CURRENT MONITORING
INSTALLATION GUIDE
Z201171-0A
PAGE 1
©2008 Veris Industries USA 800.354.8556 or 503.598.4564 / [email protected]
09083
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Current Sensing Four-Point
Remote Status Panel/Sensor Kit
Installer’s Specifications
Temperature Range
-15° to 85°C (5° to 185°F)
Humidity Range
0 - 95% non-condensing
Trip Point
Adjustable
Hysteresis
10% Typical
Output Type
Dry Contact, reed relay, N.O.
Output Rating
200mA@30VAC/DC
50mA@120VAC
No. of Points Accepted
1-4 sensors (H5800 solid core)
Supply Voltage
24VAC/DC
Supply Current
50mA max.
Housing
NEMA 1
H5800 Current Sensor:
Amperage Ratings
1 to 100A continuous
Wiring
Up to 1000’ from panel, 2 wire, 22 AWG twisted pair
All outputs and adjustments are per point.
Do not use the LED status indicators as evidence.
)";"3%0'&-&$53*$4)0$,&91-04*0/03"3$'-"4)
t 'PMMPXTBGFFMFDUSJDBMXPSLQSBDUJDFT
4FF/'1"&JOUIF64"PSBQQMJDBCMFMPDBMDPEFT
t 5IJTFRVJQNFOUNVTUPOMZCFJOTUBMMFEBOETFSWJDFECZRVBMJmFEFMFDUSJDBMQFSTPOOFM
t 3FBEVOEFSTUBOEBOEGPMMPXUIFJOTUSVDUJPOTCFGPSFJOTUBMMJOHUIJTQSPEVDU
t 5VSOPõBMMQPXFSTVQQMZJOHFRVJQNFOUCFGPSFXPSLJOHPOPSJOTJEFUIFFRVJQNFOU
t 6TFBQSPQFSMZSBUFEWPMUBHFTFOTJOHEFWJDFUPDPOmSNQPXFSJTPõ
%0/05%&1&/%0/5)*4130%6$5'0370-5"(&*/%*$"5*0/
t 0OMZJOTUBMMUIJTQSPEVDUPOJOTVMBUFEDPOEVDUPST
'BJMVSFUPGPMMPXUIFTFJOTUSVDUJPOTXJMMSFTVMUJOEFBUIPSTFSJPVTJOKVSZ
%"/(&3
Wiring ExamplE
H5004/H5004C
5004/5004C
DimEnsions
/05*$&
t 5IJTQSPEVDUJTOPUJOUFOEFEGPSMJGFPSTBGFUZBQQMJDBUJPOT
t %POPUJOTUBMMUIJTQSPEVDUJOIB[BSEPVTPSDMBTTJmFEMPDBUJPOT
t 5IFJOTUBMMFSJTSFTQPOTJCMFGPSDPOGPSNBODFUPBMMBQQMJDBCMFDPEFT
t .PVOUUIJTQSPEVDUJOTJEFBTVJUBCMFmSFBOEFMFDUSJDBMFODMPTVSF
quick install
Disconnect and lock out power to the conductor to be monitored.
1.
Install the Remote Status Panel near the controller. Wire the supply voltage
2.
terminal to 24VAC/DC power source.
Slide the conductors to be monitored through the sensing irises of the current
3.
transducers (up to 4 transducers per Panel). See Notes (page 2) for currents under
1 Amp or above 100 Amp. Note: Transducers may be located up to 1000 feet from
the Remote Status Panel.
Wire the output connections between the sensors and the Remote Status Panel.
4.
See Wiring section (page 2) for details. Sensors are polarity sensitive.
Adjust the amperage setpoint at which the Panel output will trip. Turn clockwise
5.
to increase.
Reconnect power.
6.
Motor
Control Center
Digital Control
Fan/pump #1
Hawkeye 5000
Adjustable Current
Status Sensor
Fan/pump #2
Starters
H5800 Mini-Sensor
Digital
Status
Inputs
4.2”
(105 mm)
2.75”
(70 mm)
Ø = 0.7”
(18 mm)
1.8”
(46 mm)
2.5”
(64 mm)
2.3”
(58 mm)
0.9”
(22 mm)
H5004
H5004C
proDuct iDEntification
Model
Description
H5004
Remote Status Panel
H5004C
Remote Status Panel Kit (includes four H5800 current sensors)
H5800
Current Sensors, sold separately