ASYNCHRONOUS ELECTRIC MOTOR STARTING METHODS

There are several methods for starting asynchronous squirrel-cage electric motors.
The most common methods are: direct-on-line (DOL), with a soft starter (SS) or with a frequency converter (FC).

Direct-on-line starting

In case of direct-on-line starting (i.e. by connecting the motor to the electric mains with a simple line contactor), the motor starting 
time significantly increases due to high inertia of the impeller, which, in turn, results in high in-rush starting currents in the circuit. These 
currents of long duration may cause voltage slumps (especially if the feed line section falls short of the requirements), which may affect 
load operation.
The in-rush current consumed by an electric motor in case of DOL starting is 5-8 times larger than the rated value (or even 10-14 times 
larger in some rare instances). It should be noted that the torque developed by the motor also significantly exceeds the rated value.
Upon energisation the motor operates as a transformer with a squirrel-cage secondary winding formed by the rotor cage with a very low 
resistance.
The rotor develops high induced current causing a rush of current in the feed line.
The startup torque during starting averages 0.5-1.5 of the rated torque value.

Despite such advantages as simple construction, high startup current, quick start and low cost, direct-on-line systems are suitable only 
in the following cases:
•  the motor power is low compared to the mains power which limits the adverse effect of the rush of current
•  the driven mechanism does not require gradual speed build-up or is equipped with a damping device to smooth out the inrush
•  the high startup torque has no adverse effects on the operation of the driven mechanism

Soft start. SS starting.

A soft starter gradually increases the voltage supplied to the motor – from the initial to the rated value.
This starting system can be used to meet the following goals:
•  limit the motor current
•  regulate the torque

Regulation by limiting the current sets the maximum in-rush current equal to 300-400 % (or  250 % in some rare instances) of the rated 
current and reduces torque characteristics. This type of regulation is especially suited for turbomachinery such as centrifugal pumps and 
fans.
Regulation by variation of torque optimizes the torque during startup and reduces in-rush current in the circuit. These conditions are 
suitable for mechanisms with constant load resistance.
This type of soft starting may differ in the implementation pattern:
•  motor start
•  motor start and stop
•  device bridging at the end of start sequence
•  start and stop of several motors in stage circuits

Soft start. FC starting.

During the starting the FC raises the frequency from 0 Hz to the electrical mains frequency (50 or 60 Hz). As the frequency is increased 
gradually, the motor can be assumed to operate at its rated speed for a given frequency value. Furthermore, on the assumption that the 
motor runs at its rated speed the nominal torque should be immediately available whereas the current will be approximately equal to 
the rated value.
This starting system is used for speed control and regulation and can be used in the following cases:
•  start with high-inertia load
•  start with high load and limited-capacity power supply source
•  optimization of electric power consumption depending on turbomachinery speed
The aforementioned starting system can be used for all types of mechanisms.

Problems associated with DOL starting

The problems caused by DOL starting may be divided into two groups:
1.  An abrupt start causes mechanical shock, jolts in the mechanism, shock removal of free play etc.
2.  A heavy start cannot be completed.

Содержание VKPD

Страница 1: ...USER S MANUAL VKPD Duct rectangular smoke extraction fan...

Страница 2: ...language in any form without the prior written permission of the Company Safety requirements 2 Purpose 4 Delivery set 4 Designation key 4 Technical data 5 Design and operating principle 6 Mounting an...

Страница 3: ...stallation and maintenance operations with wet hands Do not wash the unit with water Protect the electric parts of the unit against ingress of water Do not allow children to operate the unit The unit...

Страница 4: ...BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED ACCESS BY UNATTENDED CHILDREN Duct re...

Страница 5: ...315 2D 1 1 600x350 1 1 2880 2 4 3 400 VKPD 315 2 4D 1 1 0 25 600x350 1 1 0 25 2880 1440 355 4 1 230 VKPD 355 4E 0 37 700x400 0 37 1420 4 3 400 VKPD 355 4D 0 37 700x400 0 37 1420 4 6 3 400 VKPD 355 4...

Страница 6: ...ot included in the delivery set ordered separately Model Dimensions mm Weight kg A A1 A2 B B1 B2 L H VKPD 250 500 520 540 300 320 340 680 557 40 VKPD 280 600 620 640 300 320 340 680 558 40 VKPD 315 60...

Страница 7: ...the air duct It is recommended to suspend the fan to the ceiling using steel reinforcement and threaded rods or using perforated galvanized plates and connecting them to the fan flanges or to an auxi...

Страница 8: ...depending on the wire type insulation length and installation method Connection of the unit to the fixed power supply network must be carried out in accordance with the current regulations Access to t...

Страница 9: ...mechanism Soft start SS starting A soft starter gradually increases the voltage supplied to the motor from the initial to the rated value This starting system can be used to meet the following goals...

Страница 10: ...the best case scenario an SS device may help reduce the in rush current to 250 of the motor rated current If this is insufficient an FC is necessary 2 The motor cannot start the mechanism with DOL st...

Страница 11: ...ore starting maintenance works Clean the impeller blades with a soft cloth wetted in mild water detergent solution Avoid liquid dripping on the motor Wipe the fan surfaces dry after cleaning While cle...

Страница 12: ...ompliance certificate The selection should be limited to the top five foreign switching equipment manufacturers The fan fails to reach the required rotation speed due to serious overheating of the fan...

Страница 13: ...calculate the network parameters and select a matching fan The network resistance exceeds the design calculations Re arrange the ventilation network to decrease its aerodynamic resistance Wrong direct...

Страница 14: ...and in the user s manual User s failure to ensure timely technical maintenance of the unit External damage to the unit casing excluding external modifications as required for installation and interna...

Страница 15: ..._____________________________ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Nam...

Страница 16: ...V228EN 01...

Отзывы: