background image

17

ALTITUDE

model

7.1 M

AIN

C

ONTROLS

7. Control Devices

VC0101

SMART

SET

MODE

PREF

VENTA

model

VC0010 

VENTA 

20/40/60-

MINUTE PUSH

-

BUTTON TIMER

:

This remote illuminated switch is typically installed in bathrooms, kitchen and laundry room to provide 20, 40 or 60 minutes
of high speed ventilation at the push of a button. 

60-

MINUTE CRANK TIMER

:

This timer allows up to 60 minutes of high speed operation to be selected from a remote location.

D

EHUMIDISTAT

:

This optional control helps control maximum humidity level during fall, winter and spring. 
You will find a relative humidity % scale meant to reduce the window condensation problems.

7.2 O

PTIONAL

C

ONTROLS

M

ODELS

A

LTITUDE

V

ENTA

M

ODES

Off Position

X

X

Intermittent exchange (TBI) 20, 30, 40 min/h

X

Low speed continuous exchange

X

X

High speed continuous exchange

X

X

Recirculation (manual mode performing air recirculation inside the house)

X

Program (programs the desired ventilation according to the period of the day)

X

SMART (entirely automatic mode optimizing ventilation)

X

D

ETECT

O

R

T

YPES

Indoor Temperature

X

Outdoor Temperature

X

I

NDICA

T

O

RS

Mode indicator

X

Unit status

X

Speed indicator

X

Maintenance indicator

X

Day and Hour indicators

X

S

WITCHES

Sliding button

X

Push-button

X

Содержание Duo 1.2

Страница 1: ...Installer Manual Ventilation systems for residential use only Duo 1 2 part no 43710 Duo 1 4 part no 43700 Duo 1 9 part no 45700 Solo 1 5 part nos 43720 and 43725 Solo 2 0 part nos 45720 and 45725 VB0...

Страница 2: ...rce Point Ventilation 10 5 3 Simplified Volume Ventilation 10 6 INSTALLATION 11 16 6 1 Locating and Mounting the Unit 11 6 2 Planning of the Ductwork 11 6 3 Calculating the Duct Size 12 6 3 1 Example...

Страница 3: ...k Types 22 9 WIRING DIAGRAMS 23 24 10 AIR FLOW BALANCING 25 11 OVERALL VERIFICATION 26 11 1 Main Controls 26 11 2 Optional Controls 26 12 MAINTENANCE INSTRUCTIONS FOR USER 27 13 TROUBLESHOOTING 27 28...

Страница 4: ...4 1 1 3 D DRAWING 1 Service 25 16 16 18 17 17 19 20 21 22 23 24 VL0023 1 2 3 5 4 6 8 10 3 11 12 13 9 15 14 8 8 7 Unit shown in normal position...

Страница 5: ...0887 2 00887 2 00887 2 00887 2 00887 2 Screws 00601 4 00601 4 00601 4 00601 4 00601 4 16 Hinge Ass y kit 13036 13036 13036 13036 13036 Pleated Optional Filter 03316 03316 03316 03316 03316 17 Charcoal...

Страница 6: ...Bedroom no 3 Living room Bathroom no 3 Dining room VH0021A Family room Bathroom no 1 Bathroom no 2 Laundry room 1320 ft 1320 ft CSA F326 Kitchen 10 cfm Dining room 10 cfm Living room 10 cfm Family ro...

Страница 7: ...RALEIGH WASHINGTON OTTAWA NORTH BAY VAL DOR CHICOUTIMI HARTFORD CHIBOUGAMAU MONTR AL QU BEC BOSTON GOOSE BAY LABRADOR CITY SEPT ILES MATANE GASP BATHURST ST JOHN HALIFAX CHARLOTTETOWN ST JO ZONE C ZO...

Страница 8: ...27 Fahrenheit F 23 5 17 Defrosting min 6 6 6 Operationtime min between each defrost cycle 60 32 20 Defrosting min 10 10 10 Operationtime min between each defrost cycle 30 20 15 Outside Temperature Def...

Страница 9: ...Model Solo 1 5 Solo 2 0 Duo 1 2 Duo 1 4 Duo 1 9 Weight 65 lb 29 5 kg 67 lb 30 4 kg 71 lb 32 2 kg 71 lb 32 2 kg 73 lb 33 1 kg Port Diameter 6 152 mm 6 152 mm 6 152 mm 6 152 mm 6 152 mm Drain Diameter 1...

Страница 10: ...rced air heating See figure 2 Moist stale air is exhausted from the high humidity areas in the home such as bathrooms kitchen and laundry room Fresh air is supplied to the cold air return or the suppl...

Страница 11: ...no drain is close by use a pail to collect run off Solo models only Away from hot chimneys electrical panel and other fire hazards Allow for a power source standard outlet Hang the unit with the 4 ch...

Страница 12: ...ough away from the maximum value 180 Therefore a 6 duct or larger is an appropriate choice for the main exhaust duct End branches Each end branch will have to transport an air flow of 70 cfm 140 divid...

Страница 13: ...two methods for connecting the unit to the furnace Method 1 Supply side connection Cut an opening into the furnace supply duct at least 18 inches 0 5 m from the furnace Connect this opening to the fr...

Страница 14: ...nace blower operation with the unit operation but we recommend it 6 4 INSTALLING THE DUCTWORK AND REGISTERS CONT D B A VD0171 B A VD0111 Minimum 3 0 9 m Metal duct Minimum 18 0 5 m figure 12 figure 11...

Страница 15: ...making an airtight seal Avoid compressing the insulation when you pull the tape tightly around the joint Compressed insulation loses its R value and causes water dripping due to condensation on the ex...

Страница 16: ...E HOOD 6 152 MM 18 457 MM 18 457 MM 6 1 8 M 6 1 8 M 18 457 MM figure 14 VO0010 6 7 CONNECTING THE DRAIN SOLO ONLY VO0008 VO0011 VO0005 TO DRAIN To install the drain fittings punch the 2 knock out sect...

Страница 17: ...fall winter and spring You will find a relative humidity scale meant to reduce the window condensation problems 7 2 OPTIONAL CONTROLS MODELS ALTITUDE VENTA M ODES Off Position X X Intermittent exchan...

Страница 18: ...ed as a convenience to the homeowner NOTE If the power failure duration is more than 4 hours the day and hour settings must be reprogrammed CONTROL UPGRADES All controls can be used on any unit so a V...

Страница 19: ...wall control 2 Detach the front module from the mounting plate by pulling the bottom part 3 Run the cable 4 wires through the central opening of the mounting plate and mount this plate to the wall usi...

Страница 20: ...f at least 2 inches 5 cm to the right of the control to allow user to slide out the control instructions Use the template provided in the control box to position the wire hole and the screw holes Use...

Страница 21: ...appropriate connection to the furnace if applicable by referring to Section 8 4 4 NOTE If you are in a cold region zone A or B as defined in Section 3 set up extended defrost by removing jumper JU1F...

Страница 22: ...relay will then have to be installed WARNING Never connect a 120 volt AC circuit to the terminals of the furnace interlock standard wiring Only use the low voltage class 2 circuit of the furnace blow...

Страница 23: ...it only 7 SPECIFIED UL LISTED CSA CERTIFIED LINE FUSE LittelFuse 225 003 2AG Fast Acting Fuse 224 225 Series Rating 3A LINE VOLTAGE LOW VOLTAGE AND FIELD WIRE COLOR CODE BK BLACK NC NO CONNECTION BL B...

Страница 24: ...uous Low 1 0 1 0 Continuous High 1 1 1 0 K5 active only 15 C T 10 C Circulation Low 1 0 0 0 Circulation High 1 1 0 0 Defrost Cycle 1 1 0 0 Off 0 0 0 1 0 Relay coil is de energized 1 Relay coil is ener...

Страница 25: ...r appropriate high low fittings If the gauge drops below zero reverse the tubing connections NOTE It is suggested to start with the exhaust air flow reading because the exhaust has typically more rest...

Страница 26: ...lay is flashing Refer to the installation sheet included with the Altitude wall control for more details in programming and setting preferences VC0101 SMART SET MODE PREF ALTITUDE DEHUMIDISTAT Turn di...

Страница 27: ...te places wall control screen The wires may be broken Inspect every wire and replace any that are damaged The wires may have a Ensure the wires are correctly connected bad connection 2 There is no out...

Страница 28: ...button timer test it right beside the unit using another does not work OR its shorter wire If it works there change indicator light does not the wire If it doesn t change the stay on Dehumidistat or t...

Отзывы: