PW2 Series Installation Guide

Installation (cont.)

Operation

Jumper

Notes

Port Swap/Norm

Reverses polarity of the pressure ports (i.e. makes the LO port operate as the HI port and vice versa); used when the 

sensor is incorrectly plumbed.

Bi-Dr/Normal

Normal: 0 to F.S. pressure
Bidirectional:  -F.S. pressure to +F.S. pressure; output reads 1/2 when pressure is zero.

Slow Avg/Fast Norm

Slow mode provides 5-second averaging for surge damping.

Analog Rev/Norm

Normal: Output increases as pressure increases;
Reverse: Output is maximum when pressure differential is zero and decreases as pressure increases.

Bar/PSI

Select output units.

Auto-Zero:  Press and hold the Zero button for two seconds or provide contact closure on the auxiliary ‘Remote Zero’ terminal to 
reset the output to zero pressure. To protect the device from accidental zeroing, this feature is only enabled when the detected 
pressure is within 5% of factory calibration.