![Ventacity Systems VS1200 CMh/e Скачать руководство пользователя страница 23](http://html.mh-extra.com/html/ventacity-systems/vs1200-cmh-e/vs1200-cmh-e_installation-and-operation-manual_865552023.webp)
23
Rev. 01.01
INSTALLATION
4. INSTALLATION
• Insert the other end of the cable to one of the
connectors on the control computer board.
4.8.3 CONTROL PANEL CONNECTION
To activate the unit, it is necessary to connect the
control panel and the unit using the communication
cable (data cable).
• Loosen the screw on the bottom of the con-
trol panel.
• Open the control panel case.
• Connect the control cable conductors as
shown below.
• Attach the user interface panel to the wall.
• Close and tighten the control panel case.
READ CAREFULLY!
● The supply and the control cable should be as far
apart from each other as possible.
● Make sure that the cable has been properly
connected at screw terminals.
● Be careful not to damage cable insulation when
fixing the control panel to the wall or to other
surface.
● If you do not connect cables directly during
the unit’s installation, protect them against
mechanical damage or short circuit with
insulating tape.
● Cable connectors must not come into contact
with water or other liquid.
4.8.4 CONNECTING UNIT TO BMS CONTROL
SYSTEM
The HRV unit’s control includes the RS-485
interface. Connect the HRV computer control with
a standard Cat6, RJ45 communication cable. Insert
the cable BMS end into one of the connectors on
the HRV unit’s computer control board. Connect
the other end to the main BMS end computer
control.
1.
3.
5.
2.
4.
6.
CANL
(30)
CANH (29)
+12V (27)
GND (28)
Control panel
1
1.
1
5.
1
6.
1
2.
1
7.
1
8.
1
9.
1
10.
1
11.
1
12.
1
13.
1
14.
1
15.
1
16.
1
17.
1
3.
1
4.
20.
1
18.
1
19.
EN
RU
CZ
1.
A
(5-6)
LF1 - FLAP INLET (output L-open), LF2 - FLAP OUTLET ( output L-open)
LF1 ЗАСЛОНКА ВПУСК (выход L-открыт), LF2 - ЗАСЛОНКА ВЫПУСК (выход L-открыт)
LF1 - KLAPKA PŘÍVOD (výstup L-open), LF2 - KLAPKA ODVOD ( výstup L-open)
2.
A
(7-8)
RUN CONTACT (output -NO/NC settable)
RUN контакт (выход - NO/NC устанавливаемый)
RUN KONTACT (výstup -NO/NC nastavitelné)
3.
A
(9-10)
ERROR CONTACT (output NO)
ОШИБКА КОНТАКТА (выход NO)
ERROR KONTACT (výstup NO)
4.
A
(11-12)
PREHEATER WATER PUMP (11 - Lint, 12 - Lout)
ВОДЯНОЙ НАСОС ПРЕДВАРИТЕЛЬНОГО НАГРЕВА (11 - Lint,12 - Lout)
VODNÍ ČERPADLO PŘEDEHŘEVU (11 - Lint, 12 - Lout)
5.
A
(13-14)
BOOST (input NO)
BOOST (вход NO)
BOOST (vstup NO)
6.
A
(15-16)
FIRE (input NC)
FIRE -тревога (вход NC)
FIRE (vstup NC)
7.
A
(17-18)
EXTERNAL CONTROL ON/OFF (input NC)
ВНЕШНЕЕ УПРАВЛЕНИЕ ON/OFF (вход NC)
EXTERNÍ OVLÁDÁNÍ ON/OFF (vstup NC)
8.
A
(18-19)
AQS SENSOR 0-10V (input)
ДАТЧИК КАЧЕСТВА ВОЗДУХА 0-10В (вход)
ČIDLO KVALITY VZDUCHU 0-10V (vstup)
9.
B
(1-2)
WATER PUMP (1 - Lint, 2 - Lout)
ВОДЯНОЙ НАСОС (1 - Lint, 2 - Lout)
VODNÍ ČERPADLO (1 - Lint, 2 - Lout)
10.
