Installation and Wiring Instructions for the ACM IN-LINE MIXED FLOW FAN range. 

 

IMPORTANT: READ THESE INSTRUCTIONS  

BEFORE COMMENCING THE INSTALLATION 

 
DO NOT install this product in areas where the following may 
be present or occur: 

  Excessive oil or a grease laden atmosphere. 

  Corrosive or flammable gases, liquids or vapours. 

• 

Ambient temperatures higher than 40°C or less than –5°C. 

• 

Possible obstructions which would hinder the access or 
removal of the Fan. 

  Sudden ductwork bends or transformations close to the Fan. 

 

SAFETY AND GUIDANCE NOTES 
A. 

All wiring to be in accordance with the current I.E.E.       
Regulations, or the appropriate standards of your country 
and 

MUST 

be installed by a suitably qualified person. 

B.

The Fan should be provided with a local double pole isolator 
switch having a contact separation of at least 3mm. 

C.

Ensure that the mains supply (Voltage, Frequency, and 
Phase) complies with the rating label. 

D.

The Fan should only be used in conjunction with the 
appropriate Vent-Axia products. 

E. 

It is recommended that the connection to the fan connecter 
terminals is made with flexible cable. 

F. 

When the Fan is used to remove air from a room containing a 
fuel-burning appliance, precautions must be taken to avoid 
back-flow of gases into the room from the open flue of gas or 
other appliance.  Ensure that the air replacement is adequate 
for both the fan and the fuel-burning appliance. 

G. 

The Fan should not be used where it is liable to be subject to 

direct water spray for prolonged periods of time. 

Содержание ACM100 B

Страница 1: ...IONS ACM In Line MIXED FLOW FANS Stock Ref N ACM100 B 17104010D ACM100 T 17104020F ACM125 B 17105010D ACM125 T 17105020C ACM150 B 17106010C ACM150 T 17106020D ACM160 B 17107010B ACM160 T 17107020B ACM200 B 17108010C ACM200 T 17108020B Installation and Wiring Instructions 220 240V 50Hz IP44 ...

Страница 2: ...y and MUST be installed by a suitably qualified person B The Fan should be provided with a local double pole isolator switch having a contact separation of at least 3mm C Ensure that the mains supply Voltage Frequency and Phase complies with the rating label D The Fan should only be used in conjunction with the appropriate Vent Axia products E It is recommended that the connection to the fan conne...

Страница 3: ...d it should be fully extended to obtain the best results Position the fan at the highest point on the system with both ducting runs sloping downwards from this point The airflow direction is indicated on the rating label with an arrow pointing in the direction of the airflow In circumstances where an excessive amount of moisture is present in the air then a condensation trap should be installed Re...

Страница 4: ...e terminal box cover screws Fig 13 6 Ensure the impeller rotates and is free from obstructions Timer models cannot be used with a speed controller Timer Adjustment The fan must be wired to a remote switch e g light switch When switched ON the fan will operate at the selected speed and will continue to run for a preset time after the fan is switched OFF The timer is factory set at 15 minutes approx...

Страница 5: ...OT be used with the timer version C OVER HEATING PROTECTION The fan motor is fitted with Thermal Overload Protection This is a one shot thermal fuse In the event of a fault condition the fan will be automatically switched off If this occurs isolate the fan and call your service engineer D SERVICING AND MAINTENANCE WARNING THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM THE POWER SUPP...

Страница 6: ...ace Velocity m s Design Flow Rate N A N A N A N A N A Nominal External Pressure Δps ext in Pa 71 74 92 92 167 Internal Pressure Drop of Ventilation Components Δps int in Pa N A N A N A N A N A Additonal Internal Press Drop of Non Ventilation Comp Δps add Pa N A N A N A N A N A Static Eff of fans used in accordance with Regulation EU No 327 2011 TBC TBC TBC TBC TBC Declared Max Internal External Le...

Страница 7: ...A N A Face Velocity m s Design Flow Rate N A N A N A N A N A Nominal External Pressure Δps ext in Pa 71 74 92 92 167 Internal Pressure Drop of Ventilation Components Δps int in Pa N A N A N A N A N A Additonal Internal Press Drop of Non Ventilation Comp Δps add Pa N A N A N A N A N A Static Eff of fans used in accordance with Regulation EU No 327 2011 TBC TBC TBC TBC TBC Declared Max Internal Exte...

Страница 8: ...fective the product will be repaired or at the Company s option replaced without charge provided that the product Has been installed and used in accordance with the instructions given with each unit Has not been connected to an unsuitable electricity supply The correct electricity supply voltage is shown on the product rating label attached to the unit Has not been subjected to misuse neglect or d...

Отзывы: