TECHNICAL MANUAL

6

TAMPER CONNECTION (ANTI-OPENING AND ANTI-FOAM)

Connect terminals no. 7 and no. 8 to the tamper line coming from the control panel.  

LED COMMANDS

TERMINALS: 

A

=RED, 

B

=GREEN, 

C

=BLUE, 

D

=WHITE

A, B, C, D terminals control indipendently the flashing unit to run customisable notifications. Use DIP 8 to set 
functioning.

DIP-SWITCHES

NOTE

: Dip switches setting is stored after 12 hours from the first supply. Take away and give again power to the 

board to change settings.

 

DIP 1 SOUND TIMING

•  Dip-switch 1 in OFF: sound timing is 3 minutes (DEFAULT SETTING).
•  Dip-switch 1 in ON: sound timing is 8 minutes.

DIP 2 SOUNDER CONTROL INPUT POLARITY

NOTE: THE INPUT IS MISSING 
•  Dip-switch 2 in OFF: trigger for sounder activation is positive (DEFAULT SETTING).
•  Dip-switch 2 in ON: trigger for sounder activation is negative.

DIP 3 SOUND TYPE SELECTION

•  Dip-switch 3 in OFF: sound is INCREASING-CONTINUOUS-DECREASING-CONTINUOUS (DEFAULT SETTING).
•  Dip-switch 3 in ON: sound is INCREASING-DECREASING.

DIP 4 SYSTEM STATUS OPTICAL SIGNALISATION (ON-OFF IMMEDIATE AND PERMANENT)

•  Dip-switch 4 in OFF: instantaneous ON-OFF situation (DEFAULT SETTING).
•  Dip-switch 4 in ON: instantaneous ON-OFF situation with blue LED flashing intermittently while trigger is given 

to terminal 4.

By giving a command to terminal no.4, the LEDs of the sounder blink in red 3 times (ON) and all anomalies are 
reset to zero. By taking command away, the LEDs light up steady in green for 5 seconds (OFF). 

DIP 5 INPUT POLARITY 4 - 5 - A - B - C - D 

NOTE: INPUTS ARE GIVING

 

•  Dip-switch 5 in OFF: command is positive (DEFAULT SETTING).
•   Dip-switch 5 in ON: command is negative.

DIP 6 INPUT 5 FUNCTION

•   Dip-switch 6 in OFF: input 5 with block speaker function (DEFAULT SETTING).
•  Dip-switch 6 in ON: input 5 with flash reset function. The flash starts withs the trigger and stops with the reset.

DIP 7 DAILY ALARM COUNTING

•  Dip switch 7 in OFF: infinite alarms (default setting)
•  Dip switch 7 in ON: max 4 alarms every 24h. Alarm is counted if it lasts at least 30 seconds. From 5th alarm, the 

sounder flashes with no sound. System status activation resets alarm counting. 

Содержание GIUDECCA

Страница 1: ...EN TECHNICAL MANUAL GIUDECCA ...

Страница 2: ...HNICAL MANUAL 2 IMPORTANT SAFETY INSTRUCTIONS READ THE FOLLOWING SECTION CAREFULLY AND STORE IT WARNING Explosion risk if the battery is replaced with a wrong type High sound pressure risk of hearing loss ...

Страница 3: ...ion at box drilling Holes must be drilled only where indicated otherwise internal components may be improperly housed Drill only where strictly necessary MAX 5 mm Flush Drillable area Spirit level ALTO UP MAX 5 mm Flush Drillable area Spirit level ALTO UP Drillable area DIRECTIONS FOR A CORRECT MOUNTING Zona forabile Zona forabile a 1 To ensure a correct functioning of the tamper maximum installat...

Страница 4: ...CCA with high luminosity and low consumption multicolor LED flashing light anti opening tamper protection programmable sound and timing microprocessor self test of battery and speaker with anomaly negative output programming of sounder polarity command and system ON OFF immediate or permanent optical indication of ON OFF system electronic circuit protected against polarity inversion and resin trop...

Страница 5: ...se a test performed is not passed the anomaly output disconnects from ground and becomes free Notification of last anomaly indicated by LED LD4 is reset to zero only if a command is given to terminal no 4 or c3 To launch the remote battery test send a pulse to terminal no 5 with sounder on rest mode This way a 30 seconds test runs ANOMALY TYPE LD4 LED Speaker interruption test performed every 10 s...

Страница 6: ... 3 in ON sound is INCREASING DECREASING DIP 4 SYSTEM STATUS OPTICAL SIGNALISATION ON OFF IMMEDIATE AND PERMANENT Dip switch 4 in OFF instantaneous ON OFF situation DEFAULT SETTING Dip switch 4 in ON instantaneous ON OFF situation with blue LED flashing intermittently while trigger is given to terminal 4 By giving a command to terminal no 4 the LEDs of the sounder blink in red 3 times ON and all an...

Страница 7: ...mA 10 mA Consumption in stand by 15mA Consumption from control inputs 0 5 mA Vc 12V 0 3 mA Vc 0V Open collector 50 mA Max Fundamental frequency 2 100 Hz Maximum acoustic power 105 dB A 1 m LED flashing unit life 1 000 000 flashes Working temperature conditions From 30 to 65 C Timing Settable 3 8 minutes Control panel command 2 or 3 wires Battery capacity 12V 2 3Ah Pb Size 151x316x124 H x W x D Rec...

Страница 8: ...e legale e operativa Headquarters Via del Lavoro 10 30030 Salzano VE Italy Tel 39 041 5740374 Fax 39 041 5740388 info venitem com www venitem com UNI EN ISO 14001 UNI EN ISO 9001 AZIENDA CERTIFICATA MA SE GIUD 01 02 ...

Отзывы: