In addition to routine maintenance motor bearings will in the longer term require attention. If the motor 

bearings are greased through extended lubricators, a quality of grease should be periodically applied in 
accordance with the information on the fan or motor nameplate and/or instructions provided. 

 

 

 

 

9.  FAULT DETECTION 

It is necessary to turn off the fan before checking the fan and the system. During maintenance, device 

electrical connections should be cut entirely. All switches and circuit breakers should be locked by brought to 
the OFF position. Also “DO NOT START” sign should be placed on the control panel that will consistently 
stand. 

Check that the electrical connections to the unit are secure. Check that the voltage applied at the fan 

terminals is as specified on the motor nameplate, and is balanced. Measure the current on each phase (one 
phase in the case of single-phase motors) of the motor in turn and check that the current consumption is 
within the full load current specified on the motor nameplate. 

Rotate the motor shaft by hand. Investigate any sound of grinding noises, internal chaffing, rubbing or 

stiffness. Any observed defect may indicate that the bearings require lubrication or replacement. Ensure that 
all fixings are secure. Make sure that the fan blade is not blocked by an object, if fan is still not working, 
contact your supplier.  

 

 

 

10. WARRANTY 

  The warranty period starts from the date of delivery and it is for 2 years. 

  Including all parts of the entire fan is under warranty of our company. 

  The maximum repairing period is 30 business days. This period starts from the date of 

notification to us.  

  Fan's warranty does not include electrical connection errors, failures that may arise due to 

voltage and user errors.  

  The warranty is only valid under condition that the fan is assembled, operated and periodic 

maintenance to be made according to this manual.  

  For Atex-certified products, ATEX certification will be voided without repair written permission 

of the manufacturer and in cases of repair replaced with non-original parts. 

 

MAINTENANCE, REPAIR AND REPLACEMENT OF PARTS MUST BE CARRIED OUT 
BY ATEX TRAINED PERSONNEL. 

Содержание VD-EX

Страница 1: ...CE USER MANUAL WALL MOUNTED EXPROOF AXIAL FANS VENCO Havaland rma ve Makina San ve Tic A 2004 Cad No 5 45400 OSB Turgutlu MAN SA T RK YE Tel 0090 236 332 5070 Fax 0090 236 332 5030 www venco com tr ve...

Страница 2: ...d keep it Do not use devices as a workbench or a storage area VENCO VD EX Wall Mounted Axial Type Exproof Fans can only be operated in conditions of intended design and technical specifications DEVICE...

Страница 3: ...assified as a place in which an explosive atmosphere consisting of a mixture with air or flammable substances in the form of gas vapour or mist is likely to occur in normal operation occasionally Zone...

Страница 4: ...y whether the fan wheel runs freely Before installation check the minimum air gap between the blade tip and the housing according to the following table The fan can be mounted parallel to the wall wit...

Страница 5: ...2019 10 4 8 Sample pictures of the assembled device Fan Diameter VD EX Min mm Max mm 315 0 6 1 6 355 0 8 1 8 400 1 2 450 1 25 2 25 500 1 4 2 4 560 1 4 2 4 630 1 58 2 58 710 2 6 3 6...

Страница 6: ...fan has direct contact with the outside air a plastic damper must be used on the outer side of the outer wall to stop this contact for lightning protection ALL ELECTRICAL CONNECTIONS SHALL BE DONE ACC...

Страница 7: ...ar position after rotation When dismantling the crate to gain access to the fan assembly care should be taken to avoid injury from sharp edges nails staples splinters etc 8 MAINTENANCE Periodically ch...

Страница 8: ...full load current specified on the motor nameplate Rotate the motor shaft by hand Investigate any sound of grinding noises internal chaffing rubbing or stiffness Any observed defect may indicate that...

Страница 9: ...2019 10 8 8 ANNEX 11 1 Annex 1 Electrical Wiring Diagrams Motor connection without termic Motor connection with termic...

Отзывы: