![Veneco Medium Comfort Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/veneco/medium-comfort/medium-comfort_installaton-manual_4027093007.webp)
User's man
ual Medium Comf
or
t
7
The unit is designed for indoor application with the ambient temperature ranging from +1°C (+34 °F) up to +40 °C (+104 °F) and
relative humidity up to 80%.
The transported air temperature must be from -20 °C (-4 °F) up to +50°C (+122° F).
The unit is classified as a class I electric appliance.
Ingress Protection (IP) rating from solid objects and liquids:
IP 44 for the unit motors;
IP 22 for the assembled unit integrated into air ductworks.
The unit design is regularly improved, so some models may slightly differ from those ones described in this manual.
Speed
1
2
3
Voltage , 50-60 Hz
1 ~ 100-240
Power (W)
4,2
9,6
15,4
Total unit current (A)
0,02
0,04
0,07
Air capacity (m³/h)
30 (17,7)
45 (26,5)
60 (35,3)
RPM (min)
1165
1720
2685
Noise level, 3m (dBA)
22 (0,38)
25 (0,42)
29 (1,0)
Max. transported air
temperature
from -20° tot +50
IP
IP 22
Casing material
painted steel
Insulation
PE foam
Filter
extract
x
supply
x
Connected air duct diameter
dia.125
Weight
10,3
Heat recovery efficiency
79%
74%
70%
Heat exchanger type
Counterflow
Heat exchanger material
aluminium
6. TECHNICaL DaTa