background image

Fume Exhaust Fans

9

NOTE

On the model VJI, the plug needs to be removed from 
threaded drain connection regardless of plans to pipe 
and trap.

Fan Drainage Piping and Trap Detail  

(by others)

Fans have been supplied with a drain. Drains are 
located at the underside of the scroll housing. The drain 
may need to be connected to a drainage system to 
ensure proper disposal of any water or condensate that 
may occur.

•  Drain connections are 1.0 inch MNPT  (model VJI)

•  

Installed piping to have a downward angle to allow 
for drainage

•  

Fill traps to recommended level before start-up

Note:

  A conservative method of trap design is to set  

N = total static pressure.

Check local codes for proper disposal of drain water 
which has been in contact with the exhaust air.

Positive Pressure Trap

N = Negative fan pressure (inches W.C.)
H = N - 0.5 inches minimum

H/2

H/2

H

1.25 inch 
minimum

N

FAN ON

FAN OFF

Connect 
this end 
to fan drain.

The adjustable motor pulley is set at the factory for 
the fan RPM specified by the customer. Fan RPM can 
be increased by closing or decreased by opening the 
adjustable motor pulley. Multigroove variable pitch 
pulleys must be adjusted an equal number of turns 
open or closed. Any increase in fan speed represents a 
substantial increase in load on the motor.

To avoid motor overheating and possible burnout, motor 
load amperes should always be checked and compared 
to nameplate rating when fan speed is increased.

Alignment of Pulleys and Belts

Check pulleys and belts for proper alignment to avoid 
unnecessary belt wear, noise, vibration and power loss. 
Motor and drive shafts must be parallel and pulleys in 
line as shown in Figure 1.

CORRECT

WRONG

WRONG

WRONG

Figure 1

V-Belt Drives

V-Belt Drive Installation

1.  Remove the protective coating from the end of the 

fan shaft using mineral spirits or another similar 
solvent. Check to ensure that the shaft is free of 
nicks and burrs.

2.  Slide sheaves on shafts. Do not drive 

sheaves on as this may result in 
bearing damage.

3.  Align fan and motor sheaves 

with a straight edge or string 
and tighten.

4.  Place belts over sheaves. 

Do not pry or force belts, as 
this could result in damage 
to the cords in the belts.

5.  Adjust the tension until the 

belts appear snug. Run the 
unit for a few minutes and allow the belts to “Set” 
properly.

6.  With the fan off and disconnect locked out, adjust 

the belt tension by moving the motor pivot plate. 
When in operation, the tight side of the belts should 
be in a straight line from sheave to sheave with a 
slight bow on the slack side.

Aligning Sheaves with 

a Straight Edge 

Содержание VJC-200

Страница 1: ...ny stationary objects 3 Motor must be securely and adequately grounded 4 Do not spin fan wheel faster than max cataloged fan RPM Adjustments to fan speed signi cantly effects motor load If the fan RPM...

Страница 2: ...e which is sealed to prevent the entry of blowing dust rain or snow Temperatures should be evenly maintained between 30 to 110 F 1 to 43 C wide temperature swings may cause condensation and sweating o...

Страница 3: ...age 2 3 Removing from Storage 3 General Information Unit and System Identification Tags 4 Pre Installation Information 4 Electrical Disconnects 4 Moving Parts 4 Guards Motor Cover Weatherhood 4 Access...

Страница 4: ...the fan cabinet Pre Installation Information Before installation it is important to be certain the mounting surface will bear the operating weight of the unit For proper unit operation it is also impo...

Страница 5: ...stallations Inlet Duct Turns Installation of a duct turn or elbow too close to the fan inlet reduces fan performance because air is loaded unevenly into the fan wheel To achieve full fan performance t...

Страница 6: ...epair section of this manual for details involving touch up of damaged surfaces Lift unit before mounting the stack to the fan body Use standard lifting and rigging practices ALL lifting brackets on e...

Страница 7: ...rate three common methods used to install roof curbs for fume exhaust systems Methods used to attach a unit are dependent on local codes roof construction design and roof construction materials Consul...

Страница 8: ...S equipment supports are designed for use on at roof decks to be mounted directly to the roof deck structure then roofed and ashed for weather tightness The orientation of the equipment support should...

Страница 9: ...osed Any increase in fan speed represents a substantial increase in load on the motor To avoid motor overheating and possible burnout motor load amperes should always be checked and compared to namepl...

Страница 10: ...ts and centering the cone ring on the wheel If additional adjustment is required to maintain a constant radial gap loosening the bearing bolts and centering the wheel is acceptable as a secondary opti...

Страница 11: ...al number for colors other than our standard TOUCH UP PAINT REPAIR KIT CONTENTS One pint of Kem Kromik primer including a technical data sheet One pint of industrial enamel including a technical data...

Страница 12: ...ck all guarding to ensure that it is securely attached and not interfering with rotating parts 9 Check all electrical connections for proper attachment 10 Check housing and ductwork if accessible for...

Страница 13: ...e entire fan should be checked for tightness 3 Any dirt accumulation on the wheel or in the housing should be removed to prevent unbalance and possible damage 4 Inspect fan impeller and housing lookin...

Страница 14: ...cy Do not exceed maximum class fan rpm of the wheel Belt Span De ection Belt Span 64 Recommended Bearing Lubrication Schedule Relubrication Schedule in Months Standard Grease Fan RPM Bearing Bore inch...

Страница 15: ...e nozzle preset at the factory based on the order Depending on installed air performance this nozzle can be adjusted in the eld to accommodate the building situation To increase the exhaust velocity a...

Страница 16: ...ers procedures for removal and installation 3 Before removing the bearing bolts make sure the shaft is supported slightly Remember to consider the wheel weight on the shaft 4 Remove both bearings from...

Страница 17: ...ake certain unit is not capable of operation during repairs CAUTION La pr sence d un moteur antid flagrant sur un ventilateur ne garantit pas que tout l appareil est antid flagrant Pour conna tre les...

Страница 18: ...optional curb cap inlet box and inlet flanges Stack Motor Cover Disconnect Switch Motor Plate Motor Integrated Mounting Rails Access Door Curb Cap Isolation Damper Roof Curb Scroll Housing Inlet Cone...

Страница 19: ...system Use correction factor to adjust for temperature altitude Resize ductwork Clean lters coils Change fan speed High Motor Amp Draw Fan Check rotation of wheel Reduce fan speed Duct System Resize...

Страница 20: ...______ AM PM Notes __________________________________________ ________________________________________________ ________________________________________________ ________________________________________...

Отзывы: