1.0 Introduction

 

 

 

 

 

1.1 

Description 

(Fig. 1)

 

 

1. The HR300 unit is a through the wall heat 
recovery ventilator which is ideal for light 
commercial applications including function 
rooms, swimming pools, offices, classrooms etc.

 

 

2. The HR300 comes complete with an integral 
shutter device, two internal rotor motors and twin 
centrifugal impellers.

 

 

 

 

 

 

 

 

 

 

 

 

 

Bezel

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 1

 

 

 

 

 

 

 

 

 

HR300

 

 

 

 

Panel Flange

 

3. The maximum power consumption for the unit 
is 108w.

 

 

4. The twin impeller and heat exchanger 
arrangement simultaneously supplies and 
extracts air while transferring heat from the stale 
exhaust airflow to the fresh intake airflow. This 
provides up to 70% heat recovery from the stale 
extracted air.

 

 

 

1.2 

Ancillary Equipment

 

 

1. The HR300 unit can be used in conjunction with 
a range of ancillary equipment.

 

 

Controller: 

A range of controllers - see section

 

3.1 Controllers.

 

 

 

 

HR300RF2 (370402): 

Replacement Filter Pack.

 

 

 

 

 

EXT300 (370422): 

Extension Sleeve. The 

extension kit is for use with walls up to 650mm 
thick.

 

Содержание HR300

Страница 1: ...00 Through the wall Heat Recovery Ventilator Installation and Maintenance Instructions PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLEASE SAVE THESE INSTRUCTIONS Stock Ref No HR300 3703...

Страница 2: ......

Страница 3: ...d by a suitably qualified person after completion 3 Ensure the mains supply voltage frequency and phase complies with the rating label 4 The unit should be provided with a local double pole fused spur...

Страница 4: ...stallation and during any subsequent servicing and maintenance 3 Certain applications may require the installation of sound attenuation to achieve the sound levels required 4 The unit must not be conn...

Страница 5: ...Contents Section Page 1 0 Introduction 5 2 0 Site Requirements 6 3 0 Installation 7 4 0 Electrical 9 5 0 Maintenance 10...

Страница 6: ...power consumption for the unit is 108w 4 The twin impeller and heat exchanger arrangement simultaneously supplies and extracts air while transferring heat from the stale exhaust airflow to the fresh...

Страница 7: ...ply is compatible with the rating label attached to the product 8 The unit must be sited such that the ambient temperature will not exceed 40 C 9 Do not site the appliance in the vicinity of excessive...

Страница 8: ...ect an approved electrical control arrangement for the HR300 unit above 2 After considering the site requirements Section 2 0 select a suitable site for the unit and controllers and work out the cable...

Страница 9: ...the two fixing screws provided NOTE Ensure the fixings DO NOT inhibit removal or replacement of the heat exchanger 4 Make good around the case 5 Fit the bezel on the inside to cover the making good b...

Страница 10: ...HR300 is supplied with a length of cable attached from the factory This can be extended with the use of 4 core cable as required 5 Connect the wires as shown in Fig 7 to a Switched fused spur or a co...

Страница 11: ...from rear of grille 6 Slide out the heat exchanger Fig 8 7 Wash the grille filter and heat exchanger in warm water using a mild detergent and dry thoroughly CAUTION Keep water away from all electrical...

Страница 12: ...4 months Clean cell replace filters the new filters will be supplied with 4 additional Timestrip indicators Note The above is the minimum requirement more frequent cleaning intervals may be needed dep...

Страница 13: ...Typology Central Demand Control Local Demand Control Declared Max Internal External Leakage Rates for BVUs or carry over for regenerative heat exchangers only Ext Leakage Rates for Ducted UVUs 5 Inter...

Страница 14: ...Notes...

Страница 15: ...Notes...

Страница 16: ...ating label attached to the unit Has not been subjected to misuse neglect or damage Has not been modified or repaired by any person not authorised by the company IF CLAIMING UNDER TERMS OF GUARANTEE P...