B
(3-4)
HEAT PUMP CONTROL settable (output - ON/OFF)
УПРАВЛЕНИЕ ТЕПЛОВОГО НАСОСА устанавливаемый (выход - ON/OFF)
ŘÍZENÍ TEPELNÉHO ČERPADLA nastavitelné (výstup - ON/OFF)
11.
B
(5-6)
ADIABATIC MODULE (output - ON/OFF)
АДИАБАТИЧЕСКИЙ МОДУЛЬ (выход - ON/OFF)
ADIABATICKÝ MODUL (výstup - ON/OFF)
12.
B
(7-8)
COOL / HEAT settable (CO = NC/NO - DX = output settable)
ОХЛАЖДЕНИЕ /ОБОГРЕВ устанавливаемый (CO = NC/NO - DX = выход устанавливаемый)
CHLAZENÍ / TOPENÍ nastavitelné (CO = NC/NO - DX = výstup nastavitelné)
13.
B
(9-10)
ADIABATIC MODULE ERROR (input NO)
АДИАБАТИЧЕСКИЙ МОДУЛЬ ERROR (вход NO)
ADIABATICKÝ MODUL ERROR (vstup NO)
14.
B
(11-12)
HEAT PUMP DEFROST settable (input NC/NO)
РАЗМОРАЖИВАНИЕ ТЕПЛОВОГО НАСОСА устанавливаемое (вход NC/NO)
ODMRAŽOVÁNÍ TEPELNÉHO ČERPADLA nastavitelné (vstup NC/NO)
15.
B
(13-14)
HEAT PUMP ERROR settable (input NC/NO)
ОШИБКА ТЕПЛОВОГО НАСОСА устанавливаемая (вход NC/NO)
CHYBA TEPELNÉHO ČERPADLA nastavitelné (vstup NC/NO)
16.
B
(15-16)
PIR (input NC)
ДАТЧИК ДВИЖЕНИЯ PIR (вход NC)
POHYBOVÉ ČIDLO PIR (vstup NC)
17.
B
(17-18)
CONDENSATE OVERFLOW (input NC)
ДАТЧИК ПЕРЕПОЛНЕНИЯ КОНДЕНСАТА (вход NC)
ČIDLO PŘETEČENÍ KONDENZÁTU (vstup NC)
18.
B
(46-47)
EXTERNAL TEMPERATURE SENSOR (external postheater - input)
ВНЕШНИЙ ДАТЧИК ТЕМПЕРАТУРЫ (внешний дополнительный нагрев - вход)
EXTERNÍ TEPLOTNÍ ČIDLO (externí dohřev - vstup)
19.
B
(44-45)
EXTERNAL TEMPERATURE SENSOR (adiabatic module / recirc. chamber - input)
ВНЕШНИЙ ДАТЧИК ТЕМПЕРАТУРЫ (адиабатический модуль / камера рециркуляции - вход)
EXTERNÍ TEPLOTNÍ ČIDLO (adiabatický modul / recirkulační komora - input)
20.
B
(38-39)
EXTERNAL PREHEATER (output - Water= 0-10V, electric=PWM)
ВНЕШНИЙ ПОДОГРЕВ (выход - вода=0-10В, электрический=PWM)
EXTERNÍ PŘEDEHŘEV (výstup - vodní=0-10V, elektrický=PWM)
21
B
(36-37)
EXTERNAL POSTHEATER (output - Water= 0-10V, electric=PWM)
ВНЕШНИЙ ДООГРЕВ (выход - вода=0-10В, электрический=PWM)
EXTERNÍ DOHŘEV (výstup - vodní=0-10V, elektrický=PWM)
22
B
(34-35)
RECIRCULATION CHAMBER (output 0-10V)
РЕЦИРКИЛИРОВАННАЯ КАМЕРА (выход 0-10В)
RECIRKULAČNÍ KOMORA (výstup 0-10V)
A
B
21.
BROWN
MODBUS connection
EXT
Содержание VS1200 CMh/e
Страница 2: ...2 Rev 01 01 ...