Fume Exhaust Fans

12

Unit Start-Up

Visual Inspection of Equipment

The equipment type and arrangement should be verified 
as ordered at once when it arrives at the job site. When 
a discrepancy is found, the local Venco representative 
must be notified immediately so that corrective action 
may be investigated, also verify electrical conformance 
to specifications. Unauthorized alterations and 
unauthorized back charges will not be recognized by 
Venco Products.

After the unit has been assembled, installed and all 
utilities have been hooked up, the unit is now ready for 
operation.

Check

Before starting the unit, check the following:

  1.  Confirm that building supply voltage matches the 

voltage for which the unit is wired.

  2.  Check all piping and wiring penetrations made by 

contractors for water tightness. All penetrations 
must be made watertight to prevent water damage 
to the unit and building.

  3.  Rotate the fan wheel manually to be sure that it is 

free to operate. Remove any dirt or debris that may 
have accumulated during installation.

  4.  Check the fan bearing setscrews for tightness.

  5.  Check alignment of sheaves and V-belts (See 

maintenance section).

  6.  Inspect all fasteners to ensure that none have 

loosened during shipment.

  7.  Check flex coupling for proper alignment and 

connect between motor shaft and fan shaft (direct 
drive).

  8.  Check all guarding to ensure that it is securely 

attached and not interfering with rotating parts.

  9.  Check all electrical connections for proper 

attachment.

 10.  Check housing and ductwork, if accessible, for 

obstructions and foreign material that may damage 
the fan wheel.

 11.  Fill drainage piping trap.

WARNING

Disconnect and secure to the 

OFF

 position all 

electrical power to the fan prior to inspection or 
servicing. Failure to comply with this safety precaution 
could result in serious injury or death.

Additional Steps for Initial Start-Up

1.  Check for proper wheel rotation by momentarily 

energizing the fan. Access to view the wheel can be 
gained through the blower housing access panel.

 

One of the most frequently encountered problems 
are motors that are wired to rotate the wheel in the 
wrong direction. This is especially true with 3-phase 
installations where the motor will run in either 
direction, depending on how it has been wired. To 
reverse rotation of a 3-phase motor, interchange any 
two of the three electrical leads. Single phase motors 
can be reversed by changing internal connections as 
described on the motor label or wiring diagram. 

2.  Fans with multi-speed motors should be checked on 

low speed during initial start-up.

3.  Check for unusual noise, vibration or overheating of 

bearings. Refer to the “Troubleshooting” section of 
this manual if a problem develops.

4.  Grease may be forced out of the bearing seals during 

initial start-up. This is a normal self-purging feature 
for the type of bearing used on this product.

Содержание VJC-200

Страница 1: ...ny stationary objects 3 Motor must be securely and adequately grounded 4 Do not spin fan wheel faster than max cataloged fan RPM Adjustments to fan speed signi cantly effects motor load If the fan RPM...

Страница 2: ...e which is sealed to prevent the entry of blowing dust rain or snow Temperatures should be evenly maintained between 30 to 110 F 1 to 43 C wide temperature swings may cause condensation and sweating o...

Страница 3: ...age 2 3 Removing from Storage 3 General Information Unit and System Identification Tags 4 Pre Installation Information 4 Electrical Disconnects 4 Moving Parts 4 Guards Motor Cover Weatherhood 4 Access...

Страница 4: ...the fan cabinet Pre Installation Information Before installation it is important to be certain the mounting surface will bear the operating weight of the unit For proper unit operation it is also impo...

Страница 5: ...stallations Inlet Duct Turns Installation of a duct turn or elbow too close to the fan inlet reduces fan performance because air is loaded unevenly into the fan wheel To achieve full fan performance t...

Страница 6: ...epair section of this manual for details involving touch up of damaged surfaces Lift unit before mounting the stack to the fan body Use standard lifting and rigging practices ALL lifting brackets on e...

Страница 7: ...rate three common methods used to install roof curbs for fume exhaust systems Methods used to attach a unit are dependent on local codes roof construction design and roof construction materials Consul...

Страница 8: ...S equipment supports are designed for use on at roof decks to be mounted directly to the roof deck structure then roofed and ashed for weather tightness The orientation of the equipment support should...

Страница 9: ...osed Any increase in fan speed represents a substantial increase in load on the motor To avoid motor overheating and possible burnout motor load amperes should always be checked and compared to namepl...

Страница 10: ...ts and centering the cone ring on the wheel If additional adjustment is required to maintain a constant radial gap loosening the bearing bolts and centering the wheel is acceptable as a secondary opti...

Страница 11: ...al number for colors other than our standard TOUCH UP PAINT REPAIR KIT CONTENTS One pint of Kem Kromik primer including a technical data sheet One pint of industrial enamel including a technical data...

Страница 12: ...ck all guarding to ensure that it is securely attached and not interfering with rotating parts 9 Check all electrical connections for proper attachment 10 Check housing and ductwork if accessible for...

Страница 13: ...e entire fan should be checked for tightness 3 Any dirt accumulation on the wheel or in the housing should be removed to prevent unbalance and possible damage 4 Inspect fan impeller and housing lookin...

Страница 14: ...cy Do not exceed maximum class fan rpm of the wheel Belt Span De ection Belt Span 64 Recommended Bearing Lubrication Schedule Relubrication Schedule in Months Standard Grease Fan RPM Bearing Bore inch...

Страница 15: ...e nozzle preset at the factory based on the order Depending on installed air performance this nozzle can be adjusted in the eld to accommodate the building situation To increase the exhaust velocity a...

Страница 16: ...ers procedures for removal and installation 3 Before removing the bearing bolts make sure the shaft is supported slightly Remember to consider the wheel weight on the shaft 4 Remove both bearings from...

Страница 17: ...ake certain unit is not capable of operation during repairs CAUTION La pr sence d un moteur antid flagrant sur un ventilateur ne garantit pas que tout l appareil est antid flagrant Pour conna tre les...

Страница 18: ...optional curb cap inlet box and inlet flanges Stack Motor Cover Disconnect Switch Motor Plate Motor Integrated Mounting Rails Access Door Curb Cap Isolation Damper Roof Curb Scroll Housing Inlet Cone...

Страница 19: ...system Use correction factor to adjust for temperature altitude Resize ductwork Clean lters coils Change fan speed High Motor Amp Draw Fan Check rotation of wheel Reduce fan speed Duct System Resize...

Страница 20: ...______ AM PM Notes __________________________________________ ________________________________________________ ________________________________________________ ________________________________________...

Отзывы: