Round Fire and Combination Fire Smoke Dampers

7

Temperature Response Device Connections

RRL:  

The RRL (resettable link device) incorporates a single thermostat. When the thermostat temperature is reached, 
the sensor interrupts power to the actuator and the actuator's spring return mechanism causes the damper to 
close. Refer to 

Figure 8

 for wiring of the RRL thermostat.

OCI

:  The OCI (open or closed indicator) option contains two single pole single throw switches used to indicate the 

damper blade position. The switches provide a positive open and closed signal and can be used in conjunction 
with remote indicator lights. Refer to 

Figure 9 

for wiring of the OCI option.

RRL /OCI

:  The RRL/OCI performs the function of an RRL and OCI (see description above). Refer to 

Figure 10 

for 

wiring of the RRL/OCI option.

TOR

:  The TOR (temperature override device) option incorporates two thermostats with fixed settings (usually 

165°F [74°C] and 350°F [177°C]). The primary sensor (the sensor with the lower temperature setting) can be 
bypassed by an external contact closure allowing the damper to reopen until the secondary temperature is 
reached (the sensor with the higher temperature setting). See 

Figure 11.

  

The TOR assembly contains two single pole single throw switches used to indicate damper blade position. 
The switches provide a positive open and closed signal and can be used in conjunction with remote indicator 
lights. See 

Figure 11

 for wiring of the TOR thermostats and indicator switches.

 

 If either the TOR or the RRL is ordered with a pneumatic actuator, an EP switch is required with an appropriate 
electric power circuit to allow the electric thermostat to control the pneumatic actuator.

Figure 8: RRL Wiring

Figure 9: OCI

Ratings (Figure 8, 9, 10, & 11)

Integral Switch Type:

 Single Pole, double throw

Electrical Capacity:

 10 Amps, 1/3 hp, 120 or 240 Vac 

 

 

1/2 Amp, 125 Vdc;  

 

 

1/4 Amp 250 Vdc 

 

 

5 Amps, 120 Vac “L” (lamp load) 

 

 

1.0 Amps, 24 Vac 

 

 

1.5 Amps, 24 Vdc

Temperature Limit:

 165° F (standard primary sensor) 

 

 

212° F (optional primary sensor) 

 

 

250° F (secondary sensor )* 

 

 

350º F (secondary sensor)* 

* based on actuator temperature rating

Figure 10: RRL/OCI

Figure 11: TOR

Содержание DFDR Series

Страница 1: ...eiving and Handling Upon receiving dampers check for both obvious and hidden damage If damage is found record all necessary information on the bill of lading and file a claim with the final carrier Ch...

Страница 2: ...terials include but are not limited to a Mortar dust b Drywall dust c Firesafing materials d Wall texture e Paint overspray 7 Damper should be sufficiently covered as to prevent overspray if wall text...

Страница 3: ...rs must meet the requirements of the appropriate wall design See UL Fire Resistance Directory and or local codes Figure 1 12 in 24 in o c Maximum Floor Runner 2 in Ceiling Runner 2 Panhead Screws 24 i...

Страница 4: ...assembly to allow for this expansion The wall floor opening must be a minimum of 7 8 in 22mm larger than the outside diameter of the damper Clearances Required Between Damper Sleeves and Wall Floor O...

Страница 5: ...ITION INDICATOR AND OR ELECTRIC LINK DUCT CONNECTION AREA 2 00 IN 1 50 IN Optional Second Retaining Plate Do not place retainer plate in this groove Figure 5 FSDR SEFSDR SSFSDR Inserting Damper into W...

Страница 6: ...p for easy installation when the clamping screw is loosened If necessary remove the clamping screw and nut see Figure 7 Position the retaining plate between the blade axle and the actuator shaft as sh...

Страница 7: ...ensor with the lower temperature setting can be bypassed by an external contact closure allowing the damper to reopen until the secondary temperature is reached the sensor with the higher temperature...

Страница 8: ...he latest editions of NFPA 80 90A 92 101 105 UL864 AMCA 503 03 and local codes Actuator manufacturer recommendations Damper Troubleshooting The following is a possible cause and correction list for co...

Отзывы: