manualshive.com logo in svg
background image

Z204201-0H 

Page 1 of 3 

©2018 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected] 1018 

 

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

NOTICE

•  This product is not intended for life or safety applications.

•  Do not install this product in hazardous or classified locations.

•  Read and understand the instructions before installing this product.

•  Turn off all power supplying equipment before working on it.

•  The installer is responsible for conformance to all applicable codes.

If this product is used in a manner not specified by the manufacturer, the protection 

provided by the product may be impaired. No responsibility is assumed by the 

manufacturer for any consequences arising out of the use of this material.

Installation Guide

Pressure 

TM

Product Identification

Specifications

Product Overview

The PW2 Series sensor is designed to accept high differential pressure. Install the sensor on a duct or pipe across a 
pump, filter, heat exchanger, compressor, or other non-corrosive wet media. The dual sensor design eliminates the 
need for a bypass valve, and the bi-directional capability reduces installation errors. A pushbutton allows easy zero 
adjustment.

PW2 Series

Wet Media Differential Pressure Transducer

Local Display

L = LCD Display
X = No Display

NIST

N = NIST
X = None

CE

S = Standard

Operational Range*

03 = 0 to 50 psig
04 = 0 to 100 psig
05 = 0 to 250 psig

PW2

 * IMPORTANT!
Select operational range according to maximum gauge pressure, NOT differential pressure.
Example:  High gauge pressure=90 psig, select 100 psig model (04).

Media Compatibility

17-4 PH stainless steel

Input Power

12 to 24 Vdc, 29 mA max.; loop powered

Output

2-wire transmitter; 4 to 20 mA (clipped and capped)

Proof Pressure

2x max. F.S. range

Burst Pressure

5x max. F.S. range

Accuracy at 25 °C*

Ranges A, B, C: ±1% F.S.** 

Range D:  ±2% F.S.**

Surge Damping

Electronic; 5-second averaging

Temperature Compensated 

Range

0 to 50 °C (32 to 122 °F);  

TC Zero <1.5% of product F.S. per sensor 

TC Span <1.5% of product F.S. per sensor

Sensor Operating Range

-20 to 85 °C (-4 to 185 °F)

Long Term Stability

±0.25% per year

Zero Adjust

Pushbutton auto-zero

Operating Environment

-10 to 55 °C (14 to 131 °F); 10 to 90% RH non-condensing

Fittings

1/8” NPT female thread, stainless steel 17-4 PH

Physical

White powder-coated aluminum

PRESSURE RANGES

   0 to 50 psi (0 to 3.45 bar)

5/10/25/50 psid (0 to 0.34/0.69/1.72/3.45 bar)

  0 to 100 psi (0 to 6.89 bar)

10/20/50/100 psid (0 to 0.69/1.38/3.45/6.89 bar)

    0 to 250 (0 to 17.24 bar)

25/50/125/250 psid (0 to 1.72/3.45/8.62/17.24 bar)

Note: To conform to EMC standards, use shielded cabling. Technical information is available from the factory on 

request.

* Accuracy combines linearity, hysteresis, and repeatability.

** F.S. is defined as full span of selected range in bidirectional mode.