Venmar 1200 cfm Скачать руководство пользователя страница 3

Page 3

1  Safety Considerations

Hazards may exist within this equipment because it

contains electrical and powerful moving components.
Only qualified service personnel should install or
service this equipment. Untrained personnel can perform
basic maintenance such as maintaining filters.
Observe precautions marked in literature and on
labels attached to unit. Follow all safety codes.

2  Installation

2.1  Inspection

Inspect the exterior of the unit for shipping 

damage by ensuring that there is no damage to the
door, door latches, door hinges, damper, duct collars,
cabinet, etc. Inspect the interior of the unit for damage
by ensuring that the fan motors and housings, heat
exchange cores, insulation, dampers, actuators and
drain pans are all intact.

If transportation damage is found, file a claim

immediately with the transportation agency. Remove
all packaging, tape, etc. from the cabinet.

2.2  Mounting Location Requirements

When determining an installation location, the

unit must be mounted in a heated area to prevent
condensate drain lines from freezing. The mounting
location should be away from occupied areas to provide
quiet operation. The area should also be easily accessible
for maintenance. 

NOTE:

These Heat Recovery Ventilators have minimum

clearance requirements when mounting. See Appendix B
for specific clearance requirements. Mounting options
must allow 6" (152mm) clearance in front of control
cover for access.

A mounting location close to an exterior partition

will minimize the length of insulated duct. The unit
should be close to a drain and 120 volt, 60 Hz power
supply. The unit should be mounted away from hot
chimneys, electrical panels and other hazards. The
area should also be easily accessible for maintenance.

2.3  Mounting Options

There are several options for hanging or floor

mounting the unit.

NOTE:

In all cases, the unit must be level. Consult 

local building code for restrictions in your area
regarding installation.

Hang the unit with the reinforced rubber straps

provided as shown in Appendix A. Check with local
building codes regarding the use of rubber straps in
commercial buildings. Attach the straps to the unit
with two #8 screws provided. Then attach the other
end of the strap to the ceiling joists, trusses, custom
frame, etc.

The unit can also be hung with 3/8" (10mm)

threaded rod and U channels or angles (not supplied)
as shown in Appendix A.

When installing the unit, keep in mind that access to

the control panel may be required. Supply and exhaust
ducts to outside may have 1" to 2" (25 to 51mm) of
insulation on them. Rubber vibration isolation may
be required and is recommended for quiet operation.

The unit can also be mounted on a metal or wooden

curb (not supplied) bolted to the floor as shown in
Appendix A. Space must be left under the unit to
allow connection of drain lines. A gradual slope is
required for the condensate water to drain by gravity
(minimum 1/4"/foot) (6mm/305mm). If this is not
possible, a pump should be used. If attachment of the
unit to the curb is required, ensure that screws, bolts
and mounting hardware do not interfere with moving
parts or that the integrity of the cabinet insulation is
not affected.

2.4  Ductwork

The supply and exhaust duct connections on the

unit are as follows:

NOTE:

Duct sizes are for connection purposes only. 

Ducts should be sized to keep noise and pressure drop
to a minimum.

WARNING

Disconnect main power switches to unit before
performing service or maintenance. Electric shock
can cause personal injury or death.

UNIT

DUCT SIZE

600 cfm/700 cfm

14" x 8" (356 x 203mm)

1200 cfm

20" x 8" (508 x 203mm)

Содержание 1200 cfm

Страница 1: ...Light Commercial Heat Recovery Ventilators VB0002 VB0003 VB0001 600 cfm 700 cfm 1200 cfm Installation Operation and Service Instructions 06 00 04597...

Страница 2: ...5 3 4 Remote Wall Control Optional 6 4 Airflow Measurement and Balancing 6 4 1 Flow Station Positions 6 4 2 Balancing Procedure 7 5 Maintenance and Service 7 5 1 Bi Monthly Maintenance 7 5 2 Annual M...

Страница 3: ...also be easily accessible for maintenance 2 3 Mounting Options There are several options for hanging or floor mounting the unit NOTE In all cases the unit must be level Consult local building code fo...

Страница 4: ...at every grille and diffuser location to make balancing of the system possible A proper selection of style and size of grilles and diffusers is required to minimize pressure drop The velocity of the a...

Страница 5: ...creating a closure across LOW COM or high speed can be initiated by creating a closure across HIGH COM Unit Check points ___ Power connected no ventilation call Both fans are off defrost damper if eq...

Страница 6: ...rting intermittent stand by ventilation continuous low exchange continuous high exchange maintenance indicator light and exchange indicator light 4 Airflow Measurement and Balancing Once installation...

Страница 7: ...commended that they be cleaned every two months More frequent cleaning may be required under extremely dirty operating conditions Use a vacuum cleaner to remove the heaviest portion of accumulated dir...

Страница 8: ...suddenly stops the unit stays in defrost all of the time or if control functions are not working properly Ensure that power is reaching the board Test the blower motors and damper actuators for operat...

Страница 9: ...s with adequate slope for drainage Wooden Curb Supplied by others Bolt to Floor Rubber Vibration Isolator Supplied by others U Channel Supplied by others 3 8 10mm Threaded Rod Supplied by others NOTE...

Страница 10: ...CLEARANCE FROM ANY OBSTRUCTION IS REQUIRED FOR REMOVAL OF HEAT RECOVERY CORES FANS ETC THE ACCESS DOOR CAN BE REMOVED FROM CABINET WITH ONLY 2 000 51 OF CLEARANCE CONTROL PLATE ACCESS DOOR HEAT RECOV...

Страница 11: ...A minimum of 6 00 152 clearance from any obstruction is required for removal of control box A minimum of 15 00 381 clearance from any obstruction is required for removal of heat recovery cores fans et...

Страница 12: ...15 000 381 CLEARANCE FROM ANY OBSTRUCTION IS REQUIRED FOR REMOVAL OF HEAT RECOVERY CORES FANS ETC THE ACCESS DOOR CAN BE REMOVED FROM CABINET WITH ONLY 2 000 51 OF CLEARANCE EXHAUST AIR SUPPLY AIR FRO...

Страница 13: ...ement minimum de 12 00 305 est requis pour retirer le bo tier lectronique Un d gagement minimum de 15 00 381 est requis pour retirer les noyaux de r cup ration les ventilateurs etc La porte d acc s pe...

Страница 14: ...3 625 92 2 000 51 14 000 356 1 875 48 3 750 95 40 500 1029 8 000 203 12 250 311 8 000 203 15 250 387 B A 2 000 51 Line Voltage In A minimum of 12 00 305 clearance from any obstruction is required for...

Страница 15: ...Exhaust Air From Building Fresh Air From Outside Min 8 203mm Optional Canvas Vibration Isolator Min 12 305mm VP0001A Min 12 304mm Flow Measuring Station FMS Balancing Damper not supplied Canvas Vibra...

Страница 16: ...pler 3 4 NPT Note All hose pipe couplers to be supplied by others T D i All hose pipe and couplers to be supplied by others Plastic Hose Water Trap 3 4 NPT To Drain Copper or Plastic Pipe Plastic Drai...

Страница 17: ...are dry contacts Low Voltage terminal control consists of the following Wall Control 4 wire LVT 24 gauge minimum Occupied Night set back Timer Sensor 24 VAC needs dry contact LOW COM HIGH Remote fan s...

Страница 18: ...sor occupancy sensor building management system or other The unit will not operate unless these contacts are closed The illustration below shows a factory installed jumper and programmable timer optio...

Страница 19: ...ing JU1 F Extended Defrost Jumper 12 pin 2 pin Med Speed Blue Low To Medium move the fork connector To change the minimum speed setting from from here to here LOW SPEED SETTING 321 FF1 YRGB OL 1 J2 J4...

Страница 20: ...3 3 5 0 9 3 10 9 2 6 6 9 8 5 0 2 4 4 6 1 900 425 8 5 12 4 13 8 6 4 10 2 11 7 4 3 8 1 9 6 2 2 6 0 7 5 0 1 3 9 5 4 800 377 7 0 10 4 11 7 5 2 8 6 9 9 3 4 6 8 8 2 1 7 5 0 6 4 3 3 4 6 700 330 5 1 8 1 9 3 3...

Страница 21: ...MOTOR 1 2 1 2 BK R W R C L M H EXHAUST MOTOR W R BL BK Y C L M H SUPPLY MOTOR W BL R BL BK Y GND L1 NEUT BK W G 120VAC 60Hz WALL CONTROL GREEN WALL CONTROL YELLOW LOW SPEED 3 9 K COM HIGH SPEED STAND...

Страница 22: ...7 6 9 J1 3 2 1 8 1 J2 COMM N C N O t DEFROST TEMPERATURE SENSOR JU1G INTERMITTENT STANDBY SI JU1 F EXTENDED DEFROST 1 2 3 BK Y R G BL BL 1 2 3 4 5 6 8 7 BK Y W BL 115 VOLT RELAY PART 202729 W BL BK Y...

Страница 23: ...6 J1 9 BK R J1 2 W R4 1 R4 2 J1 1 BK W J1 3 T2 1 2 1 2 3 4 5 6 7 8 9 10 11 12 J5 BK R R R W R BL BK Y NOTE 1 W BL R BL MEDIUM SPEED CONNECTIONS BK Y 1 2 1 2 3 4 5 6 7 8 9 10 11 12 J6 R CORE DAMPER MO...

Страница 24: ...stall a dehumidistat option Window frame is too cold or leaky Repair window frame Unit stops functioning Electrical supply interrupted Check the unit circuit breaker Air from supply diffusers too cold...

Отзывы: