13

STORAGE AND TRANSPORTATION REGULATIONS

•  Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range 

from +5 ˚С  to +40 ˚С  and relative humidity up to 70 %.

•  Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing 

deformation.

•  Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
•  Follow the handling requirements applicable for the particular type of cargo.
•  The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and 

mechanical damage. The unit must be transported only in the working position.

•  Avoid sharp blows, scratches, or rough handling during loading and unloading.
•  Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 

3-4 hours.

The fan supplies less air than 

expected.

Wrong calculation of the ventilation network and 

wrong selection of the fan.

Re-calculate the network parameters and select a 

matching fan.

The network resistance exceeds the design 

calculations.

Re-arrange the ventilation network to decrease its 

aerodynamic resistance.

Wrong direction of the impeller rotation.

If necessary, change the impeller rotation direction by 

changing the phase sequence on the electric motor 

terminals 

(see the “Commissioning” section)

.

Air leak through a loose air duct connection.

Eliminate the air leak. Seal the air duct connection.

Impeller or air duct contamination with foreign 

objects or debris.

Clean the impeller or the air ducts from foreign objects or 

debris.

Excessive noise or vibration both 

inside the fan and in the circuit.

Loose screw connections.

Check the screw connections for proper tightness.

No flexible joints between the fan and the ventilation 

network on the suction and discharge sides.

Install flexible joints.

Loose connection of valves and dampers to the air 

ducts.

Tighten up the fasteners of valves and dampers.

Impeller or air duct contamination with foreign 

objects or debris.

Clean the impeller or the air ducts from foreign objects or 

debris.

Worn bearings.

Replace the bearings.

Unstable power supply, unstable motor operation.

Check the stability of power supply parameters and 

electric motor operation.

Содержание VKPD

Страница 1: ...USER S MANUAL VKPD Duct rectangular smoke extraction fan...

Страница 2: ...language in any form without the prior written permission of the Company Safety requirements 2 Purpose 4 Delivery set 4 Designation key 4 Technical data 5 Design and operating principle 6 Mounting an...

Страница 3: ...stallation and maintenance operations with wet hands Do not wash the unit with water Protect the electric parts of the unit against ingress of water Do not allow children to operate the unit The unit...

Страница 4: ...BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED ACCESS BY UNATTENDED CHILDREN Duct re...

Страница 5: ...315 2D 1 1 600x350 1 1 2880 2 4 3 400 VKPD 315 2 4D 1 1 0 25 600x350 1 1 0 25 2880 1440 355 4 1 230 VKPD 355 4E 0 37 700x400 0 37 1420 4 3 400 VKPD 355 4D 0 37 700x400 0 37 1420 4 6 3 400 VKPD 355 4...

Страница 6: ...ot included in the delivery set ordered separately Model Dimensions mm Weight kg A A1 A2 B B1 B2 L H VKPD 250 500 520 540 300 320 340 680 557 40 VKPD 280 600 620 640 300 320 340 680 558 40 VKPD 315 60...

Страница 7: ...the air duct It is recommended to suspend the fan to the ceiling using steel reinforcement and threaded rods or using perforated galvanized plates and connecting them to the fan flanges or to an auxi...

Страница 8: ...depending on the wire type insulation length and installation method Connection of the unit to the fixed power supply network must be carried out in accordance with the current regulations Access to t...

Страница 9: ...mechanism Soft start SS starting A soft starter gradually increases the voltage supplied to the motor from the initial to the rated value This starting system can be used to meet the following goals...

Страница 10: ...the best case scenario an SS device may help reduce the in rush current to 250 of the motor rated current If this is insufficient an FC is necessary 2 The motor cannot start the mechanism with DOL st...

Страница 11: ...ore starting maintenance works Clean the impeller blades with a soft cloth wetted in mild water detergent solution Avoid liquid dripping on the motor Wipe the fan surfaces dry after cleaning While cle...

Страница 12: ...ompliance certificate The selection should be limited to the top five foreign switching equipment manufacturers The fan fails to reach the required rotation speed due to serious overheating of the fan...

Страница 13: ...calculate the network parameters and select a matching fan The network resistance exceeds the design calculations Re arrange the ventilation network to decrease its aerodynamic resistance Wrong direct...

Страница 14: ...and in the user s manual User s failure to ensure timely technical maintenance of the unit External damage to the unit casing excluding external modifications as required for installation and interna...

Страница 15: ..._____________________________ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Nam...

Страница 16: ...V228EN 01...

Отзывы: