SPECIFICATIONS
2. SPECIFICATIONS
VS1200 CMh/e S
PECIFICATIONS
Flow Rate
300 - 1200 cfm / 510 - 2040 m
3
/h
Increments: 50 cfm / 85 m
3
/h
Max. External Static Pressure
2.0 inch W.C. / 498 Pa
Exchanger Efficiency (AHRI 1060)
HRV: 90.6% Sensible
ERV: 86.1% Sensible; 77.9% Latent; 82.9% Total
Temperature Conditions
Outdoor: -4
°
to 104
° F
/ -20
°
to 40
°
C
Ambient: 41
°
to 104
° F
/ 5
°
to 40
°
C
Max. Return Air Humidity
90%
Dimensions (L x W x D)
67.3” x 18.5” x 78.7” / 1.71 m x 0.47 m x 2 m
Shipping Dimensions (L x W x D)
75” x 25” x 91” / 1.91 m x 0.64 m x 2.3 m
Weight (Shipping)
HRV: 529 lbs / 240 kg (Shipping: 678 lbs / 308 kg)
ERV: 547 lbs / 248 kg (Shipping: 701 lbs / 318 kg)
Fans (EC, Variable Speed Control)
Aluminum Impeller; 1890 RPM; IP54
Filters
Outside Air: MERV13 (29.53 x 15.55 x 3.78 in. / 750 x 395 x 96 mm)
Return Air: MERV9 (29.53 x 15.55 x 3.78 in. / 750 x 395 x 96 mm)
Preheater
Integrated Preheater for Frost Prevention
Core Bypass
PID Bypass Damper for Temperature Control
Insulation & Thermal Conductivity
2” Foam @ 0.042 W/mK / 0.024 BTU/(hr ft
°
F); 0.8mm Galvanized Steel Inner/Outer Casing
Duct Connection
23.62” x 11.81” / 600 mm x 300 mm; Diameter 15.75” / 400 mm
Operation Modes
CAV, DCV, VAV, BMS, Economizer (Freecooling)
Certifications
TUV SUD (UL 1812, CSA 22.2 No. 113) Pending
Passive Haus: Pending
FCC Pending
Sensors
Temperature (10Kohm NTC Thermistors):
Outside Air, Supply Air, Supply Duct, Return Air, Exhaust Air
Pressure:
OA and RA Filter Pressure Drop
Pressure Differential at Supply Fan and Exhaust Fan (CAV)
Pressure Differential of Supply to Atmosphere (VAV)
Optional Accessories
(Provided by Ventacity)
External Outside Air and Exhaust Air Damper Modules
External DX or WCO Postheater Modules
Internally Mounted CO2 Sensor (Room CO2 Sensor Recommendations Available)
External Condensate Pump
ELECTRICAL
Voltage
Phase
Power Supply
FLA – Max
MCA
MOP
De-Ice Preheater
Preheater Temp Rise
Maximum Power
per Fan
208 VAC
1
6.2 kW
29.8 A
36.7 A
35 A
5.2 kW
7.7
°
C
503 W (0.67 hp)
240 VAC
1
7.9 kW
33.1 A
40.7 A
40 A
6.9 kW
10.3
°
C
FAN OPERATING RANGE
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0
External Static Pressure [in W
.C.]
0
200
400
600
800
1,000
Flow Rate [CFM]
300 – 1,200 CFM
0 – 2.0" W.C. ESP
1,200
100% FAN SPEED
(recommended operating range)
1,400