Installation Instructions

H663 Series

Split-Core Branch 

Current Monitor

OPERATION

Designed for the critical load monitoring such as Co-location Data Centers and 
lighting panels, the H663 series monitors current on up to 42 branch circuits in 
a 120/208/240 VAC electrical panel.  By individually reporting current draw and 
initiating capacity warnings and alarms, the H663 series allows the user to manage 
loading and eliminate power disturbances caused by overloaded breakers.

The H663 series consists of a data acquisition system board and up to 42 individual 
split-core current transformers (CTs). The acquisition board should be mounted in-
side the electrical panel, or in an enclosure mounted near enough for the CT output 
leads to reach the acquisition board connectors. The CTs are clipped onto each of the 
branch circuit conductors. These CTs transmit amperage data from each monitored 
circuit to the acquisition system for processing.

Current and alarm information is transmitted to the user’s Control Data Acquisition 
system over an RS485 drop using the Modbus protocol.

Set-up is made easy with a PC based configuration tool which allows for global or 
individual selection of breaker size, warning levels, and alarm levels. 

The H663 Series is a UL508 Listed open device without enclosure.

*For 240VAC Power connection versions, order catalog number H663SM-xxE
 

Easy Installation

 

First split-core solution for branch current monitoring in the industry! 

  Monitor up to 42 (breakers) poles with one product

  Split-core CT’s provide quick and easy installation...ideal for retrofit

  Simple two wire 120 VAC power connection*

Network Ready RS485 Output

 

Retrieve amperage information from up to 42 circuits with one  RS485 drop...               

 

easy wiring

  Global alarm register for instant alarm and warning notification

  Integrates to available network display for local indication

  Easy to use configuration software simplifies setup and provides flexibility to customize  

 

the configuration to meet the application

DANGER OF ELECTROCUTION:

 

BE CERTAIN THAT EVERY 

CT IS CONNECTED TO A LOAD AT ALL TIMES WHEN CLAMPED TO AN ENERGIZED 
CONDUCTOR. Current mode Current Transformers (CTs) such as those used 
in this product can be damaged, or generate lethal voltages, if clamped 
around current carrying conductors while the output leads are not prop-
erly terminated to a shorting device, or  loaded, as by the H663SM main 
board.  

Install wiring connectors in accordance with manufacturer's specifica-

tions and instructions.

•   Potential electrocution hazard exists.  Installing  sensors in an energized  
electrical panel, or on any energized conductor can be hazardous.  

CT 

outputs should not be connected to Operator Accessible circuits.

•    Read instructions thoroughly prior to install

•   This product is not intended for life or safety applications. 
•   This product is not intended for installation in hazardous or classified 
locations and must be installed in an electrical and fire enclosure in accordance 
with EN 61010-1.

Severe injury or death can result from electrical shock during contact with high 
voltage conductors or related equipment.  Disconnect and lock-out all power 
sources during installation and service. Applications  shown are suggested means 
of installing sensors, but it is the  responsibility of the installer to ensure that the 
installation is safe and in compliance with all national and local codes.  Instal-
lation should be attempted only by individuals familiar with codes, standards, 
and proper safety procedures for high-voltage installations.

WARNINGS

Shop for Power Metering products online at:

1.877.766.5412

www.

PowerMeterStore

.ca

Содержание H663 Series

Страница 1: ...workReadyRS485Output Retrieve amperage information from up to 42 circuits with one RS485 drop easy wiring Global alarm register for instant alarm and warning notification Integrates to available network display for local indication Easy to use configuration software simplifies setup and provides flexibility to customize the configuration to meet the application DANGER OF ELECTROCUTION BECERTAINTHATEVER...

Страница 2: ...Baud Rate Parity Selection Switches Field selectable RS 485 serial interface control See Chart 1 on page 5 INSTALLATION Figure1 6 4 2 12 10 8 18 16 14 24 22 20 30 28 26 36 34 32 42 40 38 9 Modbus Address Dip Switches Each Modbus device must have a unique address These switches must be set to assign an individual address before the device is connected to the network See page 5 10 Lithium Battery CA...

Страница 3: ...0 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 LEFT RIGHT 4 1 3 9 3 7 3 5 3 3 3 1 2 9 2 7 2 5 2 3 2 1 1 9 1 7 1 5 1 3 1 1 9 7 5 3 1 4 2 4 0 3 8 3 6 3 4 3 2 3 0 2 8 2 6 2 4 2 2 2 0 1 8 1 6 1 4 1 2 1 0 8 6 4 2 Channel4 Channel2 Channel3 Channel41 Channel1 FT RIGHT Channel42 6 4 2 12 10 8 18 16 14 24 22 20 30 28 26 36 34 32 42 40...

Страница 4: ...ket Kit Acquisition and interconnection boards are mounted to the bracket at the factory Data Acquisition Board 11 375 289 mm 1 12 28 mm 5 75 146 mm Data Acquisition Board Mounting Bracket Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore ca ...

Страница 5: ...alues of each dip switch are as follows 1 1 2 2 3 4 4 8 5 16 6 32 7 64 8 128 To determine an address you simply add the values of any switch that is on For example Switch number 4 has an ON Value of 8 and switch number 6 has an ON Value of 32 8 32 40 See Chart 2 on the following page for a pictorial listing of the first 63 switch positions or H663 series can be addressed as any whole number between...

Страница 6: ...NOT USE ZERO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore ca ...

Страница 7: ...use 4 Replace with new fuse see specifications for fuse type 5 Reconnect 120V power source to Data Acquisition Board 6 Reconnect power 7 Check Alive LED for proper function See Figure 1 3 on page 2 for location 240VACforH663SM xxE Iffuseblowsrepeatedly checkpowersourcetoensurethatitisastable120VACsource Master NetworkDisplay Slave H663series TX SHLD TX RX TX RX TX TX SHLD TX RX TX RX TX SHIELD SHIE...

Страница 8: ...1 stop bit Termination 5 position depluggable connector Defaults Warning Register 60 of current sensor max configurable Alarm Register 70 of current sensor max configurable Breaker Size Register 20A Dimensions Circuit Board L x W 7 25 x 5 75 Split Core CT s 6 leads 1 04 x 1 04 x 1 58 Lithium Battery Life 5 years Replace with type CRF 1220 or equiv CAUTION DANGER OF EXPLOSION IF BATTERY IS INCORRECTL...

Отзывы: