Содержание VKV 250 EC

Страница 1: ...USER S MANUAL ROOF FANS VENTS VKV VKH VKV EC VKH EC VKMK VKMKp VOK VOK1 SERIES...

Страница 2: ...key Technical data Safety requirements Installation and set up Connection to power mains Storage regulations Technical maintenance Manufacturer s warranty Certificate of acceptance Warranty card 3 3 4...

Страница 3: ...ontain dust solid particles sticky and fibrous materials The ambient temperature must not exceed the values stated in the Technical data sec tion The fan is suitable for vertical mounting on the exhau...

Страница 4: ...poles E single phase D three phase Impeller diameter mm 200 220 225 250 280 300 310 350 355 400 450 500 2 4 6 XXX XXX XX VKV centrifugal roof fan with vertical air discharge VKH centrifugal roof fan w...

Страница 5: ...VKV 2E 280 centrifugal roof fan with vertical air discharge a two pole single phase electric motor and a 280 mm impeller VKV 280 EC centrifugal roof fan with vertical air discharge an EC electric moto...

Страница 6: ...454 872 535 668 30 0 VKV 6E 500 438 454 872 535 668 33 8 VKV VKH Model Dimensions mm Weight kg D d H L L1 L2 VKH 2E 220 213 10 228 338 245 338 6 9 VKH 2E 225 213 10 228 338 245 338 7 1 VKH 2E 250 285...

Страница 7: ...900 940 1300 1480 1780 1855 RPM min 1 2700 2810 2650 2830 2600 2640 2700 2790 Sound pressure level at a distance of 3 m dBA 49 51 49 51 65 70 66 69 Max transported air temperature 55 50 55 50 50 50 5...

Страница 8: ...438 11 357 595 450 558 81 VKH 450 438 11 407 665 535 637 82 VKH 500 438 11 437 665 535 637 81 VKH 560 605 14 487 940 750 912 98 Model Dimensions mm Weight kg D H L L1 L2 VKV 250 285 320 435 330 528 1...

Страница 9: ...t a distance of 3 m dBA 48 51 Max transported air temperature 25 60 25 60 Ingress protection rating IPX4 IPX4 VKV VKH 400 VKV VKH 450 Unit voltage V 50 60 Hz 3 380 480 3 380 480 Power kW 0 77 1 01 Cur...

Страница 10: ...150 VKMK 160 VKMK 200 VKMK 250 VKMK 315 Voltage V 1 220 240 1 220 240 1 220 240 1 220 240 Frequency Hz 50 60 50 60 50 60 50 60 Power W 98 119 154 205 194 240 296 413 Current A 0 43 0 52 0 67 0 9 0 85...

Страница 11: ...0 50 60 50 60 50 60 50 60 Power W 55 61 80 91 50 56 145 178 75 92 140 147 Current A 0 26 0 28 0 4 0 42 0 22 0 24 0 66 0 79 0 35 0 4 0 65 0 66 Maximum air flow m3 h 860 875 1050 1150 800 865 2230 2280...

Страница 12: ...585 450 11 5 VOK1 200 VOK1 250 VOK1 315 Voltage V 1 230 Frequency Hz 50 60 50 60 50 60 Power W 43 33 68 76 110 104 Current A 0 28 0 21 0 48 0 51 0 75 0 7 Maximum air flow m3 h 405 470 1070 1050 1700...

Страница 13: ...objects in side the casing that can damage the impeller blades Misuse of the fan and any unauthorized modifications are not allowed The unit is not to be used by children and persons with reduced phys...

Страница 14: ...e has holes for fastening bolts for connection of the fan to the level surface or to the roof curb The roof curb intake flange and fastening bolts are not included in the delivery set and can be order...

Страница 15: ...15 VKV VKV QF 1 2 3 4 6 5 7 8...

Страница 16: ...16 VKH VKH QF 3 1 2 3 4 1 2 3 4...

Страница 17: ...17 QF QF 3 1 2 3 4 1 2 3 4 VKMK VKMKp...

Страница 18: ...pending on the modification the fans are powered by single phase AC 230 V 50 60 Hz or three phase AC 400 V 50 60 Hz The connection must be made using insulated conductors cables wires The external pow...

Страница 19: ...normally closed contact of the motor overheating protection This contact must be connected in series to the power supply circuit of the KM1 magnetic starter coil which starts the motor after pressing...

Страница 20: ...20 L1 TW1 TW2 S1 ON S2 OFF KM1 L2 L3 QF 400 V 50 60 Hz L1 L2 L3 N PE PE Fan L N X1 1 2 3 L QF N PE TW1 4 5 6 TW2 230 V 50 60 Hz KM1 S1 ON S2 OFF KM1...

Страница 21: ...circuit breaker not included in the delivery set X1 is the terminal block where QF is the automatic circuit breaker not included in the delivery set X1 is the terminal block Wiring diagram of the VKV...

Страница 22: ...0 Hz L2 L1 X1 2 7 1 3 L3 L3 5 4 6 V1 U1 W1 W2 PE U2 V2 L1 L2 L3 8 9 TW2 TW1 TW1 TW2 TW1 TW2 L2 L1 QF PE 400 V 50 60 Hz L2 L1 X1 2 4 1 3 L3 L3 where QF is the automatic circuit breaker not included in...

Страница 23: ...5 EC VKV VKH 400 EC VKV VKH 450 EC and VKV VKH 560 EC fans KL3 KL2 KL1 Terminal Connection Function PE PE Protective ground conductor KL1 L3 Mains L3 L2 Mains L2 L1 Mains L1 KL2 NC Alarm relay normall...

Страница 24: ...lication 5 50 VDC Blocking current carrying bridge to ground bus or application of 1 VDC Reset function reset func tion enabled at voltage level change to 1 VDC PELV Din2 Digital input 2 switching bet...

Страница 25: ...he VOK 2E 200 VOK 2E 250 VOK 4E 250 VOK 2E 300 VOK 4E 300 VOK 4E 350 fans Wiring diagram of the VOK1 200 VOK1 250 and VOK1 315 fans where QF is the automatic circuit breaker not included in the delive...

Страница 26: ...26 1 2 5 4 3 6 VKH...

Страница 27: ...27 VKH 1 2 5 4 3...

Страница 28: ...28 VKV VKV 1 2 4 3 6 5...

Страница 29: ...29 VKMK VKMKP 1 2 4 3 6 5...

Страница 30: ...KV 1 2 4 3 STORAGE REGULATIONS Store the unit in the manufacturer s original packaging box in a dry closed ventilated prem ise with temperature range from 5 C to 40 C and relative humidity of up to 80...

Страница 31: ...operations Use a dry soft brush or compressed air to remove dust The impeller blades require thorough cleaning at least once in 6 months To clean the soiled fan internal parts perform a partial fan d...

Страница 32: ...32 VKH VKV VKV QF 1 2 4 3 QF 1 2 4 3...

Страница 33: ...33 VKMK VKMKP VOK VOK1 QF 1 2 4 3 QF 1 2 4 3...

Страница 34: ...is not responsible for compatibility of their goods with other producers goods The warranty covers the manufacturing defects only All the defects and faults resulting from gross mechanical effect dur...

Страница 35: ...IFICATE OF ACCEPTANCE Model VENTS VKV VKH VKV VKH VKMK VKMKp VOK VOK1 tick the proper model only __________________________________________________________________________ ____________________________...