Installation Guide

Power Monitoring

E50B1A, E50C2A, E50C3A

TM

Modbus Point Map 
Overview

The E50C2A Full Data Set (FDS) features data outputs such as demand calculations, per phase VA and VAR, and VAh VARh 
accumulators. The E50C3A data logging model adds configuration registers 155-178 and buffer reading at registers 8000-13760. 
For security reasons, configuration and resets on all E50 models are protected by a user configurable passcode. The meter supports 
variable CTs and PTs, allowing a much wider range of operation from 90V x 5A up to 32000V x 5000A. To promote this, the meter 
permits variable scaling of the 16-bit integer registers via the scale registers. The 32-bit floating point registers do not need to be 
scaled.

Integer registers begin at 001 (0x001). Floats at 257 (0x101). Configuration registers at 129 (0x081). Values not supported in a 
particular System Type configuration will report QNAN (0x8000 in Integer Registers, 0x7FC00000 in Floating Point Registers).

Supported Modbus Commands

Note:  ID String information varies from model to model. Text shown here is an example.

Command

Description

0x03

Read Holding Registers

0x04

Read Input Registers

0x06

Preset Single Register

0x10

Preset Multiple Registers

0x11

Report ID
Return string:
byte0:   address
byte1:   0x11
byte2:   #bytes following w/out crc
byte3:   ID byte = 247
byte4:   status = 0xFF if the operating system is used; status = 0x00 if the reset system is used
: ID string = “Veris Industries E50xxA Power Meter Full Data Set”  or “Veris Industries E50xxA Power Meter - RESET 

SYSTEM RUNNING RS Version x.xxx” last 2 bytes: CRC

0x2B

Read Device Identification, BASIC implementation (0x00, 0x01 and 0x02 data), Conformity Level 1.
Object values:
0x01: “Veris Industries”
0x02: “ E50xxA”
0x03: “Vxx.yyy”, where xx.yyy is the OS version number (reformatted version of the Modbus register #7001, (Firmware 

Version, Operating System).  

If register #7001 == 12345, then the 0x03 data would be “V12.345”).

Legend

The following table lists the addresses assigned to each data point. For floating point format variables, each data point appears 
twice because two 16-bit addresses are required to hold a 32-bit float value.

R/W 

R=read only; R/W=read from either int or float formats, write only to integer format.

NV

Value is stored in non-volatile memory. The value will still be available if the meter experiences a power loss and reset. 

Format

UInt

Unsigned 16-bit integer.

SInt

Signed 16-bit integer.

ULong

Unsigned 32-bit integer; Upper 16-bits (MSR) in lowest-numbered / first listed register (001/002 = MSR/LSR).

Float

32-bit floating point; Upper 16-bits (MSR) in lowest-numbered / first listed register (257/258 = MSR/LSR). Encoding 

is per IEEE standard 754 single precision.

Units

Lists the physical units that a register holds.

Scale Factor   Some Integer values must be multiplied by a constant scale factor (typically a fraction), to be read correctly. This is done to allow 

integer numbers to represent fractional numbers.

Range

Defines the limit of the values that a register can contain.

Содержание E50B1A

Страница 1: ...to radio communications This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must...

Страница 2: ...38400 baud Modbus RTU MECHANICAL CHARACTERISTICS Weight 0 62 lb 0 28 kg IP Degree of Protection IEC 60529 IP40 front display IP20 Meter Display Characteristics Back lit blue LCD Terminal Block Screw...

Страница 3: ...TM Table of Contents Dimensions 4 Data Outputs 4 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power Diagrams 9 Quick Setup Instru...

Страница 4: ...figurable for CT PT ratios system type and passwords Diagnostic alerts Current 3 phase average Volts 3 phase average Current by phase Volts by phase Line Line and Line Neutral Power Real Reactive and...

Страница 5: ...only CONTROL POWER 0 1A 50 60 Hz A B C N 1 2 A B C Alarm Energy NC NO S OUTPUT IA IB IC Phase Loss Alarm Pulse VA VB VC Neutral Earth Control Power Output varies by model UL 90V L N 600V L L CE 90V L...

Страница 6: ...ays on standard 35 mm DIN rail or screw mounted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots fr...

Страница 7: ...in a particular System Type display as on the User Interface or as QNAN in the Modbus registers CTs Voltage Connections SystemType Phase Loss Measurements Wiring Diagram Number of wires Qty ID Qty ID...

Страница 8: ...ions may cause injury death or equipment damage WARNING Wiring N L1 X2 X1 White Black A B C N A B C Diagram1 1 PhaseLine to Neutral2 Wire System1CT Diagram2 1 PhaseLine to Line2 Wire System1CT L1 L2 X...

Страница 9: ...heControlPowerTransformermaybewiredL NorL L Outputto meetmeterinputrequirements DCControlPowerfrom125VDCto300VDC ULandCEmax FuseRecommendations Keep the fuses close to the power source obey local and...

Страница 10: ...aud rate c to the PAR screen Use the or buttons to select the parity d back to the S COM screen 6 to the S CT Set Current Transducer screen If this unit does not have an RS 485 port this will be the f...

Страница 11: ...arm either loss of phase when the meter is powered or loss of power when the meter is not The contacts are open when the meter is powered and no phase loss alarm conditions are present The over curren...

Страница 12: ...s A Average of Active Phases Volts Line Neutral V Average of Active Phases Total Real Power P Power Factor Average of Active Phases 3 KVA Total Apparent Power S B A B VBC B KW B VLN C A C VAC C KW C V...

Страница 13: ...Voltage Clipping A B C INFO MODEL OS SN RS Serial Number Reset System Operating System ALERT INFO PLOSS A b C LOWPF A b C F ERR A I OVR A b C V OVR A b C PASWD 00000 PASWD 00000 Model Number Energy Pu...

Страница 14: ...3L 2L 1n 2L 1L 1n Back To SETUP Back Back Back S COM To Setup p 2 SPLOS Next S PT Set Potential Transfomer Ratio RATIO Potential transformer step down is RATIO 1 Default is 1 1 No PT installed See In...

Страница 15: ...ration error bit in the Modbus Diagnostic Alert Bitmap if equipped Wh P Set Pulse Energy In Watt Hours VAR Hours if present per Pulse When moving down to a smaller energy the meter will not allow the...

Страница 16: ...y the subinterval timer The default subinterval is 15 minutes at a 15 minute interval setting the buffers hold 60 days of data An external timer can be used over Modbus by setting this register to 0 U...

Страница 17: ...ted power cycle etc during the previous demand sub interval and whether the Real Time Clock has been changed re initialized to default date time due to a power cycle or modified via Modbus commands Da...

Страница 18: ...s 0x11 Report ID Return string byte0 address byte1 0x11 byte2 bytes following w out crc byte3 ID byte 247 byte4 status 0xFF if the operating system is used status 0x00 if the reset system is used byte...

Страница 19: ...er Factor Phase B 015 R UInt Ratio 0 0001 0 10000 Power Factor Phase C 016 R UInt Volt V 0 32767 Voltage Phase A B 017 R UInt Volt V 0 32767 Voltage Phase B C 018 R UInt Volt V 0 32767 Voltage Phase A...

Страница 20: ...ite no more frequently than every 10 seconds Write 16640 0x4100 to Reset Logging E50C3A only Write 16498 0x4072 to Clear Pulse Counters to 0 Read always returns 0 130 R W NV UInt 10 11 12 31 40 Single...

Страница 21: ...ase should be 277V When the threshold is set to 10 if any phase drops more than 10 below 277V less than 249V or if any L L voltage drops more than 10 below 480V less than 432V the corresponding phase...

Страница 22: ...gister register 144 and reset the energy accumulators see reset register 129 Bit 15 Energy pulse output configuration error present pulse energy setting may not keep up with the theoretical max system...

Страница 23: ...nd register 129 Bit 1 Log Buffer Read Collision 1 Set to 1 if the meter tried to save log data while the user was reading the log Logging Page Register has been set to something other than 0 On the fi...

Страница 24: ...egister Pointer 4 Default is 30 Reactive Energy LSR 173 R W NV UInt Log Register Pointer 5 Default is 37 Real Demand 174 R W NV UInt Log Register Pointer 6 Default is 38 Reactive Demand 175 R W NV UIn...

Страница 25: ...l Real Power Present Demand 327 328 R Float kVAR Total Reactive Power Present Demand 329 330 R NV Float kVA Total Apparent Power Present Demand 331 332 R NV Float kW Total Real Power Max Demand 333 33...

Страница 26: ...parameters CT and PT ratings system type etc See the Setup section Incorrect voltage inputs Check power meter voltage input terminals to verify adequate voltage Power meter is wired improperly Check a...

Отзывы: