INSTALLATION SUGGESTIONS
In case the sounder does not work properly, check if the on-board LED flashes. If it flashes, check FAULTS CHART here above.
WARRANTY
All Venitem products are granted against factory or material defects. In order to improve design and quality of its products, Venitem reserves
the right to modify the products without prior notice. All faulty or defective products must be returned to supplier.
Chart 7:
Alarm system STI (ON/OFF) signalization setting
DIP 4
Terminal 4
Flash status (ON/OFF)
OFF (default)
+12 Vdc
All LEDs flash 3 times
Not connected or 0 Vdc
All LEDs remain steady on for 4 seconds then switch off
ON
+12 Vdc
All LEDs flash 3 times and 1 LED keeps on flashing
Not connected or 0 Vdc
All LEDs remain steady on for 4 seconds then switch off
Chart 8: flash reset mode
DIP 5
Flash behaviour – TerC and RES
OFF (default)
Flash activates tC trigger and deactivates through a negative signal to RES terminal (Flash reset)
ON
Flash activates tC trigger and deactivates tC trigger
Chart 9:
Alarm trigger mode +C
DIP 6
TeC
Note
OFF (default)
Missing Reference
Alarm occurs by disconnecting the cable (see DIP 2)
ON
Giving Reference
Alarm occurs by connecting the cable (see DIP 2)
Chart 10: Max daily alarms
JUMPER 5
Number of alarms during 24 hrs after the first alarm
CONNECTED (default)
Infinite alarms
CUT
Restriction to 4 daily alarms (24 hours) of sound activation (STI resets the counter to zero)