2.0   Site Requirement

 

 

 

2.1 

Information

 

 

1. The unit is designed for installation in external 
walls with a thickness of between 150mm to

 

315mm. For wall thicknesses upto 650mm an 
extension kit is available (ref: 370422).

 

 

2. If the unit is to be fitted in a replacement 
window panel, a mounting kit must be used.

 

 

 

3. The unit must be sited and connected by a 
suitably competent person and be in accordance 
with current UK Building Regulations and I.E.E. 
Wiring Regulations (BS 7671).

 

 

4. The unit is intended for permanent connection 
to the mains electrical supply.

 

 

5. The unit is intended for fixed wiring installation.

 

 

6. Wiring to the unit in the UK must be via a 
switched fused spur. The switched fused spur 
must have a 3mm minimum contact gap in all 
poles.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500mm 

Min Above

 

Floor Level

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

125mm

 

Min

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 2

 

 

 

 

 

 

 

125mm

 

Min

 

7. Ensure that the mains electrical supply is 
compatible with the rating label attached to the 
product.

 

 

8. The unit must be sited such that the ambient 
temperature will not exceed 40° C.

 

 

9. Do not site the appliance in the vicinity of 
excessive levels of airborne oil or grease.

 

 

10. If the unit is installed in a room containing a 
fuel burning appliance, the installer must ensure 
that air replacement is adequate for both 
appliances.

 

 

11. The unit must not be installed at a level below

 

500mm from the floor.

 

 

12. The internal grille surround must be sited at 
least 125mm away from any wall or projecting 
surface (Fig. 2).

 

 

13. The external grille of the unit must be sited at 
least 500mm away from any flue of gas or solid 
fuel appliances. This is to avoid back flow of 
gases entering the room.

 

 

14. All safety regulations and requirements must 
be strictly followed to prevent hazards to life and 
property both during and after installation and 
during subsequent maintenance or servicing.

 

 

15. Ensure the mains electrical supply is switched 
off before commencing installation or 
maintenance.                                                        

 

Содержание HR300

Страница 1: ...00 Through the wall Heat Recovery Ventilator Installation and Maintenance Instructions PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLEASE SAVE THESE INSTRUCTIONS Stock Ref No HR300 3703...

Страница 2: ......

Страница 3: ...d by a suitably qualified person after completion 3 Ensure the mains supply voltage frequency and phase complies with the rating label 4 The unit should be provided with a local double pole fused spur...

Страница 4: ...stallation and during any subsequent servicing and maintenance 3 Certain applications may require the installation of sound attenuation to achieve the sound levels required 4 The unit must not be conn...

Страница 5: ...Contents Section Page 1 0 Introduction 5 2 0 Site Requirements 6 3 0 Installation 7 4 0 Electrical 9 5 0 Maintenance 10...

Страница 6: ...power consumption for the unit is 108w 4 The twin impeller and heat exchanger arrangement simultaneously supplies and extracts air while transferring heat from the stale exhaust airflow to the fresh...

Страница 7: ...ply is compatible with the rating label attached to the product 8 The unit must be sited such that the ambient temperature will not exceed 40 C 9 Do not site the appliance in the vicinity of excessive...

Страница 8: ...ect an approved electrical control arrangement for the HR300 unit above 2 After considering the site requirements Section 2 0 select a suitable site for the unit and controllers and work out the cable...

Страница 9: ...the two fixing screws provided NOTE Ensure the fixings DO NOT inhibit removal or replacement of the heat exchanger 4 Make good around the case 5 Fit the bezel on the inside to cover the making good b...

Страница 10: ...HR300 is supplied with a length of cable attached from the factory This can be extended with the use of 4 core cable as required 5 Connect the wires as shown in Fig 7 to a Switched fused spur or a co...

Страница 11: ...from rear of grille 6 Slide out the heat exchanger Fig 8 7 Wash the grille filter and heat exchanger in warm water using a mild detergent and dry thoroughly CAUTION Keep water away from all electrical...

Страница 12: ...4 months Clean cell replace filters the new filters will be supplied with 4 additional Timestrip indicators Note The above is the minimum requirement more frequent cleaning intervals may be needed dep...

Страница 13: ...Typology Central Demand Control Local Demand Control Declared Max Internal External Leakage Rates for BVUs or carry over for regenerative heat exchangers only Ext Leakage Rates for Ducted UVUs 5 Inter...

Страница 14: ...Notes...

Страница 15: ...Notes...

Страница 16: ...ating label attached to the unit Has not been subjected to misuse neglect or damage Has not been modified or repaired by any person not authorised by the company IF CLAIMING UNDER TERMS OF GUARANTEE P...

Отзывы: