manualshive.com logo in svg
background image

H8051/H8053

Z201659-0N 

PAGE 4 

©2011 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected]  

12112

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

TM

INSTALLATION GUIDE

Model 8053 

Model 8051

WIRING

Typical 240/120 VAC 1Ø, 3-Wire Installation

Typical 277 VAC 1Ø, 2-Wire Installation

NOTE: Multiply output by 3 for 
proper kWh indication 
(Assuming balanced load)

NOTE: Multiply output by 2 for 
proper kWh indication
(Assuming balanced load)

PULSE OUTPUT LINE

277V

Black

Red

Yellow

Neutral

NOTE: Wires are crossed through 
the CT, each entering from 
the opposite direction. This 
arrangement does not require 
multiplying the output data.

Alternative 277 VAC 1Ø, 2-Wire Installation

Typical 208/480 VAC 3Ø, 3- or 4-Wire Installation

277V

Black

Red

Yellow

Neutral

PULSE OUTPUT LINE

Neutral

277V   

PULSE OUTPUT LINE

120   

Neutral  

120   

PULSE OUTPUT LINE

PULSE OUTPUT LINE

ØB

ØA

ØC

PULSE OUTPUT LINE

PHASE

PHASE

PHASE

120V

120V

Black

Red

Yellow

Neutral

PULSE OUTPUT LINE

NOTE: Multiply output 
by 2 for proper kWh 
indication

Cap This

Cap This

Cap This

Cap This

Cap This

Отзывы: