www.ventilation-system.com
15
UNIT CONTROL
The unit is operated via the control panel A11, A14 or A19 depending on the unit model. For details, please refer to the user's manual
for the respective control panel.
UNIT CONTROL WITH SOFTWARE
To enable operation of the unit using the pre-installed software connection the unit to a laptop or PC via a USB cable with a Type A
and Type B connectors. The USB cable is not included in the scope of delivery.
USB Type B
USB Type A
USB Type B
VUT/VUE 200 V(B) A14
VUT/VUE 250 V(B) A14
The software enables editing the unit parameters:
Parameter
Factory setting
Control range
Zero speed (off) [%]
0
0 - 100
Low speed [%]
40
0 - 100
Medium speed [%]
70
0 - 100
High speed [%]
100
0 - 100
Unit speed with the closed dry contact of the external control unit [%]
100
0 - 100
Filter cleaning (replacement) interval
2160 (3 months)
0 - 10000
Humidity level [%]
60
30 - 80
The list of the adjustable parameters can be expanded in new versions of the software.
Setting, troubleshooting and upgrading of the software version is made by the service technician.
The software is available for downloading on our website: http://vents.ua/images/cat/812_2902_cat_file.rar.