VUT 100 P mini
MOUNTING AND SET-UP
The unit is designed for suspended mounting by means of the threaded rod fixed in the threaded dowel pin.
While mounting the unit provide the minimum required access to the unit for maintenance and repair. The required minimum
distances from the unit to the wall is shown below.
min 400 mm
min 10 mm
min 300 mm
Nut
Washer
Vibration-absorbing rubber
Nut and lock-nut
Mounting example
Precautions:
The unit is designed for mounting on a rigid and stable structure.
The unit is mounted with anchor bolts. Make sure that a mounting construction has sufficient load capacity matching the unit weight.
Otherwise reinforce an installation place by beams, etc.
If the threaded bolts used for the unit mounting are too short the unit can generate abnormal noise and resonate with the ceiling. The
suspended bolts must be long enough to prevent resonating.
If the unit connection place to the spiral seam duct is supposed to be the source of abnormal noise, install a flexible air duct instead of the
flexible one. Optionally the flexible connectors may also be used to prevent resonating.
CONDENSATE DRAINAGE
The condensate drain pan has pipes for extracting the condensed fluid outside the unit.
Connect the pipe, U-trap (not included in delivery package) and sewage collection system with metal, plastic or rubber connecting
pipes and. The pipe slope downwards must be at least 3°. Fill up the system with water before connecting the unit to the power mains! The
U-trap must be filled with water at all times during the unit operation. Make sure that the water flows freely into the sewage collection
system or otherwise condensed water may build up in the unit during the heat exchanger operation which, in turn, may cause equipment
failure and water ingress into the premises.
The condensate drainage system is designed for normal operation in premises with air temperatures above 0 °C. If the expected air
temperatures are below 0 °C the condensate drainage system must be equipped with heat insulation and pre-heating facilities.
Drain pipe
Pipe
U-trap
Pipe
Sewage system
min 3°
UNIT MOUNTING
CONDENSATE DRAINAGE ARRANGEMENT