental zeroing, this feature is only enabled when the detected
pressure is within 5% of factory calibration.
3. Configure the jumpers as described below.