The supply and exhaust ducts connected to 

outside, as well as any ducts passing through an
unconditioned space, must have a minimum insulation
value of R5. In addition, a continuous integral vapor
barrier over the duct insulation must be used.

Air balancing dampers are recommended for both

supply and exhaust ducts to allow for adjustment of
airflow. Also, flexible canvas connectors should be
installed close to the unit in the supply duct to the
building and the exhaust duct from the building to
reduce noise transmission from the unit to the 
building, see Appendix C.

All ports on the 600 cfm and 1200 cfm units have

1" (25mm) flanges to facilitate the installation of the
ductwork. Please note that the "Fresh Air from
Outside" port has a defrost damper incorporated with it.
Ensure that any mechanical fasteners used to connect
the duct do not interfere with the operation of the
damper. 

Screws can be installed on the side of the

cabinet rather than the flange for this port only.

For port locations see Appendix B.

All ports on the 700 cfm unit have 2" (51mm)

flanges to facilitate the installation of the ductwork.
Please note the "Fresh Air From Outside" connection
is factory set to be the left side upper port. It is 
possible to reverse the operation of the defrost
damper in order to use the port on top of the 
cabinet for "Fresh Air From Outside" connection.

To change the "Fresh Air From Outside" from the

side to the top use the following directions. For port
locations see Appendix B.

Remove the cover of the damper motor with a flat

screwdriver. Reverse the Orange and Red wires by
moving the Orange from terminal #2 to terminal #3 and
moving the Red wire from terminal #3 to terminal #2.
The end result in order to have the "Fresh Air From
Outside" connection to the top port will be: 
#1 - White, #2 - Red, #3 - Orange.

2.5  Internal Grilles and Diffusers

Locate exhaust grilles and supply diffusers to provide

effective ventilation and avoid short circuiting of airflows.
Adjustable dampers should be provided at every
grille and diffuser location to make balancing of the
system possible.

A proper selection of style and size of grilles and 

diffusers is required to minimize pressure drop. The
velocity of the airflow should not exceed 400 ft/min
(2 m/sec) for normal applications.

The duct system should be designed according to

the high speed flow rate of the unit. In order to keep
the noise and pressure drop to a minimum, a maximum
air velocity of 1100 ft/min (5.6 m/sec) should be used
in calculations in duct design. The duct runs should
be kept as short as possible with the minimum
amount of elbows and transitions.

The manufacturer recommends the use of smooth

radius elbows or square elbows with turning vanes to
achieve maximum performance.

2.6  Exterior Hoods

It is important that the fresh air intake hood be 

positioned well away from any source of contamination.
The exterior supply and exhaust hoods must be 
separated enough to prevent cross-contamination
and at an elevation that will prevent blockage by
snow, dirt and leaves.

NOTE:

Consult local building code for restrictions in 

your area.

A rodent screen with 1/4" (6mm) mesh must be

installed to prevent the intake of large debris and 
animals. A backdraft damper may need to be
installed in the exhaust duct to prevent cold air entering
the building if the unit is to be shut off for a long
period of time.

To maintain optimum airflow performance, 

exterior hood selection must be such that the 
minimum free area of opening is as follows: 
140 inches

2

(0.09m

2

).

2.7  Drains

The drain fittings provided with the unit will

accept a 3/4" (19mm) NPT coupler (supplied by others).
The drain line for the unit must be fabricated 
on-site and connected to the building main. A loop in
the hose or trap in the copper or plastic pipe must be
provided to prevent sewer gases from entering the
unit when connecting to a drain as illustrated in
Appendix D.

NOTE:

Consult local building code for plumbing requirements

in your area. If copper pipe is to be used, ensure not
to solder to the 3/4" (19mm) coupler while it is
attached to the plastic drain fitting as deformation may
occur. Ensure adequate slope is present to allow good
drainage (minimum 1/4" per foot or 6mm per 305mm).

Содержание 1200 cfm

Страница 1: ...Light Commercial Heat Recovery Ventilators VB0002 VB0003 VB0001 600 cfm 700 cfm 1200 cfm Installation Operation and Service Instructions 06 00 04597...

Страница 2: ...5 3 4 Remote Wall Control Optional 6 4 Airflow Measurement and Balancing 6 4 1 Flow Station Positions 6 4 2 Balancing Procedure 7 5 Maintenance and Service 7 5 1 Bi Monthly Maintenance 7 5 2 Annual M...

Страница 3: ...also be easily accessible for maintenance 2 3 Mounting Options There are several options for hanging or floor mounting the unit NOTE In all cases the unit must be level Consult local building code fo...

Страница 4: ...at every grille and diffuser location to make balancing of the system possible A proper selection of style and size of grilles and diffusers is required to minimize pressure drop The velocity of the a...

Страница 5: ...creating a closure across LOW COM or high speed can be initiated by creating a closure across HIGH COM Unit Check points ___ Power connected no ventilation call Both fans are off defrost damper if eq...

Страница 6: ...rting intermittent stand by ventilation continuous low exchange continuous high exchange maintenance indicator light and exchange indicator light 4 Airflow Measurement and Balancing Once installation...

Страница 7: ...commended that they be cleaned every two months More frequent cleaning may be required under extremely dirty operating conditions Use a vacuum cleaner to remove the heaviest portion of accumulated dir...

Страница 8: ...suddenly stops the unit stays in defrost all of the time or if control functions are not working properly Ensure that power is reaching the board Test the blower motors and damper actuators for operat...

Страница 9: ...s with adequate slope for drainage Wooden Curb Supplied by others Bolt to Floor Rubber Vibration Isolator Supplied by others U Channel Supplied by others 3 8 10mm Threaded Rod Supplied by others NOTE...

Страница 10: ...CLEARANCE FROM ANY OBSTRUCTION IS REQUIRED FOR REMOVAL OF HEAT RECOVERY CORES FANS ETC THE ACCESS DOOR CAN BE REMOVED FROM CABINET WITH ONLY 2 000 51 OF CLEARANCE CONTROL PLATE ACCESS DOOR HEAT RECOV...

Страница 11: ...A minimum of 6 00 152 clearance from any obstruction is required for removal of control box A minimum of 15 00 381 clearance from any obstruction is required for removal of heat recovery cores fans et...

Страница 12: ...15 000 381 CLEARANCE FROM ANY OBSTRUCTION IS REQUIRED FOR REMOVAL OF HEAT RECOVERY CORES FANS ETC THE ACCESS DOOR CAN BE REMOVED FROM CABINET WITH ONLY 2 000 51 OF CLEARANCE EXHAUST AIR SUPPLY AIR FRO...

Страница 13: ...ement minimum de 12 00 305 est requis pour retirer le bo tier lectronique Un d gagement minimum de 15 00 381 est requis pour retirer les noyaux de r cup ration les ventilateurs etc La porte d acc s pe...

Страница 14: ...3 625 92 2 000 51 14 000 356 1 875 48 3 750 95 40 500 1029 8 000 203 12 250 311 8 000 203 15 250 387 B A 2 000 51 Line Voltage In A minimum of 12 00 305 clearance from any obstruction is required for...

Страница 15: ...Exhaust Air From Building Fresh Air From Outside Min 8 203mm Optional Canvas Vibration Isolator Min 12 305mm VP0001A Min 12 304mm Flow Measuring Station FMS Balancing Damper not supplied Canvas Vibra...

Страница 16: ...pler 3 4 NPT Note All hose pipe couplers to be supplied by others T D i All hose pipe and couplers to be supplied by others Plastic Hose Water Trap 3 4 NPT To Drain Copper or Plastic Pipe Plastic Drai...

Страница 17: ...are dry contacts Low Voltage terminal control consists of the following Wall Control 4 wire LVT 24 gauge minimum Occupied Night set back Timer Sensor 24 VAC needs dry contact LOW COM HIGH Remote fan s...

Страница 18: ...sor occupancy sensor building management system or other The unit will not operate unless these contacts are closed The illustration below shows a factory installed jumper and programmable timer optio...

Страница 19: ...ing JU1 F Extended Defrost Jumper 12 pin 2 pin Med Speed Blue Low To Medium move the fork connector To change the minimum speed setting from from here to here LOW SPEED SETTING 321 FF1 YRGB OL 1 J2 J4...

Страница 20: ...3 3 5 0 9 3 10 9 2 6 6 9 8 5 0 2 4 4 6 1 900 425 8 5 12 4 13 8 6 4 10 2 11 7 4 3 8 1 9 6 2 2 6 0 7 5 0 1 3 9 5 4 800 377 7 0 10 4 11 7 5 2 8 6 9 9 3 4 6 8 8 2 1 7 5 0 6 4 3 3 4 6 700 330 5 1 8 1 9 3 3...

Страница 21: ...MOTOR 1 2 1 2 BK R W R C L M H EXHAUST MOTOR W R BL BK Y C L M H SUPPLY MOTOR W BL R BL BK Y GND L1 NEUT BK W G 120VAC 60Hz WALL CONTROL GREEN WALL CONTROL YELLOW LOW SPEED 3 9 K COM HIGH SPEED STAND...

Страница 22: ...7 6 9 J1 3 2 1 8 1 J2 COMM N C N O t DEFROST TEMPERATURE SENSOR JU1G INTERMITTENT STANDBY SI JU1 F EXTENDED DEFROST 1 2 3 BK Y R G BL BL 1 2 3 4 5 6 8 7 BK Y W BL 115 VOLT RELAY PART 202729 W BL BK Y...

Страница 23: ...6 J1 9 BK R J1 2 W R4 1 R4 2 J1 1 BK W J1 3 T2 1 2 1 2 3 4 5 6 7 8 9 10 11 12 J5 BK R R R W R BL BK Y NOTE 1 W BL R BL MEDIUM SPEED CONNECTIONS BK Y 1 2 1 2 3 4 5 6 7 8 9 10 11 12 J6 R CORE DAMPER MO...

Страница 24: ...stall a dehumidistat option Window frame is too cold or leaky Repair window frame Unit stops functioning Electrical supply interrupted Check the unit circuit breaker Air from supply diffusers too cold...

Отзывы: