manualshive.com logo in svg
background image

ZL0124-0E 

Page 1 of 20 

©2018 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected] 0818 

 

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

For use in a Pollution Degree 2 or better environment only. A Pollution Degree 2 environment must 
control conductive pollution and the possibility of condensation or high humidity. Consider the 
enclosure, the correct use of ventilation, thermal properties of the equipment, and the relationship with 
the environment. Installation category:  CAT II or CAT III.  Provide a disconnect device to disconnect the 
meter from the supply source. Place this device in close proximity to the equipment and within easy 
reach of the operator, and mark it as the disconnecting device. The disconnecting device shall meet the 
relevant requirements of IEC 60947-1 and IEC 60947-3 and shall be suitable for the application. In the US 
and Canada, disconnecting fuse holders can be used. Provide overcurrent protection and disconecting 
device for supply conductors with approved current limiting devices suitable for protecting the wiring. 
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the 
device may be impaired.

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

•  Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
•  This equipment must only be installed and serviced by qualified electrical personnel.
•  Read, understand and follow the instructions before installing this product.
•  Turn off all power supplying equipment before working on or inside the equipment.
•  Product may use multiple voltage/power sources. Disconnect ALL sources before

 servicing.
•  Use a properly rated voltage sensing device to confirm that power is off.
  DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION.
•  Current transformer secondaries must be shorted or connected to a burden at all times.
•  Products rated only for basic insulation must be installed on insulated conductors.
•  Replace all doors, covers and protective devices before powering the equipment.

Failure to follow these instructions will result in death or serious injury.

A qualified person is one who has skills and knowledge related to the construction and 

operation of this electrical equipment and installations, and has received safety 

training to recognize and avoid the hazards involved.  

NEC Article 100

If this product is used in a manner not specified by the manufacturer, the protection 

provided by the product may be impaired. No responsibility is assumed by the 

manufacturer for any consequences arising out of the use of this material.

DANGER

NOTICE

•  This product is not intended for life or safety applications.

•  Do not install this product in hazardous or classified locations.

•  The installer is responsible for conformance to all applicable codes.

•  Mount this product inside a suitable fire and electrical enclosure.

FCC PART 15 INFORMATION

NOTE: This equipment has been tested by the manufacturer and found to 

comply with the limits for a class B digital device, pursuant to part 15 of 

the FCC Rules. These limits are designed to provide reasonable protection 

against harmful interference when the equipment is operated in a 

residential environment. This equipment generates, uses, and can radiate 

radio frequency energy and, if not installed and used in accordance with 

the instruction manual, may cause harmful interference to radio 

communications. This device complies with part 15 of the FCC Rules. 

Operation is subject to the following two conditions:

   

(1) This device may not cause harmful interference, and

   

(2) this device must accept any interference received, including

   

      interference that may cause undesired operation.

   Modifications to this product without the express authorization of the 

manufacturer nullify this statement. 

WARNING

LOSS OF CONTROL

∙  Assure that the system will reach a safe state during and after a control path failure.
∙  Separate or redundant control paths must be provided for critical control functions.
∙  Test the effect of transmission delays or failures of communication links.

1

∙  Each implementation of equipment using communication links must be individually 

and thoroughly tested for proper operation before placing it in service.

Failure to follow these instructions may cause injury, death or equipment damage.

1

For additional information about anticipated transmission delays or failures of the link, refer to 

NEMA ICS 1.1 (latest edition). 

Safety Guidelines for the Application, Installation, and Maintenance 

of Solid-State Control

 or its equivalent in your specific country, language, and/or location.

Control system design must consider the potential failure modes of control paths and, for 

certain critical control functions, provide a means to acheive a safe state during and after a 

path failure. Examples of critical control functions are emergency stop and over-travel stop.

TM

Installation Guide

Power Monitoring

The safety of any system incorporating this equipment is the responsibility of the 

assembler of the system.

Product Overview

The E50C1A DIN Rail Power Meter provides a solution for measuring energy data with a single device. Inputs include 
Control Power, CT, and 3-phase voltage. The E50C1A supports multiple output options, including solid state relay 
contacts, Modbus, and pulse. The LCD screen on the faceplate allows instant output viewing. 

The meter is housed in a plastic enclosure suitable for installation on T35 DIN rail according to EN 50022. The 
E50C1A can be mounted with any orientation over the entire ambient temperature range, either on a DIN rail or in a 
panel. The meter is not sensitive to CT orientation, reducing installation errors.

E50C1A

Product Identification

Model

Description

Output

DIN Mount (meter only)

Pulse

RS-485

Alarm

E50C1A Modbus output, basic data set   

Specifications

MEASUREMENT ACCURACY

   Real Power and Energy

IEC 62053-22 Class 0.5S, ANSI C12.20 0.5%

   Reactive Power and Energy

IEC 62053-23 Class 2, 2%

   Current

0.4% (+0.015% per °C deviation from 25 °C) from 5% to 100% of range;  

0.8% (+0.015% per °C deviation from 25 °C) from 1% to 5% of range

   Voltage

0.4% (+0.015% per °C deviation from 25 °C) from 90 V

L-N

  to 600 Vac

L-L

   Sample Rate

2520 samples per second 

   Data Update Rate

1 sec

   Type of Measurement

True RMS up to the 21st harmonic 60 Hz; one to three phase AC system

INPUT VOLTAGE CHARACTERISTICS

   Measured AC Voltage

Minimum 90 V

L-N

 (156 V

L-L

) for stated accuracy; 

UL Maximum:  600 V

L-L

 (347 V

L-N

CE Maximum:  300 V

L-N

  

   Metering Over-Range

+20%

   Impedance

2.5 MΩ

L-N

 / 5MΩ

L-L

   Frequency Range

45 to 65 Hz

INPUT CURRENT CHARACTERISTICS

      CT  Scaling                                             

50 to 5000 A measured range; 400 to 5000 A breaker size

   Measurement Input Range

E683 series rope style CTs only (CTs must be rated for connection to Class 1 

voltage inputs)

Compact Power and Energy Meter

For Use Only With E683 Series Rope CTs

E683 Series CT 

(sold separately)

Содержание E50C1A

Страница 1: ...nd if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications This device complies with part 15 of the FCC Rules Operation is subject to...

Страница 2: ...529 IP40 front display IP20 meter Display Characteristics Back lit blue LCD Terminal Block Screw Torque 0 37 to 0 44 ft lb 0 5 to 0 6 N m Terminal Block Wire Size 24 to 14 AWG 0 2 to 2 1 mm2 Rail T35...

Страница 3: ...Installation Guide Table of Contents Dimensions 4 Data Outputs 4 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power 9 Quick Setu...

Страница 4: ...VerisIndustries L L C intheUSAand orothercountries Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners TM E50C1A Installation Guide Dimensions 4 2 107mm 3 6 91mm 1 5 39mm 2 3...

Страница 5: ...ndicator RS 485EquippedUnitsOnly TransmitData ReceiveData ReceiveDataError LCDScreen Buttons Up Select Right Next Down Select Left Back kWh 1234 5 Alarm Energy Two5 characterrows ofdisplaytext Toprowa...

Страница 6: ...35 mm DIN rail or screw mounted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside Th...

Страница 7: ...r System Type will display as on the User Interface or as QNAN in the Modbus registers CTs Voltage Connections SystemType Phase Loss Measurements Wiring Diagram Number of wires Qty ID Qty ID Type Modb...

Страница 8: ...TnoPT UseSystemType11 2L UseSystemType12 2L 1n UseSystemType 31 3L UseSystemType10 1L 1n Wiring RISK OF ELECTRIC SHOCK OR PERMANENT EQUIPMENT DAMAGE CT terminals are referenced to the meter s neutral...

Страница 9: ...L L Outputto meetmeterinputrequirements DCControlPowerfrom125Vdcto300Vdc ULandCEmax FuseRecommendations Keep the fuses close to the power source obey local and national code requirements For selecting...

Страница 10: ...ect the parameter screen you want to set 6 After you set the parameters you want use or to select the next Setup screen or to exit the Setup screens return to SETUP B ToEnterModbuscommunicationparamet...

Страница 11: ...powered and no phase loss alarm conditions are present All pulse outputs and communication circuits are only intended to be connected to non hazardous circuits SELV or Class 2 Do not connect to hazar...

Страница 12: ...KWh Accumulated Real Energy Ph SETUP ALERT RESET Back Display nOnE if no alerts To Setup Setup Meter Reset Data Phase Loss A B C Low Power Factor A B C Frequency Out of Range A Current Over Range Vol...

Страница 13: ...00 SYSTM 3L 1n 3L 2L 1n 2L 1L 1n Back To SETUP Back Back Back S COM To Setup p 2 SPLOS Next S PT Set Potential Transfomer Ratio RATIO Potential transformer step down is RATIO 1 Default is 1 1 No PT in...

Страница 14: ...the selection if it cannot find a pulse duration that will allow the pulse output to keep up with Theoretical Maximum System Power see S_PWR screen When moving up to a larger energy the meter will jum...

Страница 15: ...47 k pull down to Shield RS 485 signal ground Wire the RS 485 bus as a daisy chain from device to device without any stubs Use 120 termination resistors at each end of the bus not included Shield is...

Страница 16: ...status 0x00 if the reset system is used bytes5 ID string Veris Industries E50xx Power Meter Full Data Set or Veris Industries E50xx Power Meter RESET SYSTEM RUNNING RSVersion x xxx last 2 bytes CRC 0x...

Страница 17: ...atio of 2 1 The default is 100 1 00 1 which is with no PT attached Set this value before setting the system voltage below 134 R W NV UInt 82 32000 SystemVoltage This voltage is line to line except for...

Страница 18: ...nd a pulse duration that will keep up with the max system power register 135 it will reject the new value Try a larger value kWh Pulse Contacts Note The kWh pulse contact can keep up with a maximum po...

Страница 19: ...nge Description 152 R W NV UInt 0 32767 Power Up Counter 153 R NV UInt 0 32767 Output Configuration E50C1 always returns 0 154 R UInt Reserved returns 0 Floating Point Data 257 258 R NV Float kWh Real...

Страница 20: ...ct connection to the same service PT polarity and adequate powering See theWiring Diagrams section for more information Cannot communicate with power meter from a remote personal computer Power meter...

Отзывы: