background image

USER’S MANUAL

VUT 100 P mini

Heat recovery air handling unit

Содержание VUT 100 P mini

Страница 1: ...USER S MANUAL VUT 100 P mini Heat recovery air handling unit ...

Страница 2: ...al parameters 6 Design and operating logic 7 Mounting and set up 8 Condensate drain 8 Connection to power mains 9 Unit control 9 Maintenance 10 Troubleshooting 11 Storage and transportation rules 11 Manufacturer s warranty 12 Acceptance certificate 13 Seller s information 13 Mounting certificate 13 Warranty Card 14 ...

Страница 3: ...e unit While transferring the unit control the user s manual must be turned over to the receiving operator Symbol legend used in the manual UNIT MOUNTING SAFETY PRECAUTIONS WARNING DO NOT The unit must be disconnected from the power supply prior to every installation or repair operation The unit must be grounded The unit must not be operated outside the temperature range stated in the user s manua...

Страница 4: ...nit and do not put any objects on it OFF ON Disconnect the unit from power supply prior to maintenance Do not let children operate the unit Do not damage the power cable while operating the unit Do not put any objects on the power cable Keep combustible gases and inflammable products away of the unit Do not open the operating unit In case of unusual sounds smoke disconnect the unit from power supp...

Страница 5: ...o warm up the clean supply air The unit is designed for wall mounting The unit is rated for continuous operation always connected to power mains Transported air must not contain any flammable or explosive mixtures evaporation of chemicals coarse dust soot and oil particles sticky substances fibrous materials pathogens or any other harmful substances Unit 1 item User s manual 1 item Speed switch 1 ...

Страница 6: ...so some models may slightly differ from those ones described in this manual 595 397 96 105 212 404 164 UNIT OVERALL DIMENSIONS MM UNIT TECHNICAL DATA Model VUT 100 P mini Speed low medium high Supply voltage 50 Hz V 1 230 Power W 30 38 56 Total unit current A 0 18 0 23 0 34 Air capacity m3 h 57 78 106 RPM min 1 1300 1950 2500 Noise level dB A 24 32 41 Max transported air temperature C from 25 up t...

Страница 7: ...r from outside and warms it up Heat recovery minimizes thermal energy losses energy demand and operating costs for air heating accordingly SUPPLY AIR EXTRACT AIR EXHAUST AIR INTAKE AIR Extract fan Drain pan Thermostat Heat exchanger fan UNIT OPERATING LOGIC TOP VIEW The freeze protection thermostat is installed in the exhaust air duct downstream of the heat exchanger In case of a freeze danger the...

Страница 8: ...rmal noise install a flexible air duct instead of the flexible one Optionally the flexible connectors may also be used to prevent resonating CONDENSATE DRAINAGE The condensate drain pan has pipes for extracting the condensed fluid outside the unit Connect the pipe U trap not included in delivery package and sewage collection system with metal plastic or rubber connecting pipes and The pipe slope d...

Страница 9: ...rminal marking The terminal marking is shown inside of the terminal box The unit terminal clamps are marked according to the marking on the wiring diagram Route the wires to the terminal box through the stepped grommet on the unit side panel to preserve the electrical protection class Connect the unit to power mains through the external automatic circuit breaker with magnetic trip integrated into ...

Страница 10: ...emove four triangular screws 2 Remove the filter covers 3 Pull the filters downwards to remove 1 Undo four clips 2 Remove the service panel 3 Turn the retaining support to loosen and remove the heat exchanger HEAT EXCHANGER REMOVAL AS FOLLOWS DISCONNECT THE UNIT FROM POWER SUPPLY PRIOR TO MAINTENANCE DISCONNECT THE DRAIN PIPE PRIOR TO HEAT EXCHANGER MAINTENANCE 1 2 3 1 2 3 2 Heat exchanger mainten...

Страница 11: ...Contact the service centre Low air flow Low set fan speed Set higher speed The filters the fans or the heat exchanger are dirty Clean or replace the filter clean the fans and the heat exchanger The ventilation system components air ducts diffusers louver shutters grilles are clogged or damaged Clean or replace the ventilation system components such as air ducts diffusers louver shutters grilles Lo...

Страница 12: ...espective details stated on the unit packing and in the user s manual User s failure to ensure timely technical maintenance of the unit External damage to the casing excluding external modifications of the unit as required for its installation and the internal components of the unit Alteration of the unit design or engineering changes of the unit Replacement and use of the unit assemblies parts an...

Страница 13: ... the product with the requirements relating to electromagnetic compatibility was based on the following standards Quality Inspector s Stamp The heat recovery air handling unitVUT 100 P mini has been connected to power mains pursuant to the requirements stated in the present user s manual Company name Address Telephone Installation technician s full name Installation date Signature Shop name Addres...

Страница 14: ..._______________________________________________________________________________________________ ______________________________________________________________________________________________________ ______________________________________________________________________________________________________ __________________________________________________________________________________________________...

Страница 15: ...2013 V59EN 04 ...

Отзывы: