INSTALLATION GUIDE

OPERATION

The H8051 and H8053 pulse output meters combine microprocessor-based kWh 
transducers and high-accuracy split-core instrument grade current transformers (CTs) 
in one unit. The H8051 is a single CT version designed for balanced loads, and the 
H8053 is a 3-CT version for monitoring each phase. Integration of electronics lowers 
hardware and installation costs. The sensors automatically detect phase reversal, so 
CT load orientation is not a concern. The CTs and meters are calibrated as a set, so it is 
necessary to color-match the CTs and voltage leads when installing.

These devices are used in tenant submetering, performance contracting, and 
departmental costing applications. The 1% total system accuracy conforms to 
ANSIC12.1 metering standards.

PRODUCT DIAGRAM

PRODUCT IDENTIFICATION

Single CT Units

MODEL

MAX. AMPS

CT SIZE

H8051-0100-2

100

SMALL

H8051-0300-2

300

SMALL

H8051-0400-3

400

MEDIUM

H8051-0800-3

800

MEDIUM

H8051-0800-4

800

LARGE

H8051-1600-4

1600

LARGE

H8051-2400-4

2400

LARGE

Three-CT Units

MODEL

MAX. AMPS

CT SIZE

H8053-0100-2

100

SMALL

H8053-0300-2

300

SMALL

H8053-0400-3

400

MEDIUM

H8053-0800-3

800

MEDIUM

H8053-0800-4

800

LARGE

H8053-1600-4

1600

LARGE

H8053-2400-4

2400

LARGE

DIMENSIONS

Enercept

®

1

2

3

4

5

6

1.  Voltage Leads

2.  Fuses

3.  Pulse Output connector

4.  Status LED:  blink codes: slow green for normal operation; slow red for incorrect 

wiring or low power factor (less than 0.5); fast red for max. current exceeded.

5.  Pulse Rate Switches:  used to set the pulse output rate.

6.  External CTs: permanently attached; do not disconnect or use with other power 

meters.

Color match CTs and voltage leads! Example:  clamp the red 

labeled CT around the power conductor connected to the 

red voltage wire.

A

B

E

F

C

D

B

E

F

C

D

A

A

B

E

C

F

D

SMALL

100/300 Amp

MEDIUM

400/800 Amp

LARGE

800/1600/2400 Amp

A =  

3.8"   (96 mm)

B =  

1.2"   (30 mm)

C =  

1.3"   (31 mm)

D =  

1.2"   (30 mm)

E =  

4.0"   (100 mm)

F =  

4.8"   (121 mm)

A =  

4.9"   (125 mm)

B =  

2.9"   (73 mm)

C =  

2.5"   (62 mm)

D =  

1.2"   (30 mm)

E =  

5.2"   (132 mm)

F =  

6.0"   (151 mm)

A =  

4.9"   (125 mm)

B =  

5.5"   (139 mm)

C =  

2.5"   (62 mm)

D =  

1.2"   (30 mm)

E =  

7.9"   (201 mm)

F =  

6.0"   (151 mm)