6.  OPERATION 

Before starting, check the followings; Be sure that foreign objects are removed from fan area, check 
connection to the electrical installation, minimum air gap between the tip of the blade and the housing and no 
noise appears when starting the fan. If the air gap is correct, switch the device on and off briefly, in order to 
check the direction of rotation of the fan. The rotation direction of the fan must match up with the direction of 
the arrow on the housing of the fan. If the direction of rotation is wrong, interchange two phases in order to 
set the correct direction of rotation. If the wall to be installed is the outer wall and the fan has direct contact 
with the outside air, a plastic damper must be used on the outer side of the outer wall to stop this contact for 
lightning protection. 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

ALL  ELECTRICAL  CONNECTIONS  SHALL  BE  DONE ACCORDING TO  EN  60204-1 
BY TRAINNED AND AUTHORIZED PERSONNEL. 

 

 

SWITCH  THE  ENERGY  SUPPLY  OFF  BEFORE  YOU  BRING  ABOUT  THE 
ELECTRICAL  CONNECTION  OF  THE  FAN.  MAKE  SURE  THAT  THE  ENERGY 
SUPPLY  CANNOT  BE  SWITCHED  ON  AGAIN  PREMATURELY.  THE  ELECTRICAL 
CONNECTION MAY ONLY BE CARRIED OUT BY TRAINED PERSONNEL. 

 

THE  ELECTRICAL  CONNECTION  IS  TO  BE  DONE  ACCORDING  TO  VALID 
DIRECTIVES  AND  ONLY  BY  A  QUALIFIED  FITTER  WITH  MATCHING  SAFETY 
DEVICES FOR THE PROTECTION OF THE MOTOR. 

 

THE  DEVICE MUST  BE  EARTHED.  DEVICE GROUND  CONNECTION;  SHOULD  BE 
MADE OF EARTHING BOLT ON BODY. 

 

PAINT IS NOT USED IN THE DEVICE AND BODY.

 

IF PAINTING ON EQUIPMENT AND 

BODY IS USED, THE PAINT MUST BE ANTISTATIC. 

Содержание VD-EX

Страница 1: ...CE USER MANUAL WALL MOUNTED EXPROOF AXIAL FANS VENCO Havaland rma ve Makina San ve Tic A 2004 Cad No 5 45400 OSB Turgutlu MAN SA T RK YE Tel 0090 236 332 5070 Fax 0090 236 332 5030 www venco com tr ve...

Страница 2: ...d keep it Do not use devices as a workbench or a storage area VENCO VD EX Wall Mounted Axial Type Exproof Fans can only be operated in conditions of intended design and technical specifications DEVICE...

Страница 3: ...assified as a place in which an explosive atmosphere consisting of a mixture with air or flammable substances in the form of gas vapour or mist is likely to occur in normal operation occasionally Zone...

Страница 4: ...y whether the fan wheel runs freely Before installation check the minimum air gap between the blade tip and the housing according to the following table The fan can be mounted parallel to the wall wit...

Страница 5: ...2019 10 4 8 Sample pictures of the assembled device Fan Diameter VD EX Min mm Max mm 315 0 6 1 6 355 0 8 1 8 400 1 2 450 1 25 2 25 500 1 4 2 4 560 1 4 2 4 630 1 58 2 58 710 2 6 3 6...

Страница 6: ...fan has direct contact with the outside air a plastic damper must be used on the outer side of the outer wall to stop this contact for lightning protection ALL ELECTRICAL CONNECTIONS SHALL BE DONE ACC...

Страница 7: ...ar position after rotation When dismantling the crate to gain access to the fan assembly care should be taken to avoid injury from sharp edges nails staples splinters etc 8 MAINTENANCE Periodically ch...

Страница 8: ...full load current specified on the motor nameplate Rotate the motor shaft by hand Investigate any sound of grinding noises internal chaffing rubbing or stiffness Any observed defect may indicate that...

Страница 9: ...2019 10 8 8 ANNEX 11 1 Annex 1 Electrical Wiring Diagrams Motor connection without termic Motor connection with termic...

Отзывы: